A Performance-Based Methodology for Retrofitting Buildings Guided by Visual Comfort

,
,
,
,
and
1
Department of Architecture, Built Environment and Construction Engineering, Politecnico di Milano, Via Ponzio 31, 20133 Milan, Italy
2
Department of Building Architecture, Universitat Politècnica de València, Campus de Vera, Camino de Vera, s/n, 46022 Valencia, Spain
*
Author to whom correspondence should be addressed.

Abstract

Extensive glazing is a common feature of modern buildings, intended to maximize daylight and strengthen visual connections with the outdoors. While this strategy can enhance energy performance, its effectiveness strongly depends on climate, orientation, and seasonal variations, and it often introduces challenges related to visual comfort, particularly glare. This paper proposes a refurbishment methodology that systematically integrates the view out, often neglected in current practice, into the decision-making framework, focusing on its relationship with daylight. The methodology follows a stepwise process encompassing the identification of discomfort conditions, evaluation of intervention feasibility, and design of targeted refurbishment strategies. Its main innovation lies in integrating and verifying a balance between view quality and daylight within a unified analytical framework. Validation through a university building in València confirmed that optimizing these parameters represents a significant design challenge, as enhancing one may compromise the other. The analysis also revealed limitations of current standards, such as EN 17037, whose static approach fails to capture the dynamic interactions among daylight, shading operation, and user perception. Furthermore, the proposed methodology introduces a scalable level of analytical granularity, enabling the assessment depth to be adapted to economic resources and time constraints, thereby supporting informed and sustainable decisions in building refurbishment.

1. Introduction

Extensive glazing has become a recurrent feature in contemporary architecture, supported by the intention to enhance daylight and improve visual connection with the outdoors [1]. Large glazed areas are often associated with increased natural light availability and access to views, two factors that are widely recognized as contributors to occupant comfort and well-being [2]. However, this design strategy introduces additional layers of complexity through cross-domain dependencies, where actions aimed at enhancing daylight availability and view quality may have significant implications, for example, regarding energy performance [3], thermal comfort [4], and visual comfort itself, as increased daylight penetration can concurrently elevate the risk of glare.
Post-occupancy evaluations in office and commercial spaces indicate that glare from windows is among the most frequent sources of visual discomfort [5]. Operational aspects can further affect the occupant’s experience. Automated daylighting and shading systems are increasingly applied to optimize daylight performance, yet studies have reported that malfunctions or over-responsiveness may generate user dissatisfaction, occasionally prompting manual overrides [6].
Similar conditions are observed in educational environments, where large, glazed façades and skylights provide daylight and open views but may also create glare. Field studies in libraries and classrooms have documented cases of visual discomfort, particularly when direct sunlight is not adequately controlled [7].
In essence, integrating a visual environment that successfully reconciles luminous and visual aspects can be challenging, particularly in buildings where these qualities were not effectively addressed during the initial design phase. When post-occupancy evaluations reveal persistent discomfort due to glare or inadequate view conditions, retrofit interventions are necessary to restore a balanced relationship among daylight provision, visual comfort, and outward visibility. However, in practice, refurbishment decisions often address these factors separately, with limited coordination between glare management and the preservation of views out. This lack of integration can reduce the overall effectiveness of retrofit actions, especially when multiple comfort and performance criteria must be satisfied simultaneously. To respond to this issue, the present study introduces a stepwise methodology that systematically incorporates both luminous and view-related aspects into the retrofit design process. The proposed framework, structured around the identification of discomfort conditions, the evaluation of intervention feasibility, and the design of targeted refurbishment strategies, provides a coherent stepwise approach to improving visual comfort while maintaining perceptual connection with the outdoor environment.
Recent research increasingly demonstrates that multi-objective optimization frameworks are essential for resolving the trade-offs among daylight provision, glare control, sunlight exposure, and the view out, often including energy efficiencies. Options that could enhance an optimal breakeven are dynamic and adaptive shadings, such as kinetic louvers, smart blinds, and photovoltaic-integrated devices, which can outperform static overhangs and fins by enabling real-time responses to solar and sky conditions [8,9]. In parallel, orientation- and climate-sensitive optimization of classroom envelopes has shown that vertical eye-level illuminance and circadian-related metrics can shift optimal design solutions toward northeast-oriented openings that balance visual, energy, and non-visual health performance [10]. A comprehensive review by Alsukkar et al. [11] synthesizes these advances, reporting that optimized shading systems can enhance annual energy savings and thermal comfort and, in terms of visual performance, glare and daylight provision can be effectively improved. Collectively, these findings reinforce the need for analytical frameworks that are capable of systematically integrating all the variables involved to guide the decision-making process.

1.1. View Out Relevance

As people typically spend more than 90% of their lives indoors [12], providing a satisfying view out is a good strategy to increase their comfort. Specifically, as highlighted by Lottrup et al. [13], satisfaction with views in office environments, especially those incorporating natural features, is linked to higher productivity and job satisfaction, contributing to an overall sense of comfort for occupants. The relevance of views spans various settings, such as hospitals [14], correctional facilities [15], and educational institutions [16].
From a healthcare standpoint, having visual access to outdoor scenes can offer “restorative mini-breaks” that alleviate visual fatigue [17]. Shifting the gaze between nearby tasks, such as using a computer, and distant natural views creates a soothing effect for the eyes [18]. In a broader sense, expansive and aesthetically pleasing views can support both physical health and psychological well-being [19]. Exposure to natural elements has been associated with numerous health benefits, including reduced diastolic blood pressure [20], lower levels of depression [21], anxiety [22], and stress [23], improved concentration and psychological health [24], and faster recovery rates [25]. Moreover, Heschong and Saxena [26] demonstrated that access to views from workspaces could improve memory and cognitive performance by 10% to 25%.
In educational contexts, visual access to nature also plays a key role in enhancing cognitive function. Zhang et al. [27] explored how natural views influence student mood and learning capacity by correlating self-reported experiences with physiological data gathered through electroencephalogram (EEG) monitoring. Similarly, Benfield et al. [28] observed that students exposed to more appealing views tended to achieve higher final grades. Jang et al. [29] further confirmed these benefits through experiments conducted in virtual environments, supporting the adoption of such design strategies in line with human-centered design principles. Within university classrooms, Kim and Wineman [30] noted a preference for seats near windows, as proximity to better views was associated with greater psychological comfort.
The nature of the landscape visible through windows also greatly affects occupants’ perceived comfort. Studies indicate that views of natural settings, especially those including green areas [31] and water elements [32], positively impact well-being and comfort. Conversely, views of unattractive urban environments or busy roads tend to have negative effects, often due to concerns related to air pollution, reduced air quality, and increased noise [33].

1.2. Daylight–View Out Relation

The literature addressing the relationship between daylight and outdoor views suggests that, although a connection exists, it remains insufficiently understood [34]. This complexity is due to the numerous variables influencing visual comfort, as well as the dynamic interaction between daylight and views [35]. For instance, the perception of a view can be altered by light levels or by the specific activity taking place during the view evaluation [36].
Windows are a key architectural element that simultaneously provide daylight access and outdoor views, shaping not only the visual comfort, but also the psychological, cognitive, and circadian responses of building occupants. Over the last two decades, research has expanded beyond purely photometric aspects of daylight to encompass the broader interaction among daylight quality, glare, and view content, highlighting their combined impact on comfort, health, and performance [37].
Systematic reviews have shown that studies of human responses in indoor environments have often concentrated on artificial lighting parameters and window characteristics, while giving less attention to the combined role of daylight and outdoor views [38]. In many cases, the interaction between these two factors has not been fully explored, which makes it difficult to clearly interpret user responses. Nonetheless, evidence suggests that, when daylight is effectively managed and paired with unobstructed views, it can foster better decision-making, support stress recovery, and enhance attentional capacity [38].
From a perceptual perspective, view quality is shaped by both content (e.g., preference for natural over urban scenes or artistic and historical points of interest) and composition, such as the horizontal layering of sky, landscape, and ground [39]. Importantly, the acceptance of glare is not only a function of photometric thresholds, but also of interest in the view: glare is perceived as less disturbing when associated with engaging or restorative outdoor scenes, particularly those containing greenery or water elements [35,39,40]. This effect appears to moderate discomfort in the short term, although it is not sufficient to fully offset the impact of glare.
This interaction highlights a fundamental trade-off: maximizing daylight penetration and view clarity often increases the risk of glare [40,41]. Recent computational workflows for EN 17037 [42], even though they show relevant limitations [43], have reinforced this point, showing that requirements for “exposure to sunlight” should be assessed together with “protection from glare,” as both criteria directly inform shading design strategies [44]. Post-occupancy evaluations confirm that occupant satisfaction is highest when windows provide both abundant daylight and multi-layered, natural views, suggesting that daylight and view are not additive, but synergistic, in shaping comfort and satisfaction [45].

