Article

Optimal Design and Performance Analysis for Hybrid PV/Wind System of Al-Tafilah Cement Factory Using HOMER Pro Software

by
Mohammed Q. Al-Odat
1,* and
Abdulmajeed S. Al-Ghamdi
2,*
1
Department of Mechanical Engineering, Al-Huson University College, Al-Balqa Applied University, Irbid 21510, Jordan
2
Department of Mechanical Engineering, College of Engineering and Architecture, Umm Al-Qura University, Mecca City 24381, Saudi Arabia
*
Authors to whom correspondence should be addressed.
Energies 2026, 19(12), 2735; https://doi.org/10.3390/en19122735
Submission received: 27 April 2026 / Revised: 30 May 2026 / Accepted: 2 June 2026 / Published: 6 June 2026

Abstract

Hybrid power generation systems are an effective solution for matching energy production with electrical load demand. In this study, we examine the viability of a grid-connected hybrid PV/Wind system for meeting the electricity demand of the Lafarge cement factory in Al-Tafilah, Jordan, using HOMER Pro software. The results indicate that the optimal configuration consists of a 6.1   M W wind turbine and a 22.8   M W PV array, producing 71.94   G W h annually, with wind and PV contributing 31.3 % and 68.7 % , respectively. The system achieves a 100% renewable fraction while maintaining a high level of reliability, with unmet load and capacity shortage limited to 0.057 % and 0.1 % , respectively. The economic evaluation reveals a levelized cost of energy (LCOE) of 0.13   U S D / k W h and a net present cost (NPC) of U S D   25.827   m i l l i o n , representing a 27.8 % reduction in LCOE compared to the national grid tariff. In this study, we present a novel large-scale PV/Wind system for the cement industry in Jordan, based on real data, with enhanced techno-economic performance. The innovation of this research lies in the development and optimization of a large-scale grid-connected hybrid PV/Wind system for the cement industry in Jordan, utilizing actual industrial load data and site-specific renewable energy resources. Unlike previous PV-dominated studies, the proposed system integrates a significant contribution of wind energy to improve system reliability and renewable energy penetration, reduce dependency on the national grid, and improve the overall techno-economic performance under actual industrial operating conditions.

1. Introduction

Renewable energy systems are an essential alternative for meeting energy requirements, especially in countries that lack conventional energy resources. Moreover, conventional energy sources tend to be depleted, and their prices can increase dramatically; this situation has increased interest in the utilization of different types of renewable energy sources, particularly solar and wind energy. Renewable energies represent the best solution to the energy shortage and environmental problems currently facing our world. A single renewable energy source is often insufficient to meet the required power demand. Fluctuations in energy supply lead to intermittent power generation and may cause problems when supply continuity is required.
This problem can be avoided by combining more than one energy resource in a system (known as hybrid systems), enhancing load factors and reducing maintenance costs [1]. The utilization of hybrid energy systems such as PV/Wind has gained significant attention for meeting electrical power demand while ensuring a less intermittent and more reliable electrical supply. Additionally, hybrid energy systems lead to substantial reductions in the total cost of energy generation.
Numerous software types. including HOMER, HOMER Pro, HOGA, PROLOAD, RET-Screen and MATLAB, are employed to optimize and design hybrid energy systems. Among these, HOMER and HOMER Pro are most commonly used by researchers worldwide. Indeed, HOMER software has been extensively used to optimize hybrid energy systems in the literature. Different hybrid energy systems that include renewable and nonrenewable sources have been extensively studied and analyzed. Two types of research have been reported regarding the optimization of hybrid energy systems. The first type considers off-grid systems, and the second type focuses on grid-connected systems. Many energy sources are combined together; these include two or more of the following resources: solar PV, wind, biomass, hydropower, geothermal, and diesel engines. Among the first category, substantial attention has been paid to the optimization of off-grid hybrid systems based on renewable resources using HOMER software. Off-grid hybrid energy systems depend on batteries to store excess electrical energy. The results indicate that off-grid hybrid renewable electrical systems are an optimal, cost-effective solution for ensuring electrical energy supply in remote areas [2,3,4,5,6,7,8,9,10,11].
Similarly, the optimization of on-grid hybrid energy systems has been extensively investigated in recent years. On-grid hybrid energy systems are the optimal option for areas close to the national electrical grid [12,13,14,15,16,17,18]. The installation costs of on-grid systems are lower than those of off-grid systems since the costs of required materials are lower. The excess electrical energy produced is fed into the grid (virtual battery); thus, no investment is required in batteries. In addition, maintenance and repair costs are lower.
Another group of reported studies considered the optimization and analysis of both on- and off-grid hybrid energy systems [19,20,21]. Comprehensive reviews of different hybrid energy systems in terms of cost and size optimization and prefeasibility analysis, conducted using Homer software, were carried out in [22,23,24,25,26,27]. A hybrid PV/Wind system for the Lafarge cement factory in Al-Tafilah, Jordan, was proposed in [28]. Al-Odat et al. [29] carried out a numerical investigation using HOMER Pro software to obtain an optimum on-grid hybrid PV/Wind system to deliver the required electrical power to a cement factory in Kuwait. The findings demonstrate that hybrid PV/Wind systems attain higher renewable penetration and lower LCOE in industrial sectors. In contrast to the Kuwait case study, which focused on smaller-scale, primarily PV-dominated installations, the Al-Tafilah system integrates a larger share of wind energy, resulting in a more balanced generation profile and improved reliability throughout the year. This comparison highlights the importance of tailoring hybrid system design to site-specific solar and wind resources to optimize technical and economic performance. Nwachukwu et al. [30] presented a comprehensive and systematic review on the use of HOMER Pro software, highlighting its widespread application in optimizing hybrid renewable energy systems, particularly in emerging economies.
This review of the previous literature indicates that no previously reported research has addressed the optimization and analysis of a hybrid PV/Wind energy system for a megaproject in Jordan, thereby motivating the present investigation. In this research, we investigate the feasibility of creating a hybrid on-grid PV/Wind energy system for the Lafarge cement factory in Al-Tafilah, Jordan, using HOMER Pro software (Version 3.18.4). We develop and optimize an on-grid large-scale hybrid PV/Wind system using actual industrial load data, site-specific renewable energy resources, and detailed techno-economic analysis through HOMER Pro software. Furthermore, we evaluate renewable energy penetration, system reliability, excess electricity generation, environmental impact reduction, and sensitivity analysis to assess the robustness and applicability of the proposed system for industrial applications.
In this study, we present a novel techno-economic optimization of an on-grid hybrid PV/Wind system for a large cement factory in Al-Tafilah, Jordan, which has not previously been investigated. Unlike earlier PV-dominated or small-scale studies, it examines a high-capacity industrial configuration under real operating conditions. A comparative analysis of PV-dominant and wind-integrated cases is performed using HOMER Pro (Version 3.18.4) with long-term site-specific data. The results show that wind integration improves energy balance, reliability, and grid dependency reduction in arid regions.

