Study on Shock Disinfection in a Fire Extinguishing Water Supply System

by 1, 2,3, 1, 1, 1,2 and 2,*
1
Institute of Building Fire Research, China Academy of Building Research, Beijing 100013, China
2
Department of Urban Construction, Beijing University of Technology, Beijing 100124, China
3
Beijing Municipal Commission of Housing and Urban-rural Development, Beijing 101100, China
*
Author to whom correspondence should be addressed.
Academic Editor: Helvi Heinonen-Tanski Academic Editor
Water 2021, 13(21), 2967; https://doi.org/10.3390/w13212967
Received: 26 September 2021 / Revised: 17 October 2021 / Accepted: 18 October 2021 / Published: 21 October 2021
(This article belongs to the Section Wastewater Treatment and Reuse)
The biofilms generated in a fire extinguishing water supply system can cause corrosion and a reduction in the water supply capacity; thus, degrading the system performance. To mitigate microbial corrosion, appropriate disinfection measures are necessary. In this study, the secondary addition of chlorine is employed to investigate the kinetics of chlorine decay, and shock disinfection is applied to investigate the removal efficiency of corrosion bacteria, and the microbial composition of a biofilm on the pipe wall was also clarified. The results show that the residual chlorine content in the secondary chlorination process was directly correlated with the decay rate of residual chlorine and the corrosion rate of the pipe wall. Additionally, the chlorine impact disinfection method could reduce the electrochemical corrosion phenomenon of the pipe wall. When the concentration of chlorine was 3 mg/L, the removal rate of corrosion bacteria was higher in 60 min than in 30 min. Specifically, most of the bacteria were inactivated in 60 min and the biofilm was severely damaged. Shock disinfection could significantly inactivate all microflora in the biofilm; the relative abundances of microflora varied significantly, while the change of microflora at the phylum level was insignificant. This study can provide theoretical support for the secondary addition of chlorine and shock disinfection in a fire extinguishing water supply system. View Full-Text
Keywords: fire extinguishing water supply system; stainless steel pipeline; microbial corrosion; biofilm; shock disinfection fire extinguishing water supply system; stainless steel pipeline; microbial corrosion; biofilm; shock disinfection
Show Figures

Figure 1

MDPI and ACS Style

Xiang, K.; Geng, P.; Sun, X.; Yuan, S.; Du, P.; Li, X. Study on Shock Disinfection in a Fire Extinguishing Water Supply System. Water 2021, 13, 2967. https://doi.org/10.3390/w13212967

AMA Style

Xiang K, Geng P, Sun X, Yuan S, Du P, Li X. Study on Shock Disinfection in a Fire Extinguishing Water Supply System. Water. 2021; 13(21):2967. https://doi.org/10.3390/w13212967

Chicago/Turabian Style

Xiang, Kun, Pan Geng, Xuan Sun, Shasha Yuan, Peng Du, and Xing Li. 2021. "Study on Shock Disinfection in a Fire Extinguishing Water Supply System" Water 13, no. 21: 2967. https://doi.org/10.3390/w13212967

Find Other Styles
Note that from the first issue of 2016, MDPI journals use article numbers instead of page numbers. See further details here.

Article Access Map by Country/Region

1
Back to TopTop