1.3. Actual Standard Framework

Among the available standards and sustainable building protocols, EN 17037 and the LEED protocol are presented here, as they are among the most widely adopted frameworks in the field of daylight and visual comfort assessment.
The European Standard “EN 17037—Daylight in Buildings” [42] establishes a structured approach to evaluating daylight in indoor environments, with the aim of supporting occupant health, comfort, and well-being. It addresses four core aspects of daylight performance: daylight provision, view out, exposure to sunlight, and protection from glare. In relation to the view out, the standard proposes, as for the other aspects, an evaluation method that classifies spaces into three performance levels: minimum, medium, and high. This assessment is based on the horizontal sight angle, the viewing distance, and the presence of multiple layers in the visual field, reflecting both the extent and the quality of the outdoor view. For daylight provision, EN 17037 defines target illuminance values and their availability across occupied spaces, linking the quantity of daylight to its usability for daily activities, and a minimum sunlight exposure, whereas for glare, the standard proposes an assessment methodology based on daylight glare probability (DGP). The reference values considered for analysis in this study are reported in Table 1.
Table 1. Level of compliance with daylight provision, view out, exposure to sunlight, and glare standards, according to EN 17037.
Regarding LEED, version v4.1 [46], the most used in the last years, and v5, the latest one (April 2025) [47], have been considered by analyzing the criteria for points assignment for the Building Design and Construction section of the protocol. For daylight, the protocol requires compliance with either simulation-based or measurement-based criteria. Using simulation, spaces must achieve a minimum spatial daylight autonomy (sDA) and an annual sunlight exposure (ASE). Regarding views, LEED grants a maximum of one point if at least 75% of the regularly occupied floor area has direct views through glazing with a visible light transmittance (VLT) above 40%. Views must include nature, urban landmarks, art, or objects located at least 7.5 m beyond the glazing line and must be directly accessible to occupants. Concerning glare, LEED suggests the installation of shading devices that can properly avoid potential issues. A complete and detailed collection of the LEED v4.1 and LEED v5 requirements is provided in Table 2.
Table 2. LEED v4.1 and v5 building design and construction criteria for daylight and the view out.
In this regard, it is worth mentioning other guidelines often listed alongside the presented references, such as the BREEAM (Building Research Establishment Environmental Assessment Method) standard [48] and the WELL Building Standard [49]. In this context, these are considered to be largely encompassed through the substantial overlap of metrics and indices across these frameworks. For example, the BREEAM standard, within the Health and Wellbeing category, includes section HEA 01—Visual Comfort, which provides an evidence-based framework for assessing appropriate daylight availability, glare control, and quality of view. Daylight assessment explicitly recognizes EN 17037 as an equally valid alternative reference framework [50]. Adequacy of view is evaluated based on criteria such as minimum view distance from the window and target window-to-wall ratio thresholds [51]. Glare mitigation, in turn, is primarily assessed through the provision of appropriate glare control systems, such as external or internal shading devices, in relevant occupied spaces [52]. Similarly, the WELL Building Standard addresses daylight, glare, and view design within the Light and Mind concepts. The assessment criteria in the Light concept show partial overlap with other standards, such as LEED, particularly regarding daylight availability and glare control, which are analyzed via consolidated metrics such as sDA or the presence of glare protections [53]. In contrast, access to views is primarily addressed under the Mind concept, within the feature titled M09—Enhanced Access to Nature. This feature contributes one point toward the Mind score if the requirements are met. Specifically, at least 75% of workstations and seating areas on each floor must have a direct line of sight to one of the three targets: indoor plants, water features, or natural outdoor views [54]. The system does not provide a complementary target for visual quantity, for example, how much of the field of view is covered by those elements. Therefore, the requirements can be deemed acceptable even in the presence of few visible elements.

2. Methodology

To address challenges of visual comfort in building renovation, this study introduces a structured, decision-oriented framework for retrofit interventions aimed at balancing daylight provision, view quality, exposure to sunlight, and glare control. Rather than a strictly linear workflow, the method is conceived as an oriented catalogue, in which each procedural step is associated with a curated set of methodological options.
The approach is articulated into a sequence of logically connected steps. Within this structure, the oriented catalogue focuses attention on three critical actions that represent core aspects of the performance-oriented design paradigm: (i) methods for detecting visual discomfort conditions; (ii) the definition of key performance indicators (KPIs) capable of supporting retrofit action planning; and (iii) the evaluation and validation of potential retrofit intervention options. The methodology is then validated through its application to a real case study at the Universitat Politecnica de València (UPV), illustrating how it can be translated into practical design and refurbishment strategies.