2. Research Methodology

2.1. Methodology

To tackle the intermittency and reliability issues resulting from use of a single renewable energy source, a hybrid PV/Wind grid-connected system was implemented in this study. The proposed methodology relied on combining solar PV and wind energy resources to improve the continuity and reliability of electrical power supply and reduce dependence on the national electrical grid. HOMER Pro software Version 3.18.4 was utilized to simulate, analyze, and optimize different hybrid system configurations under actual operating conditions. The adopted method included load profile analysis, the collection of solar radiation and wind speed data, techno-economic evaluation, sensitivity analysis, and the comparison of different hybrid system arrangements. The optimum system configuration was selected based on minimum net present cost (NPC), the lowest levelized cost of energy (LCOE), a high renewable energy fraction, and reliable system operation.

2.2. Wind Resource in Jordan

The Jordanian wind map depicted in Figure 1 was sourced from Jordan’s wind atlas, which was established in 1987. Between 2001 and 2008, the National Energy Research Center (NERC) carried out a wind measurement campaign at Jordan’s potential sites at various heights (10, 30, 40, 50, and 60 m above ground level) to obtain more reliable wind data, especially wind speed and direction. Following a study of grid expansion, wind potential, and electricity substations, seven locations were chosen in three regions: north (Hofa, Ras-Monief, and Ibrahimya), middle (Zabda and Tafila), and south (Aqaba 5 and Fujaij). Table 1 shows geographic information about the chosen sites. The selected sites and the closest power plants are depicted in Figure 2. The wind data were monitored throughout the period from 2002 to 2008. The annual mean wind speeds for all sites are depicted in Table 2. The average wind speeds for all examined sites exceed 6.5 m/s. The windiest stations at Hofa, Zabda, and Tafila show annual average wind speeds exceeding 7 m/s.
All considered sites are feasible for wind energy investment. Tafila possesses the highest wind energy potential and was, therefore, selected as the study site for this investigation.

2.3. Solar Resources in Jordan

The electrical power generated from PV systems depends mainly on the solar radiation intensity of the selected sites. Actually, there is a shortage of solar irradiance data, which is a critical challenge. Even in countries with significant solar resources, such as Jordan, the presence of a limited number of weather stations means that we must record detailed solar irradiance for a long period for data to be statistically significant. The Jordan Meteorological Department (JMD) provided data for monthly average solar irradiance on a horizontal surface for 10 sites to estimate solar irradiance over the entire country. Figure 3a demonstrates the solar map of Jordan. The annual average solar irradiance in Jordan is excellent as the average solar irradiance varies from 5   t o   7   k W h / m 2 / d a y on a horizontal surface; this value averages at approximately 6   k W h / m 2 / d a y as shown in Figure 3b. In most areas of the country, the average value is around 6 kWh/m2/day, indicating that Jordan is one of the promising regions for solar energy applications.
Figure 4 demonstrates the monthly average solar irradiance in Jordan. Jordan has a high solar radiation potential all year-round, accompanied by a moderate ambient air temperature and low levels of dust and humidity. Therefore, the electrical conversion efficiency of PV modules will be satisfactory. Additionally, the months of May to August have the highest values for solar radiation, which is consistent with the load on the national grid.

2.4. Modeling Software—HOMER Pro

The optimization and eco-technical analysis of hybrid renewable energy systems can be carried out utilizing various types of software. HOMER Pro is a highly reliable and powerful tool for designing optimal renewable systems. HOMER is a computer program that helps designers to configure, simulate, evaluate, and optimize different designs for electricity generation systems with different loads. HOMER-PRO was developed in the United States by the National Renewable Energy Laboratory (NREL). HOMER has been used to define, design, and model hybrid power generation systems for reliably meeting rural communities’ electricity demand while ensuring continuity, quality, and energy security. As a result, knowledge of the research area’s electricity demand, as well as the possible availability of solar irradiance and wind from each location, is required.
The main stages of the methodology used for electrification using hybrid PV/Wind system energy can be summarized as follows:
  • Identify and analyze the electrical energy demand.
  • Examine the solar irradiance and wind potential at the factory’s site using Excel sheets and HOMER software.
  • Carry out a financial–technical evaluation of the hybrid energy system for electrification at the selected site.
  • Conduct simulations, optimizations, and comparative analysis of different hybrid system arrangements using HOMER Software to ensure the provision of electricity to the Lafarge cement factory at Al-Tafilah.
  • Select the hybrid system arrangement option that best meets the electricity demand of the factory in terms of reliability and low cost.
In this study, we extend HOMER Pro optimization by using high-resolution industrial load data and long-term site-specific solar and wind resources in southern Jordan. Unlike previous research based on synthetic loads, it applies real cement factory consumption data. The grid-connected model excludes batteries, enabling the direct assessment of renewable penetration and export potential.

2.5. Technical Specifications of System Components

The hybrid renewable energy system considered in this study consists of PV modules, wind turbines, and a power conversion system. The system configuration and component parameters were defined via HOMER Pro based on commercially available technologies and region-specific resource conditions in Jordan.
The PV system was modeled utilizing flat-plate crystalline silicon PV modules. The module efficiency was assumed to be 16–19%, while a derating factor of 80–90% is implemented to account for temperature effects, dust accumulation, wiring losses, mismatch losses, and long-term degradation under Jordanian climatic conditions [31].
The wind energy system consists of a utility-scale wind turbine. The turbine performance was represented using manufacturer power curve data available in HOMER Pro. A hub height of 50 m was adopted based on the wind resource characteristics of the Tafila region. The vertical wind speed variation was modeled using the standard power-law wind shear profile with a suitable shear coefficient consistent with semi-arid climate conditions.
A bidirectional power converter was established to ensure appropriate AC/DC power conversion and system integration between the renewable sources and the grid. The converter efficiency was assumed to be 95–98%, aligned with updated high-efficiency inverter technologies.
All cost-related parameters, including capital cost, replacement cost, component lifetime, and operation and maintenance cost, were achieved from the HOMER Pro database and adjusted to reflect local market conditions in Jordan. The overall project lifetime was assumed to be 25 years, with annual operation and maintenance costs considered for both PV and wind systems.
The economic analysis was based on a 25-year project lifetime, a fixed real discount rate as per HOMER Pro standards, and an assumed rate of inflation. The grid electricity tariff and net-metering conditions were included to estimate imported and exported energy. These financial parameters ensured consistency in economic modeling and enhanced the transparency, comparability, and reproducibility of the results.

3. Data Collection and Electrical Load Profile

The load profile is the most critical factor for determining the accuracy of the simulation and optimization process of the hybrid energy systems, which means meeting the power demand at any given time without incurring extra costs due to oversizing. Load assessment should be carried out carefully. The average monthly electricity demand for the Lafarge cement factory in Al-Tafilah was obtained from electricity bills, as well as the average hourly load profile. The load profile data were fed into HOMER as time-series data. Figure 5 shows the average hourly energy demand of the Lafarge cement factory in Al-Tafilah, Jordan, in 2015. The daily load profile of energy demand for the at-hand cement factory is plotted in Figure 6. The load is highest between 10:00 and 11:00 a.m. and lowest between 1:00 and 5:00 a.m. For the profile, the daily electrical energy is approximately constant at 60,000   k W h . The estimated average energy demand for the factory was fed into HOMER Pro as input data.