Proposed Workflow

The structure and content of the oriented catalogue are further detailed in this section, clarifying its role as a decision-support tool through the articulation of three core components, hereafter referred to as steps, that characterize the critical actions of the performance-oriented design process. The first step in this process, hereafter referred to as Step 1, consists of an array of discomfort identification methods intended to support the detection and characterization of both the presence and nature of visual discomfort within the building. This section of the oriented catalogue encompasses (i) direct input from the building manager regarding observed visual discomfort conditions; (ii) feedback derived from occupant surveys; (iii) results obtained from in situ measurements; and (iv) outputs from performance-based simulations of the building’s visual environment. In this regard, the building manager’s assessment is the fastest and least complex approach, as it relies on observations from existing personnel, without the need for specialized equipment. However, it reflects the perception of a single individual and may only partially capture the actual user experience. By contrast, the remaining three methodologies should be regarded as expert-based approaches, as their implementation requires professionals with an appropriate level of technical competence in the respective assessment methods.
The use of occupant surveys provides direct feedback from users, making them the most reliable method for understanding perceived discomfort. However, its main drawback lies in the time required for survey design, distribution, data collection, and subsequent statistical analysis. Next, through on-site measurements, it is possible to deliver objective data on parameters such as illuminance, luminance contrasts, and view access. Nevertheless, these measurements may not fully capture subjective occupant perception and often need to be repeated over multiple time periods to provide a more comprehensive and representative assessment of visual quality throughout the building’s operational use. They also require a medium-to-high investment in hardware (e.g., lux meters, luminance cameras) and trained personnel to operate instruments and interpret data.
Finally, the use of software simulations makes it possible to predict discomfort conditions in different design or operational scenarios. Their reliability depends on the accuracy of the model and its assumptions. They require moderate to high investments in time, specialized software licenses, and skilled operators with expertise in building performance modelling.
Beyond listing assessment methodologies, the oriented catalogue qualitatively indicates the potential of each option to generate input data that can be carried forward to subsequent stages of the retrofit planning process, in addition to its primary visual discomfort assessment output. For example, the execution of building performance simulations to identify visual discomfort conditions requires expert practitioners to collect detailed building and site data, which can subsequently be reused in later planning and design actions, thereby reducing the need for additional data integration. By contrast, interventions based on the building manager’s assessment, which rely on a lower application of evidence-based analytical procedures, may yield limited contextual data and consequently increase the need for further building and site data integration in subsequent phases.
Once the main visual discomfort issues have been identified, it becomes necessary to assess whether a minor or major retrofit intervention is required and, in the latter case, whether such a major retrofit can be realistically implemented. In cases where major modifications are not feasible, alternative lean strategies should be considered. These may include soft and low-cost actions aimed at improving the livability of the space, such as regrouping, altering the internal functional layout of the building, or promoting user education to encourage adaptive behaviors.
Once the feasibility of intervention has been established, Step 2 focuses on the selection of KPIs that form the basis for retrofit strategy evaluation and design. Essentially, this step follows Step 1 only when the target space is deemed suitable for refurbishment, taking into account enabling conditions such as building management approval, regulatory and permitting constraints, and budget availability. The primary objective of this step is to define an evaluative framework that supports an evidence-based, performance-oriented design process aimed at addressing the visual quality issues identified in the target space. Accordingly, the oriented catalogue associated with Step 2 presents a structured set of metrics, reference metrics, and indices organized in relation to contextual and design factors. As the data required to implement the selected KPIs may differ from or extend beyond those potentially carried over from Step 1, this phase also entails identifying and acquiring any additional information necessary to support subsequent analyses.
The elements listed within Step 2 of the oriented catalogue are derived from multiple reference sources. In particular, the EN 17037 standard and the LEED protocols (v4.1 and v5) are adopted due to their comprehensive coverage of widely used daylight, glare, and view-related KPIs.
Step 2 of the oriented catalogue provides a structured articulation of performance indicators intended to support retrofit strategy definition through a matrix-based organization of KPIs. Indicators are first classified into four thematic groups according to their domain of application, daylight, view out, exposure to sunlight, and glare, reflecting the main dimensions of visual quality addressed in the performance-oriented design process. Within each thematic group, KPIs are further arranged across four increasing levels of analytical detail, numbered from Level 0 to Level 3, which collectively express the information density, analytical effort, and decision support potential associated with each metric. Level 0 includes KPIs derived from geometric analysis and statistical inference, such as binary or descriptive indicators (e.g., window access) and simplified exposure metrics (e.g., hours of direct sunlight). This level can also host metrics and indexes derived from mandatory national legislation; however, because these regulatory rules can vary significantly depending on the country where the catalogue is applied, the referenced information should be adapted to the specific application site. For reference, we cite Italian legislation, which mandates the application of simple geometric assessments for visual quality and, in particular, daylight compliance (e.g., WFR, window-to-floor ratio, >1/8 for Italy provided by the Ministerial Decree 5 July 1975 [55]). Other countries differ in how they regulate natural light: for example, the Spanish Código Técnico de la Edificación [56] is a mandatory national building code that does not directly prescribe specific daylight performance metrics such as daylight factor thresholds, but it does require buildings to incorporate daylight in indoor spaces and may be complemented by regional habitability decrees that set minimum opening sizes relative to room area or other parameters to ensure adequate natural lighting conditions.
Level 1 introduces physics-based static analyses, based on point-in-time assessments of specific visual phenomena; at this level, the catalogue exhibits the highest diversity of view out–related KPIs, reflecting the multiplicity of descriptors applicable to visual connection with the exterior. Level 2 encompasses dynamic performance indicators that require the analysis of extended temporal domains, typically over seasonal or annual periods, enabling a more comprehensive characterization of daylight provision, sunlight exposure, and glare occurrence. View out metrics are not associated with Level 2, due to the lack of widespread dynamic analysis. This issue will be discussed in subsequent paragraphs. Finally, Level 3, denoted as “beyond regulation,” groups KPIs derived from advanced or emerging research approaches, which may be either static or dynamic in nature and are distinguished by their higher implementation complexity, as they often rely on specialized expertise, advanced hardware, or custom computational workflows.
In this regard, the metrics currently listed under Level 3 in the oriented catalogue are not intended to constitute a comprehensive review of innovative assessment approaches; rather, they serve to demonstrate the extensibility of the framework and to reserve a conceptual space for the integration of emerging or case-specific performance indicators. As an illustrative example, Level 3 includes selected advanced metrics across the four visual domains. Within the daylight domain, melanopic equivalent daylight illuminance (mEDI) [57] is introduced as an emerging indicator that links daylight evaluation with non-visual, biologically mediated human responses. For exposure to sunlight, sunlight autonomy (SA) [58] is included as a dynamic metric that assesses the adequacy of sunlight availability over defined temporal periods. In contrast, the glare and view out domains at this level are represented through more generic analytical frameworks, oriented toward case-dependent applications, such as three-dimensional perceptual analysis for view out evaluation.
Finally, all elements listed within the Step 2 catalogue are further classified according to the technical constraints required for their implementation. These constraints describe the methodological prerequisites associated with each KPI, including the need for conventional or specialist hardware, the availability of software tools capable of supporting their calculation, and the potential requirement for custom scripting or advanced computational workflows. In addition, the catalogue qualitatively indicates the type and level of contextual data required to implement each metric. In this respect, distinctions are made between KPIs that can be evaluated using simplified geometric representation, such as building and site massing models and basic spatial references (e.g., sunpath information), and those that require more detailed characterization of building and site properties, including the optical characteristics of materials and the use of typical weather datasets to determine climatic variability.
The integration of these parameters, evaluated at different intervention levels, ensures that retrofit strategies are both measurable and verifiable, while maintaining a direct link to user comfort and well-being. In this sense, the goal of Step 2 is to select and define the evaluation system that will guide the subsequent phases of the process. The choice made at this stage determines the reference framework against which actions are developed, influencing the level of detail, scope, and granularity of the analyses to be performed.
Finally, Step 3 requires the validation of specific design proposals derived from the refurbishment strategy consolidated between Step 2 and Step 3. Within the methodological framework defined in the previous stage, this phase applies the selected evaluation system to assess a narrower set of targeted intervention options, which may address transformative actions at different levels, including modifications to the functional layout of the target space, changes to its spatial configuration, or improvements to the performance of technological elements. Similar to the previous steps, the oriented catalogue supports Step 3 by presenting a structured set of alternative validation processes aimed at verifying the outcomes of the proposed retrofit strategy. Validation options are grouped into three main categories based on the aspect under which the retrofit strategy is assessed: (i) aesthetic quality, addressing perceptual and experiential attributes of the intervention; (ii) performance, verifying compliance with visual comfort requirements and performance targets; and (iii) cost-effectiveness, evaluating the economic feasibility and value of the proposed solutions. As with the previous steps, the content of Step 3 within the oriented catalogue is intentionally flexible, as the present contribution focuses on refining its underlying structure, while future extensions and updates are explicitly anticipated as part of the framework’s ongoing development.
As the aim of the catalogue is to guide selection through fitness-based criteria, the validation methods listed under Step 3 are further characterized by associating each entry with a set of validation process features. These features enable rapid and comparative reading of each validation method’s characteristics, with reference to procedural constraints related to implementation and to their effectiveness in relation to specific objectives or design stages. In particular, validation process features describe (i) execution stage, indicating the phase of the design or retrofit process in which the validation method is most effective; (ii) hardware constraints, identifying required equipment or instrumentation beyond traditional PC hardware and software; (iii) external dependencies, specifying whether the validation process relies on mandatory external inputs, such as users/occupants test groups; (iv) the strategic driver, outlining the primary intent and focus of the validation method; and (v) output granularity, indicating whether the resulting output is suitable for preliminary screening or qualitative assessment, predictive simulation of specific conditions, or in situ verification of previously established assumptions.
Among the validation options included in the catalogue, qualitative aesthetic assessment represents the most immediate approach, relying on expert judgement to evaluate spatial coherence, material compatibility, and visual integration of the proposed intervention. At more advanced levels, virtual reality (VR)-based methods support contextual user assessments through surveys or perceptual feedback tracking using biometric tools, enabling deeper investigation of experiential and perceptual responses before implementation. Performance-oriented validation methods include simulation-based compliance checks against visual comfort requirements and in situ visual comfort measurements, which respectively support predictive verification and post-intervention confirmation of achieved performance. From an economic perspective, validation methods range from capital and maintenance cost analyses to return-on-investment (ROI) and life cycle cost (LCC) evaluations, with extended approaches, such as productivity and well-being ROI analyses, allowing potential indirect benefits of improved visual environments to be considered. The proposed catalogue is presented in Figure 1.
Figure 1. Proposed catalogue for a retrofit strategy based on visual comfort.
Overall, the oriented catalogue functions as a structured decision-making aid that supports retrofit design by aligning assessment methods, performance indicators, and validation strategies within a coherent, performance-oriented framework. By linking analytical depth, data requirements, and implementation constraints to specific decision contexts, the catalogue enables informed and adaptable choices throughout the retrofit process, while preserving flexibility to accommodate project-specific conditions and future methodological extensions.
In the following sections, the practical applicability of the oriented catalogue is demonstrated through its implementation within a case study, illustrating how the proposed structure can effectively guide retrofit decision-making in real design scenarios.

3. Case Study Description, Modelling, and Analysis Set-Up

3.1. Context and Building Description

The case study is Building 1C of the UPV, a teaching and administrative facility belonging to the School of Building Engineering and located on UPV’s Campus de Vera (Camí de Vera s/n, València). The building is surrounded by a park and small buildings on the university side, on the other side, a large street with trees and residential facilities is present. The analyzed building and its surroundings are shown in Figure 2.
Figure 2. (a) Model of the analyzed building and its context from the top; (b) Aerial view of the analyzed area from Google Earth [59].
In this context, the building retrofit design process is initiated by the reporting of visual discomfort by the building manager (Step 1). This distress report is qualitative in nature and merely indicates that the building fails to ensure adequate visual comfort conditions. However, it does not provide sufficient information to assess the severity of the discomfort, nor does it specify its spatial distribution within the building or its temporal occurrence. Consequently, this initial qualitative evidence must be complemented by additional data to enable comprehensive evaluation of the problem.
In this regard, the building presents single windows with no shading devices on the whole first floor, whereas the upper floors have
  • single windows on the south façade, with no internal and external shading devices;
  • single windows on the north façade, with external inclinable lamellas and no internal shading devices;
  • wholly glazed façades on the east and west sides, three façades per side, with fixed external horizontal shadings and no internal shading devices;
  • single windows on the north-east corner, with external inclinable lamellas and no internal shading devices.
To better characterize the relationship between the glazed and opaque parts of the building envelope, the window wall ratio (WWR) is indicated for each façade: north is 22%, south is 11%, east is 64%, and west is 59%. A complete overview of the glass distribution in the building faces is presented in Appendix A, where the four elevations of the building are reported. To also gain a more quantitative comprehension of this distribution, a map of the building floors reporting the window-to-floor ratio of the analyzed spaces has been reported in Appendix B.

3.2. Building Modelling

The building was modelled in Rhinoceros 7, and analyses were carried out in accordance with the EN 17037 standard, using the ClimateStudio (CS) [60] and Ladybug (LB) tools [61]. To simplify the model and reduce the computational effort, the main elements (walls, floors, and windows) were represented as planar surfaces, while the horizontal fixed shadings of the curtain walls were modelled in 3D. Since no specific technical documentation on the building’s materials was available, reference materials from a standard database (Table 3) were adopted after visual inspection of the analyzed spaces, specifying the main material properties of both transparent materials (visual light transmittance (VLT), visual light reflectance (VLR), solar factor (SF) and u-value) and opaque materials (roughness, VLR).
Table 3. Material properties assigned in CS.
All glazed components were modelled as double clear glass with an argon-filled gap. As no technical information could be retrieved, optical properties were estimated with the AGC glass configurator [62], assuming a low-e coating on the internal cavity side, based on an assessment of light transmittance obtained after on-site illuminance measurements. Illuminance measurements were taken using a Minolta T-10 illuminance meter with a basic accuracy of ±2% for reading the ±1 digit [63].
The surrounding context was also considered, as vegetation significantly affects both daylight and view quality. Trees were positioned in the green area between the School of Building Engineering and the School of Architecture, as well as along the street adjacent to the building. The Acer platanoides species was selected due to its morphological similarity to the existing orange trees. The analyzed building and a comparison between the model and the real building are shown in Figure 3.
Figure 3. (a) Analyzed building; (b) East elevation of the model; (c) East elevation of the real building; (d) Building floors plans; (e) Layout and dimensions of the test space; (f) View from the test space.

3.3. Retrofit Solutions Selection and Modelling

In order to frame the intervention within a realistic design context, the most common shading retrofit solutions were first reviewed and comparatively discussed to establish a general understanding of their expected impacts. Each option was considered according to three key aspects that guide the validation of retrofit measures proposed in the third step of the methodology discussed in the present study. Aesthetic implications, cost-effectiveness, and performance have indeed been analyzed to obtain a comprehensive overview of the potential outcomes and constraints associated with different types of interventions. Specifically for the performance section, the reported analyses are qualitative for daylight provision, view out, and sunlight exposure, aiming to highlight the most relevant parameters impacting the specific daylight aspect. For glare, “very little” to “very good” effects are reported, following the classification recalled in EN 17037. Internal roller and venetian blinds and external louvres and overhang have been examined, and the comparison is shown in Table 4. This process effectively enables assessment of whether a major retrofit intervention can be considered, while simultaneously supporting the definition of a preliminary set of feasible design solutions to be further developed in subsequent planning stages. The overall evaluation mirrors, at a reduced scale, the analytical logic of later design phases and draws on the catalogue content associated with both Step 2 and Step 3. It provides a qualitative appraisal of the applicability and limitations of available intervention strategies with respect to the four primary domains of visual comfort (daylight availability, view out, exposure to sunlight, and glare control), while also accounting for additional aspects relevant to the validation of retrofit strategies.
Table 4. Comparison of the different retrofit options for shading system installation.
Based on the comparative analysis, internal roller blinds were identified as the most suitable refurbishment strategy for the analyzed case study. From an aesthetic perspective, this solution ensures minimal visual impact, as it is installed entirely within the interior space and does not alter the external appearance of the façade; this aspect was particularly relevant given that no modification of the building elevations was intended. In addition, roller blinds represent a widely adopted and effective solution for mitigating glare and managing daylight-related issues, allowing for a uniform reduction of direct solar radiation while maintaining adequate daylight provision. Their use effectively reduces problems associated with indirect glare, but discomfort caused by direct glare, occurring when the sun is clearly present within the visual field, may persist in the case of transparent fabric [64]. The system also provides direct user control, which has been widely recognized in the literature as a key factor in improving occupants’ visual comfort and satisfaction with indoor environmental conditions [65]. From a cost-effectiveness standpoint, internal roller blinds offer the most advantageous balance between performance and economic feasibility, due to their low installation cost, ease of implementation from the interior, and limited indirect costs associated with cleaning and maintenance.
To address their efficacy against both direct and indirect glare, two specific design options, referred to as Option 1 and Option 2, a transparent and an opaque one, have been modelled and analyzed. Option 1 is a gray transparent blind (shading material in CS: Satine Charcoal), with “very little effect” on glare control, as indicated by CS, whereas Option 2 is opaque, with a “very good effect” on glare control (shading material in CS: Sunshadow—3000 NET 1 N901 Charcoal/Charcoal). CS standard blinds materials have been selected, and the blinds have been placed on the inner side at 5.08 cm from the window. The analysis of these two different options allows us to evaluate the impact of blinds with different permeability on the view, in addition to their impact on glare control. The correlation between the blind material and the quality view has been discussed by Konstantzos et al. [66], who defined the view clarity index to evaluate this factor. The blinds are activated by an automated control, triggered when the direct normal illuminance exceeds 2000 lux, consistent with the UDI range. The control logic is based on virtual illuminance sensors positioned at a permissible depth of 1.5 m from the window, in accordance with ClimateStudio settings. Illuminance is evaluated at an interior point located within the space but projected onto the work plane. When the calculated illuminance at this point exceeds the activation threshold, the dynamic shading of the corresponding window is triggered for that hour. This approach replicates the behavior of a potential real-world automated shading system based on local illuminance sensors such as an IoT-based local control setup [67]. The blinds’ features are reported in Table 5, alongside an average cost, which includes the installation cost.
Table 5. Internal blind properties. Cost sources: [68,69].

3.4. Analysis Set-Up

The case study building was analyzed using a selected set of components extracted from the Step 2 catalogue, focusing exclusively on spaces characterized by continuous occupant presence and direct access to daylight, while excluding circulation areas such as corridors. The building analysis has been carried out using CS (v2.0.9012.26837) and LB Tools (v1.8.0), the EPW TMYx 2004–2018 of Valencia as the reference weather file for the analyses under climate-based sky, and an occupation schedule of the spaces that goes from 8 a.m. to 6 p.m. For the CS analyses, model layers were tagged according to their function: window glazing was assigned as VisionGlass, while natural elements such as grass and trees were tagged as Nature/Vegetation. Other layers were classified as Other. The ground was not explicitly modelled, as all buildings were positioned on the default horizontal ground plane (Z = 0 m). The analysis height was defined in line with EN 17037 recommendations: view and glare assessments were performed at 1.2 m, corresponding to the eye level of a seated occupant, while daylight simulations were conducted at 0.8 m, the reference height of a working desk. The analysis grid sensor spacing is set to 0.5 m.

3.4.1. Whole-Building Analysis

A whole-building daylight assessment was carried out in accordance with EN 17037 to evaluate the current performance of the case study against minimum regulatory and standard-based targets. Four key aspects of daylight in interior spaces were assessed: daylight provision, glare risk, sunlight exposure, and view out. This first evaluation provides the reference scenario and preliminary evaluations to understand the main building daylight-related issues and more deeply analyze single spaces to assess the rooms’ behavior at a higher level of detail. Specifically, the global building analysis includes the following aspects:
  • The daylight provision analysis defines three levels of recommendation (minimum, medium, and high) by verifying whether at least 50% of the occupied area achieves the corresponding target illuminance levels of 300, 500, or 750 lx, while ensuring that 95% of the space meets the associated minimum illuminance thresholds (100, 300, and 500 lx) for at least 50% of the daylight hours across a working plane.
  • The quality of the view out is assessed through three levels of recommendation (minimum, medium, and high), with each evaluation parameter, namely horizontal sight angle, outside view distance, and number of visible layers, having its own set of threshold values to determine its individual quality level. The overall view quality of a space is then defined by the lowest quality achieved among these individual parameters, in accordance with a limiting-factor approach. In addition, view out is assessed as a static condition, without reference to a specific time frame, and is evaluated at a fixed height of 1.20 m above the floor to represent a seated occupant position.
  • Sunlight exposure was assessed by choosing the 21st of March as a reference day and positioning for each window a reference point on the inner surface of the aperture at the center of its width. The reference point was positioned at least 1.20 m above the floor and 0.3 m above the sill, where present; in the absence of a sill, a height of 1.20 m above floor level was adopted. For each opening, the duration of direct sunlight at the reference point was calculated over the selected day, and, where multiple apertures were present on different façades, sunlight exposure times were cumulatively considered when occurring at different times of the day. This analysis has been conducted with the LB Tools and Grasshopper components.
  • Glare has been evaluated by spatial disturbing glare (sDG), an annual metric that indicates the percentage of view across the regularly occupied floor that experiences disturbing or intolerable glare (DGP > 38%) for at least 5% of the occupied hours, considering values for eight different view directions.

3.4.2. Test Space Selection and Analysis

A detailed analysis was conducted with CS on a single test space of 87 m2 located on the third floor, selected due to the presence of critical glare conditions observed in the overall building assessment. In addition, the room is characterized by a dual orientation (south and east), which increases the complexity of daylight analyses and makes it particularly suitable for in-depth investigation. The selected environment can therefore be considered representative of the most recurrent daylight- and glare-related issues observed throughout the building and serves as a reference space for applying the proposed methodological workflow. While the detailed analyses focus on this specific room, the same approach has been replicated in other areas to assess the effectiveness of the tested retrofit strategies across the building.
For the detailed space analyses, in addition to the EN 17037-based indicators used in the whole-building analysis, further simulations were performed to capture the temporal variability and critical peak conditions of daylight and solar radiation, as presented below:
  • Point-in-time illuminance analysis, used to investigate time-specific and localized issues at different solar elevations throughout the year. Illuminance values were calculated under a CIE clear sky for three representative days (21 March, 21 June, and 21 December) at three times of the day (10:30, 13:30, and 16:30), enabling a comprehensive understanding of the room’s behavior under varying seasonal and hourly solar conditions.
  • Useful daylight illuminance (UDI), considering a useful range between 300 and 2000 lux, further investigates the daylight availability of the selected space.
  • Spatial daylight autonomy (sDA) with a target 300 lux threshold for 50% of the occupied hours was also calculated to more precisely investigate the accomplishment of minimum requirements.
  • Annual sunlight exposure (ASE), included as a proxy indicator of potential glare and overexposure, consistent with LEED methodologies, to more deeply investigate the glare-related issues of the analyzed space. ASE indicates the percentage of regularly occupied floor area that is considered overlit. Overlit areas are defined as locations receiving direct sunlight exceeding 1000 lux from the solar disc for more than 250 occupied hours per year.

3.4.3. Retrofit Analysis

The retrofit analysis evaluates the impact of internal roller blinds on the daylight and view performance of the selected test space. The two selected alternative configurations have been tested in the same space considered in the previous analysis to ensure direct comparability with the existing conditions. For each configuration, annual daylight metrics (UDI, sDA, and sDG) were calculated alongside the view out assessment. ASE is not reported, as it is not sensitive to the shading effect according to the CS guide, as suggested also by ANSI/IES LM 83-22 [70], the reference standard for ASE calculation.
With the main goal of going beyond the EN 17037 view assessment and providing a more realistic understanding of visual connection with the outdoors, an additional analysis of view access was carried out using the LB View Percent component, which “evaluates the percent of view to the outdoors or sky from input geometry through context [61],” and the Sky Exposure ViewType, which assesses the percentage of the sky that is visible from each test point of the space grid, modelled as the previous ones. The tool is semi-three-dimensional, enabling a more realistic approximation of visual perception compared to purely planar methods, as it accounts for the spatial configuration of the façade, context, and shading devices; its main limitation is the impossibility of accounting for material transparency. In addition to the existing building condition, the analysis considered the introduction of a transparent internal roller blind, selected to better investigate issues related to indirect glare. Four levels of window activation were examined, corresponding to partial blind deployment at 25%, 50%, 75%, and 100% closure.
This complementary assessment supports a more comprehensive evaluation of retrofit strategies, extending beyond the EN 17037, adding advanced assessment to building diagnosis.

4. Results

In this section, the results of the building diagnosis are presented and analyzed. First, an analysis of the four daylight components is discussed for the entire building, followed by a deeper analysis of a single space, which deepens the level of detail and introduces a semi-three-dimensional methodology for the view out assessment. The results of the analyses pursued according to the EN 17037 consider, in addition to the three levels of compliance, a “fail” level, which serves as a complementary indicator to quantify the extent of underperforming areas within the analyzed space and to support clearer interpretation of the building’s daylight performance relative to the minimum recommended levels.

4.1. Daylight Provision

The first set of whole-building results concerns daylight provision, in accordance with the requirements of EN 17037. The results of the analysis, considering both the minimum and target level of illuminance, are shown for all the analyzed spaces in Figure 4 and Figure 5.
Figure 4. Daylight provision results according to EN 17037, considering the minimum target level of illuminance.
Figure 5. Daylight provision results according to EN 17037, considering the target level of illuminance.
The analysis of target illuminance levels across the building highlights differentiated performance among floors, with the ground floor presenting the most critical conditions. This level is characterized by smaller window openings and the absence of curtain wall systems; additionally, the larger footprint of the upper floor acts as an overhang, further limiting daylight. On the upper floors, daylight provision generally improves: most spaces consistently achieve at least the minimum target illuminance and, in many cases, a high level of compliance. Exceptions occur in one north-facing room on the second floor and in a room on the third floor characterized by a small window area and elongated plan geometry, where performance is slightly reduced. Overall, while the second and third floors largely meet high compliance levels, the largest spaces of the first floor reach a medium level of compliance, due to their large dimensions.
A summary of the presented results is shown in Table 6, with the percentage indicating the portion of the total analyzed area that falls between the specific criteria. In general, the building shows good levels of daylight provision, as 78.6% of the analyzed area fulfills both criteria, with the highest rating. More critical results are obtained for the ground floor, where the highest range is reached only by 6.2% of the floor area, and most of the area falls into the fail and minimum ranges. This is mainly caused by the presence of single windows instead of the curtain wall of the upper floors, and the first floor has some cantilevered parts that reduce the amount of incoming light. The main limit of this analysis is that the actual criteria considered by the standards do not consider a maximum illuminance threshold: this can cause problems of glare and excessive light.
Table 6. Summary result of the daylight provision analysis (target level) in the whole building according to the EN 17037 standard.

4.2. View Out

The second set of global results focuses on view out, and the spaces with a view to outdoors have been considered. Figure 6 shows that spaces equipped with larger openings and continuous façade exposure generally achieve medium to high levels of compliance, while rooms characterized by small or fragmented window surfaces present the most critical conditions. The presence of reduced window dimensions emerges as the main factor limiting the quality of the view out. Specifically, on the ground floor, several rooms along the main façade reach only the minimum level of compliance, and in some cases fail to meet the required view criteria due to the combination of small window openings and the reduced vertical field of view caused by the overhang of the upper floor. On the upper floors, the overall performance improves, with most rooms achieving medium or high compliance; however, those with smaller window apertures continue to present lower values, particularly in their rear portions. The third floor shows the highest levels of compliance overall, yet variability remains among individual spaces. Rooms with larger glazing areas and unobstructed façade exposure reach high compliance, whereas elongated rooms with small windows or limited façade width show reduced performance, often dropping to minimum levels in their deeper zones.
Figure 6. View out results according to EN 17037.
These results are summarized in Table 7, where it is emerges that, according to EN 17037, the building has a good view, as 62% of the analyzed floor area reaches the highest rating, and just the 2.6% of it fails the criteria. A more critical situation can be seen on the ground floor, as almost no area meets the criteria at the maximum level, and 18.9% of the area completely fails the criteria. This is mainly due to the smaller windows that are present on this floor, instead of the curtain walls that characterize the upper floors.
Table 7. Summary results of the view out analysis of the whole building, according to EN 17037.

4.3. Sunlight Exposure

The third global analysis concerns sunlight exposure, evaluated in accordance with EN 17037, and its results are reported in Figure 7. North-facing rooms consistently fail to meet the minimum sunlight requirements on all levels, due to the absence of direct solar access during the reference period. The ground floor presents the most critical conditions overall, with several spaces failing or achieving only minimum compliance, mainly because of reduced solar penetration caused by surrounding obstructions and the shielding effect of upper volumes. Moving to the upper floors, sunlight exposure generally improves, particularly along the west-facing façades, where higher levels benefit from increased solar access and reduced external shading. As a result, west-oriented rooms show progressive improvement in compliance from the ground to the upper floors, reaching medium (first floor) and high (second and third floor) levels of compliance.
Figure 7. Exposure to sunlight results, according to EN 17037.
The overall results (Table 8) highlight that the building shows generally good sunlight exposure performance, with an average of 75.8% of the floor area achieving high compliance. The ground floor presents the most critical conditions, with the highest fail percentage (18.7%), whereas upper floors perform significantly better, with over 88.1, 87.1 and 92.1% of their area, respectively, reaching high compliance, confirming that sunlight exposure improves with elevation.
Table 8. Summary of the sunlight exposure results for the whole building, according to EN 17037.

4.4. Protection from Glare

The fourth global analysis addresses glare conditions, assessed according to EN 17037 through the sDG metric. The results, reported in Figure 8, are expressed as the percentage of the analyzed floor area that complies with the recommended limits for disturbing or intolerable glare over the occupied period.
Figure 8. Glare results according to EN 17037.
On the ground floor, glare issues are generally limited and mostly confined to zones close to the south- and east-facing façades, where direct solar penetration affects areas immediately adjacent to the windows, while deeper portions of the rooms remain largely unaffected. Conditions become more critical on the upper floors, where increased solar exposure and larger glazed surfaces lead to more frequent occurrences of disturbing glare. This is particularly evident in smaller rooms with high window-to-floor ratios, where the reduced depth does not allow sufficient attenuation of direct sunlight, resulting in more extensive areas exceeding the glare threshold. North-facing spaces across all floors show minimal glare risk due to the absence of direct solar radiation, showing almost no glare problems.
The summary of the results in Table 9 indicate that the majority of the regularly occupied areas experience imperceptible daylight glare conditions, accounting for 86.08% of the total analyzed area. However, a clear vertical gradient is observed across the building. While the ground floor shows almost entirely imperceptible glare conditions (98.82%), upper floors exhibit a progressive increase in perceptible, disturbing, and intolerable glare. In particular, the second and third floors present the highest shares of intolerable glare, exceeding 9% of the analyzed area.
Table 9. Result of the glare analysis for the whole building, according to the DGP.

4.5. Detailed Analysis of a Single Space

To present the analysis results in greater detail, a single space was selected for in-depth investigation. This space, with a floor area of 87 m2 and located on the third floor, is particularly relevant due to the significant daylight quality issues identified at the building scale, which are strongly influenced by its plan layout and double exposure. The presence of a south-facing window and an east-oriented curtain wall results in complex daylight conditions that make this space a critical case for assessment. For these reasons, it was chosen as the focus for a detailed presentation of the subsequent refurbishment and evaluation process. The results of the analysis are reported in Figure 9. The percentages shown in the chart represent the average DA achieved by the test points (sDA); hours in the useful range (UDI); area achieving the minimum level of compliance (view out); area failing the criteria (ASE); and area hours suffering disturbing glare issues (sDG).
Figure 9. Results of the analyzed variables in the selected space.
Due to the large curtain wall on the east side, from the daylight point of view, the problems are more relevant; especially in the morning hours, when the sun is directly facing the curtain wall, high illuminance values are registered. This same result can also be seen in the UDI and sDA maps visible in the previous figure. These results show that the actual horizontal fixed shading system is not highly effective.
On the view side, instead, the office shows good results, as most of the analyzed area exhibits the maximum level of quality view. This satisfying result is mainly because one of the room’s sides is a curtain wall that allows high view access.
It can be noted that view out and daylight results can be discordant: where the view out has the highest values, there is excessive glare, visible from the sDG and ASE results, and the illuminance falls outside the UDI range.

4.6. Impact of a Building Retrofit Solution

Building on the outcomes of the preliminary qualitative assessment conducted for initial validation of the refurbishment strategy, a more detailed performance-based evaluation is carried out using the reference within the catalogue Step 3. In this context, the influence of the roller blind system on daylight-related aspects has been analyzed in detail, considering both transparent and opaque configurations. The comparative results of this analysis, which allow the relative performance of the two solutions to be assessed under consistent boundary conditions, are presented in Table 10.
Table 10. Effect of different refurbishment scenarios on daylight for the considered areas.
The transparent blind addition, from the daylight point of view, results in better daylight conditions, especially in the spaces of the third floor that were most affected by excessive daylight (UDI and sDA maps). The transparent blind helps in reducing glare issues, but, specifically for this problem, the opaque one was more efficient. On the other hand, opaque roller blinds reduce the illuminance as well, leading to longer periods when the minimum illuminance level is not reached. To have a better understanding of the shadings’ effect, their operation is shown in Figure 10.
Figure 10. Average daily and annual internal roller blind operation in the east-facing window (a) and the south-facing window (b).
From the previous analysis, it emerged that the east-facing window shows a total opening percentage of 70.41%, with the closing period mainly concentrated during the central hours of the day (7 a.m. to 1 p.m.), during the entire year. In contrast, the south-facing window exhibits a slightly higher annual opening percentage of 71.9%, with the closing period mainly concentrated from 10 a.m. to 5 p.m. from January to March and from September to December, as, when the sun is higher, activation is limited by how much of the window is revealed.
From the perspective of view performance, the results are particularly significant, as the analysis based on the EN 17037 evaluation grid for view out assessment does not record any variation before and after implementation of the refurbishment strategy. This occurs because the selected intervention affects spatial conditions that are not measured by the EN 17037 methodology. The presence of roller blinds introduces temporal variation in access to the outdoor view, as the blinds can be fully raised, partially lowered, or completely closed, therefore cropping or obstructing the view in different ways over time. However, since the discussed standard considers only static geometric conditions and assumes complete visibility through the glazed surface, these variations are not represented in the analysis. Furthermore, the analysis framework fails to account for potential reductions in visibility caused by the optical properties of the roller blinds, such as varying degrees of transparency. Currently, an object is treated as either a complete obstruction, fully blocking sight, or fully transparent, allowing unobstructed vision. Consequently, when modeling blinds, curtains, or other similar filters that may be made of materials with partial transparency, a decision must be made to classify the object as either fully obstructive or entirely transparent. In this case, roller blinds are treated as fully opaque for the purposes of the view out analysis. As a result, the evaluation returns identical scores before and after the intervention, which may cause a misleading interpretation of the actual view quality in the refurbished scenario. Although transparent roller blinds can still allow some vision, they nevertheless act as partial filters that can affect color consistency and overall visibility, depending on factors such as indoor–outdoor luminance contrast and the blinds’ condition due to cleanliness or maintenance; therefore, for planning purposes, it is more effective to evaluate the worst-case scenario by treating them as full obstructions.
The relation between view, as assessed by semi-three-dimensional analysis, and the various analyzed indicators is shown in Table 11 at different levels of blind closure. The analysis with this method reflects typical roller blind operation, deployed from the top of the glazing, that progressively compresses the upper portion of the visual field, masking the upper view with a blind and causing reduced view access. Among the view layers defined by EN 17037, the sky component is therefore the most immediately and significantly affected by blind deployment. A reduction in the visible sky fraction can thus be interpreted as a direct measure of the loss of openness and visual continuity, and as a partial representation of view clarity under dynamic shading conditions. While higher sky visibility is generally associated with improved view access, it may also increase the likelihood of visual discomfort due to glare. For this reason, sky access values are systematically discussed in relation to sDG results across different blind states. This combined assessment enables a more nuanced interpretation of the trade-offs between view quality and visual comfort introduced by adaptive roller blind operation, avoiding fragmented evaluation of these interdependent visual performance aspects.
Table 11. Impact of internal shading on outdoor view.
As expected, the blinds have a negative effect on view, increasing the area with no view and reducing the view percentage in other zones. Quantitatively, the values are more difficult to correlate with effective view quality, as the absolute view results are quite low due to analysis methodology, but they have been included to provide a quantitative indication of the differences between the analyzed scenarios, even if the most relevant outcome is the qualitative distribution of view access across the floor area rather than the absolute percentages. It is interesting to note the trend of the analyzed indicators in the different scenarios: glare continuously improves as the blinds are more closed, together with the UDI useful range, whereas the sDA decreases. Particularly relevant and interesting is the fully closed (100%) scenario, as in this condition glare-related issues are significantly reduced, because direct solar radiation is completely blocked, together with the related effects of reflected components. The percentage of useful daylight illuminance remains almost unchanged: the decrease in overlit areas is largely balanced by an increase in insufficiently lit areas, and sDA slightly worsens, particularly in the zones farther from the windows, where the absence of direct and reflected solar contributions becomes more critical.
This analysis also highlights important limitations of the EN 17037 view assessment methodology. Considering three-dimensional approaches would lead to a more accurate and precise quality view assessment, overcoming some constraints related to the bidimensional analysis at a fixed plane height.

5. Conclusions

This study has presented a comprehensive refurbishment methodology that systematically integrates outdoor views into the decision-making process for improving visual comfort in existing buildings. While daylight provision, sunlight exposure, and glare have traditionally received greater attention in both research and practice, view quality has often been treated as a secondary parameter. The proposed approach addresses this gap by structurally incorporating view assessment alongside daylight, sunlight exposure, and glare evaluation, providing a more holistic framework for refurbishment strategies.
The application of the workflow to a university building in València has highlighted how optimizing daylight and the view out represents a substantial challenge. Expanding window surfaces to enhance the quality of the view out may inadvertently increase illuminance levels and the risk of glare, underscoring the intrinsic trade-off between these parameters. Nevertheless, this case study suggests that movable shading systems, particularly those employing transparent fabrics, can offer a cost-effective strategy for reconciling this balance. By mitigating glare and excessive illuminance while still allowing outward vision, such solutions demonstrate their potential as practical interventions for improving user comfort without requiring major structural changes.
At the same time, the study has revealed significant limitations in the current calculation framework of EN 17037. The standard is based on a bidimensional and static methodology that does not adequately capture the complexity of real-world conditions. Movable shading devices, fabric transparency, or partial activation of blinds are not considered, even though they strongly influence the perception of view and visual comfort. Likewise, the static nature of the assessment does not reflect the dynamic interactions among daylight, shading operation, and user needs, suggesting that research-based protocols are now more accurate in representing the actual view quality. These constraints highlight the need for methodological improvements that can more accurately align computed results with user experience.
Overall, the proposed methodology demonstrates the value of adopting an integrated perspective on daylight, sunlight exposure, glare, and view out in refurbishment projects. Beyond addressing limitations in existing standards, it also provides a framework for bridging performance-based requirements and user-centered comfort. Future research should expand the analysis of the limitations across existing view out calculation frameworks and work towards the development of new metrics capable of accounting for dynamic and perceptual aspects of view. Such advancements would strengthen the reliability of view evaluation, fostering more effective and sustainable renovation practices that can boost the potential of actual sustainable frameworks, which will further bridge the gap between the assessed evaluation and the real occupant perception.

Author Contributions

Conceptualization, G.C., M.C., A.S., L.P.I., T.P. and A.G.M.; methodology, G.C., M.C., A.S., L.P.I., T.P. and A.G.M.; validation, G.C., M.C. and A.S.; formal analysis, G.C., M.C. and A.S.; investigation, G.C., M.C. and A.S.; resources, G.C., M.C., A.S., L.P.I., T.P. and A.G.M.; data curation, G.C., M.C. and A.S.; writing—original draft preparation G.C., M.C. and A.S.; writing—review and editing, G.C., M.C., A.S., L.P.I., T.P. and A.G.M.; visualization, G.C., M.C. and A.S.; supervision, M.C., A.S., L.P.I., T.P. and A.G.M.; project administration, L.P.I. and T.P.; funding acquisition, L.P.I. and T.P. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Institutional Review Board Statement

Not applicable.

Data Availability Statement

The original contributions presented in this study are included in the article. Further inquiries can be directed to the corresponding author.

Acknowledgments

The authors would like to acknowledge the support of SeedLab and the Escola Tècnica Superior d’Enginyeria de Edificació of the Universitat Politècnica de València (UPV) for their technical assistance and contribution to the development of this research.

Conflicts of Interest

The authors declare no conflicts of interest.

Abbreviations

The following abbreviations are used in this manuscript:
EEGElectroencephalogram
mEDIMelanopic Equivalent Daylight Illuminance
SASunlight Autonomy
sDASpatial Daylight Autonomy
ASEAnnual Sunlight Exposure
VLTVisual Light Transmittance
VLRVisual Light Reflectance
SFSolar Factor
KPIKey Performance Indicator
DGPDaylight Glare Probability
WFRWindow-to-Floor Ratio
WWRWindow-to-Wall Ratio
DFDaylight Factor
UGRUnified Glare Rating
VRVirtual Reality
LCCLife Cycle Cost
UDIUseful Daylight Illuminance
UPVUniversitat Politècnica de València
CSClimateStudio
LBLadybug
sDGSpatial Disturbing Glare

Appendix A

Figure A1. Elevations of the Rhino model of building 1C.

Appendix B

Figure A2. Window-to-floor ratio (in percentage) of the analyzed spaces.

References

  1. Michael, M.; Favoino, F.; Jin, Q.; Luna-Navarro, A.; Overend, M. A Systematic Review and Classification of Glazing Technologies for Building Façades. Energies 2023, 16, 5357. [Google Scholar] [CrossRef] [Scilit]
  2. Woo, M.; MacNaughton, P.; Lee, J.; Tinianov, B.; Satish, U.; Boubekri, M. Access to Daylight and Views Improves Physical and Emotional Wellbeing of Office Workers: A Crossover Study. Front. Sustain. Cities 2021, 3, 690055. [Google Scholar] [CrossRef] [Scilit]
  3. Al-Ashwal, N.T.; Hassan, A.S. The integration of daylighting with artificial lighting to enhance building energy performance. AIP Conf. Proc. 2017, 1892, 160010. [Google Scholar] [CrossRef] [Scilit]
  4. Chinazzo, G.; Wienold, J.; Andersen, M. Daylight affects human thermal perception. Sci. Rep. 2019, 9, 13690. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  5. Hirning, M.; Isoardi, G.; Garcia-Hansen, V. Prediction of discomfort glare from windows under tropical skies. Build. Environ. 2017, 113, 107–120. [Google Scholar] [CrossRef] [Scilit]
  6. Vaidya, P.; Mcdougall, T.; Steinbock, J.; Douglas, J.; Eijadi, D. What’s Wrong with Daylighting? Where It Goes Wrong and How Users Respond to Failure. American Council for an Energy-Efficient Economy (ACEEE). 2004. Available online: https://www.eceee.org/library/conference_proceedings/ACEEE_buildings/2004/Panel_7/p7_30/ (accessed on 1 October 2025).
  7. Xue, J.; Fan, Y.; Dong, Z.; Hu, X.; Yue, J. Improving Visual Comfort and Health Through the Design of a Local Shading Device. Int. J. Environ. Res. Public Health 2022, 19, 4406. [Google Scholar] [CrossRef] [Scilit]
  8. Kim, D.-H.; Luong, H.T.; Nguyen, T.T. Optimizing the Shading Device Configuration of Kinetic Façades Through Daylighting Performance Assessment. Buildings 2024, 14, 1038. [Google Scholar] [CrossRef] [Scilit]
  9. Budhiman, N.H.N.; Koerniawan, M.D. Comparing the Effectiveness of Dynamic Facades for Natural Daylight and Energy Usage in Buildings. In IOP Conference Series: Earth and Environmental Science; Institute of Physics: London, UK, 2024. [Google Scholar] [CrossRef] [Scilit]
  10. Alkhatatbeh, B.J.; Kurdi, Y.; Asadi, S. Multi-objective optimization of classrooms’ daylight performance and energy use in U.S. Climate Zones. Energy Build. 2023, 297, 113468. [Google Scholar] [CrossRef] [Scilit]
  11. Alsukkar, M.; Ibrahim, A.; Eltaweel, A. Multi-objective optimization of daylighting systems for energy efficiency and thermal-visual comfort in buildings: A review. Build. Environ. 2026, 288, 113921. [Google Scholar] [CrossRef] [Scilit]
  12. EPA. Report to Congress on Indoor Air Quality. Volume 2: Assessment and Control of Indoor Air Pollution. Available online: https://hero.epa.gov (accessed on 11 November 2024).
  13. Lottrup, L.; Stigsdotter, U.K.; Meilby, H.; Claudi, A.G. The Workplace Window View: A Determinant of Office Workers’ Work Ability and Job Satisfaction. Landsc. Res. 2015, 40, 57–75. [Google Scholar] [CrossRef] [Scilit]
  14. Shepley, M.M. The role of positive distraction in neonatal intensive care unit settings. J. Perinatol. 2006, 26, S34–S37. [Google Scholar] [CrossRef] [Scilit]
  15. Moore, E.O. A Prison Environment’s Effect on Health Care Service Demands. J. Environ. Syst. 1981, 11, 17–34. [Google Scholar] [CrossRef] [Scilit]
  16. Matsuoka, R.H. Student performance and high school landscapes: Examining the links. Landsc. Urban Plan. 2010, 97, 273–282. [Google Scholar] [CrossRef] [Scilit]
  17. Kaplan, R. The Nature of the View from Home. Environ. Behav. 2001, 33, 507–542. [Google Scholar] [CrossRef] [Scilit]
  18. Aries, M.B.; Veitch, J.A.; Newsham, G.R. Windows, view, and office characteristics predict physical and psychological discomfort. J. Environ. Psychol. 2010, 30, 533–541. [Google Scholar] [CrossRef] [Scilit]
  19. Kaplan, R. The role of nature in the context of the workplace. Landsc. Urban Plan. 1993, 26, 193–201. [Google Scholar] [CrossRef] [Scilit]
  20. Hartig, T.; Evans, G.W.; Jamner, L.D.; Davis, D.S.; Gärling, T. Tracking restoration in natural and urban field settings. J. Environ. Psychol. 2003, 23, 109–123. [Google Scholar] [CrossRef] [Scilit]
  21. Knight, C.; Haslam, S.A. The relative merits of lean, enriched, and empowered offices: An experimental examination of the impact of workspace management strategies on well-being and productivity. J. Exp. Psychol. Appl. 2010, 16, 158–172. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  22. Chang, C.-Y.; Chen, P.-K. Human Response to Window Views and Indoor Plants in the Workplace. HortScience 2005, 40, 1354–1359. [Google Scholar] [CrossRef] [Scilit]
  23. Parsons, R.; Tassinary, L.G.; Ulrich, R.S.; Hebl, M.; Grossman-Alexander, M. The view from the road: Implications for stress recovery and immunization. J. Environ. Psychol. 1998, 18, 113–140. [Google Scholar] [CrossRef] [Scilit]
  24. Ulrich, R. Biophilia, biophobia, and natural landscapes. In The Biophilia Hypothesis; Island Press: Washington, DC, USA, 1993; pp. 73–137. [Google Scholar]
  25. Ulrich, R.S. View through a window may influence recovery from surgery. Science (1979) 1984, 224, 420–421. [Google Scholar] [CrossRef] [Scilit]
  26. Heschong, L.; Saxena, M. Windows and Offices: A Study of Office Worker Performance and the Indoor Environment. 2003. Available online: https://www.researchgate.net/publication/328416566 (accessed on 27 February 2026).
  27. Zhang, Y.; Tang, Y.; Wang, X.; Tan, Y. The Effects of Natural Window Views in Classrooms on College Students’ Mood and Learning Efficiency. Buildings 2024, 14, 1557. [Google Scholar] [CrossRef] [Scilit]
  28. Benfield, J.A.; Rainbolt, G.N.; Bell, P.A.; Donovan, G.H. Classrooms with Nature Views: Evidence of Differing Student Perceptions and Behaviors. Environ. Behav. 2015, 47, 140–157. [Google Scholar] [CrossRef] [Scilit]
  29. Jang, D.; Kim, H.-J.; Choi, K. Enhancing Student Learning in Virtual Classrooms: Effects of Window View Content and Time of Day. IEEE Access 2024, 12, 152630–152638. [Google Scholar] [CrossRef] [Scilit]
  30. Kim, J.-J.; Wineman, J. Are Windows and Views Really Better? A Quantitative Analysis of the Economic and Psychological Value of Views; The University of Michigan: Ann Arbor, MI, USA, 2005. [Google Scholar]
  31. Taylor, A.F.; Kuo, F.E.; Sullivan, W.C. Views of nature and self-discipline: Evidence from inner city children. J. Environ. Psychol. 2002, 22, 49–63. [Google Scholar] [CrossRef] [Scilit]
  32. Bulut, Z.; Yilmaz, H. Determination of waterscape beauties through visual quality assessment method. Environ. Monit. Assess. 2009, 154, 459–468. [Google Scholar] [CrossRef] [Scilit]
  33. Farley, K.M.J.; Veitch, J.A. A Room with a View: A Review of the Effects of Windows on Work and Well-Being; National Research Council Canada: Ottawa, ON, Canada, 2001. [Google Scholar] [CrossRef] [Scilit]
  34. Sasaki, S.; Oe, Y.; Kishimoto, N.; Taniguchi, K.; Yoshizawa, N.; Budoh, Y. Causal connection between psychological view and daylighting evaluation in living spaces. In CIE x050:2023 Proceedings of the 30th Session of the CIE, Ljubljana, Slovenia, 15–23 September 2023; International Commission on Illumination, CIE: Vienna, Austria, 2023; Volume 1, pp. 1472–1479. [Google Scholar] [CrossRef] [Scilit]
  35. Hellinga, H. Daylight and View: The Influence of Windows on the Visual Quality of Indoor Spaces. 2013. Available online: https://api.semanticscholar.org/CorpusID:131694287 (accessed on 27 February 2026).
  36. Khanie, M.S.; Stoll, J.; Mende, S.; Wienold, J.; Einhäuser, W.; Andersen, M. Uncovering Relationships Between View Direction Patterns and Glare Perception in a Daylit Workspace. 2013. Available online: https://api.semanticscholar.org/CorpusID:17895549 (accessed on 27 February 2026).
  37. Ardabili, N.G.; Wang, J.; Wang, N. A systematic literature review: Building window’s influence on indoor circadian health. Renew. Sustain. Energy Rev. 2023, 188, 113796. [Google Scholar] [CrossRef] [Scilit]
  38. Vasquez, N.G.; Rupp, R.F.; Andersen, R.K.; Toftum, J. Occupants’ responses to window views, daylighting and lighting in buildings: A critical review. Build. Environ. 2022, 219, 109172. [Google Scholar] [CrossRef] [Scilit]
  39. Abd-Alhamid, F.; Kent, M.; Wu, Y. Quantifying window view quality: A review on view perception assessment and representation methods. Build. Environ. 2023, 227, 109742. [Google Scholar] [CrossRef] [Scilit]
  40. Tabadkani, A.; Roetzel, A.; Li, H.X.; Tsangrassoulis, A. Daylight in buildings and visual comfort evaluation: The advantages and limitations. J. Daylighting 2021, 8, 181–203. [Google Scholar] [CrossRef] [Scilit]
  41. He, S.; Zhang, W.; Guan, Y. The Impact of Building Windows on Occupant Well-Being: A Review Integrating Visual and Non-Visual Pathways with Multi-Objective Optimization. Buildings 2025, 15, 2577. [Google Scholar] [CrossRef] [Scilit]
  42. EN 17037:2018+A1:2021—Daylight in Buildings. Available online: https://bsol.bsigroup.com/Bibliographic/BibliographicInfoData/000000000030450533 (accessed on 9 November 2024).
  43. Waczynska, M.; Sokol, N.; Martyniuk-Peczek, J. Computational and experimental evaluation of view out according to European Standard EN17037. Build. Environ. 2021, 188, 107414. [Google Scholar] [CrossRef] [Scilit]
  44. Brembilla, E.; Azadi, S.; Nourian, P. A Computational Approach for Checking Compliance with European View and Sunlight Exposure Criteria. In Building Simulation Conference Proceedings; International Building Performance Simulation Association: Verona, WI, USA, 2022; pp. 2459–2466. [Google Scholar] [CrossRef] [Scilit]
  45. Sfaksi, I.; Mezerdi, T.; Zemmouri, N. The Workplace Windows Effect: Post Occupancy Evaluation of Office Employees’ Satisfaction within Daylight and Exterior View. Int. J. Innov. Stud. Sociol. Humanit. 2022, 7, 210–220. [Google Scholar] [CrossRef] [Scilit]
  46. LEED v4.1—BD+C: New Construction. Available online: https://www.usgbc.org/leed/v41 (accessed on 9 November 2024).
  47. LEED v5: Building Design and Contruction. 2025. Available online: https://www.usgbc.org/resources/leed-v5-reference-guide-building-design-and-construction-april-2025-launch-edition (accessed on 1 October 2025).
  48. BREEAM UK. Available online: https://kb.breeam.com/us/homepage/ (accessed on 2 February 2026).
  49. WELL v2. Available online: https://v2.wellcertified.com/en (accessed on 2 February 2026).
  50. BREEAM Daylighting—Alternative Methods. Available online: https://kb.breeam.com/knowledgebase/breeam-daylighting-well-crosswalk/ (accessed on 24 February 2026).
  51. BREEAM—Health and Wellbeing—Visual Comfort—Adequate View Out. Available online: https://files.bregroup.com/breeam/technicalmanuals/sd/uk-new-construction-2018/#05_health/hea01_nc_a.htm#AdequateViewOut (accessed on 24 February 2026).
  52. BREEAM—Health and Wellbeing—Visual Comfort—Definitions. Available online: https://files.bregroup.com/breeam/technicalmanuals/sd/uk-new-construction-2018/#05_health/hea01_nc_a.htm#hea01definitions (accessed on 24 February 2026).
  53. WELL v2—Light—L01—Light Exposure. Available online: https://v2.wellcertified.com/en/wellv2/light/feature/1 (accessed on 24 February 2026).
  54. WELL v2—Mind—M09 Enhanced Access to Nature. Available online: https://v2.wellcertified.com/en/wellv2/mind/feature/9 (accessed on 24 February 2026).
  55. Decreto Ministeriale 18 Dicembre 1975. Available online: https://www.edscuola.it/archivio/norme/decreti/dm181275.html (accessed on 30 June 2025).
  56. Código Técnico de la Edificación. Available online: https://www.codigotecnico.org/ (accessed on 24 February 2026).
  57. Trinh, V.Q.; Bodrogi, P.; Khanh, T.Q. Determination and Measurement of Melanopic Equivalent Daylight (D65) Illuminance (mEDI) in the Context of Smart and Integrative Lighting. Sensors 2023, 23, 5000. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  58. Dervishaj, A.; Gudmundsson, K. Sunlight Autonomy for Buildings: A New Methodology for Evaluating Sunlight Performance in Urban and Architectural Design. LEUKOS 2025, 21, 34–64. [Google Scholar] [CrossRef] [Scilit]
  59. Google Earth—Building 1C—Top View. Available online: https://earth.google.com/web/@39.48082761,-0.34490075,6.25933333a,252.67750635d,81.54607083y,20.25451503h,0t,0r/data=CgRCAggBOgMKATBKDQj___________8BEAA (accessed on 8 October 2024).
  60. ClimateStudio Homepage. Available online: https://www.solemma.com/climatestudio (accessed on 9 November 2024).
  61. Ladybug Suite. Available online: https://www.food4rhino.com/en/app/ladybug-tools# (accessed on 9 November 2024).
  62. AGC Glass Configurator. Available online: https://www.agc-glass.eu/en (accessed on 24 February 2026).
  63. T-10/T-10M Illuminance Meters. Available online: https://sensing.konicaminolta.us/us/products/t-10-t-10m-illuminance-meters/ (accessed on 27 December 2025).
  64. Konstantzos, I.; Tzempelikos, A. Daylight glare evaluation with the sun in the field of view through window shades. Build. Environ. 2017, 113, 65–77. [Google Scholar] [CrossRef] [Scilit]
  65. Lolli, N.; Nocente, A.; Brozovsky, J.; Woods, R.; Grynning, S. Automatic vs. Manual Control Strategy for Window Blinds and Ceiling Lights: Consequences to Perceived Visual and Thermal Discomfort. J. Daylighting 2019, 6, 112–123. [Google Scholar] [CrossRef] [Scilit]
  66. Konstantzos, I.; Chan, Y.-C.; Seibold, J.C.; Tzempelikos, A.; Proctor, R.W.; Protzman, J.B. View clarity index: A new metric to evaluate clarity of view through window shades. Build. Environ. 2015, 90, 206–214. [Google Scholar] [CrossRef] [Scilit]
  67. Nicoletti, F.; Carpino, C.; Arcuri, N. IoT Control-Based Solar Shadings: Advanced Operating Strategy to Optimize Energy Savings and Visual Comfort. In IoT Edge Solutions for Cognitive Buildings; Springer: Cham, Switzerland, 2023; pp. 173–195. [Google Scholar] [CrossRef] [Scilit]
  68. Prezzi Infromativi dell’Edilizia—Nuove Costruzioni; Genio Civile: Roma, Italy, 2025.
  69. Prezzario Regione Lombardia. Available online: https://www.regione.lombardia.it/wps/portal/istituzionale/HP/servizi-e-informazioni/enti-e-operatori/autonomie-locali/acquisti-e-contratti-pubblici/osservatorio-regionale-contratti-pubblici (accessed on 24 February 2026).
  70. ANSI/IES LM 83-22. Available online: https://store.ies.org/product/approved-method-ies-spatial-daylight-autonomy-sda-and-annual-sunlight-exposure-ase/?v=0d149b90e739 (accessed on 24 February 2026).
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.