3.1. Tafilah Region Solar and Wind Potential Analysis

In this study, the solar radiation and wind data of the Al-Tafilah region were collected; after that, the site’s geographical coordinates were introduced to HOMER as input data for resource specification and calculation.

3.1.1. Wind Information

In this investigation, wind data were collected at a height of 20 m, and then these data were imported into HOMER. The monthly average wind speeds at 20 m above ground level in Al-Tafilah, as obtained via HOMER, are illustrated in Figure 7. The figure illustrates clear seasonal wind speed fluctuation, with higher wind speeds recorded during the winter and early spring months, while comparatively lower values occur in summer. This variation can be attributed to the effects of regional atmospheric pressure systems and local climatic conditions. In general, the site shows moderate-to-strong wind potential throughout the year, confirming its suitability for wind energy production and the fact that it is a major contributor to hybrid PV/Wind system performance stability.

3.1.2. Solar Radiation Information

Figure 8 and Figure 9 show the monthly solar radiation and daily temperature data, respectively. These values were obtained from HOMER. Solar radiation data are available during the entire year; therefore, a significant amount of PV power can be produced. Figure 8 indicates significant seasonal variation, with greater irradiance levels during summer months and lower values in winter due to changes in sun angle and atmospheric conditions. This indicates strong solar potential, suitable for PV generation throughout the year. Figure 9 shows higher temperatures during summer and more moderate conditions in winter. Temperature variations directly affect PV performance, with module performance slightly declining at higher temperatures while maintaining acceptable operating conditions for reliable energy production.

4. Results and Discussion

The results presented in this section were obtained via simulation and optimization performed using HOMER Pro software based on the input data described in Section 2.1. The model evaluates different possible system configurations by combining various sizes of photovoltaic arrays, wind turbines, and power electronic converters under the specified load profile and renewable resource conditions. For each configuration, HOMER Pro performs hourly time-step simulations over the project lifetime to calculate the technical performance and economic indicators, such as the net present cost (NPC) and levelized cost of energy (LCOE). The software then compares and ranks all feasible configurations and selects the optimal system based on minimum cost, high renewable energy fraction, and reliable system operation. The achieved results are additionally analyzed in terms of energy production, excess electricity, unmet load, and overall system performance under real operating conditions.
The present hybrid PV/Wind energy strategy is not limited to the case study of the Lafarge cement factory in Al-Tafilah; rather, it can be extended and applied to other industrial sectors and geographical locations with similar energy demand characteristics. The adopted methodology based on HOMER Pro optimization is a general framework that depends on site-specific input data such as solar irradiance, wind speed, load profile, and electricity tariff. Therefore, the same approach can be transferred to other cement plants or energy-intensive industries by updating the local resource data and load requirements. In addition, the grid-connected hybrid configuration without storage can be considered a practical solution for regions with strong renewable resources and reliable grid infrastructure. However, the optimal system sizing and energy mix will vary from one location to another depending on resource availability and economic conditions. This confirms that the proposed strategy is flexible, scalable, and adaptable for different industrial applications rather than being limited to a single case study.
In the same regional context, the Kingdom of Saudi Arabia (KSA) represents a relevant extension for the proposed optimization strategy because of its strong solar resources, promising wind potential, and rapidly expanding renewable-energy deployment under Vision 2030 [32,33]. Recent Saudi studies have identified suitable locations for large-scale PV, wind, and hybrid PV/wind systems, while operational projects such as the Sakaka PV plant and Dumat Al-Jandal wind farm demonstrate the practical implementation of these technologies in the Kingdom [33]. Moreover, HOMER-based Saudi case studies have shown that optimized hybrid renewable systems can reduce NPC, LCOE, and emissions while maintaining reliable power supply [34]. Accordingly, the present Jordanian cement-factory case study provides a practical and scalable reference for future grid-connected PV/wind applications in Saudi cement plants and other energy-intensive industrial facilities, subject to site-specific recalibration of renewable resources, load demand, grid conditions, and economic parameters.

4.1. Hybrid Energy System Configuration

Figure 10 shows the proposed system’s overall component configuration and its HOMER model. For numerous sensitivity value ranges of generation capacity, finance prices, wind speed, and solar irradiation, the software setup comprises all simulations and alternative arrangements tested for solar PVs and wind turbines. Accordingly, HOMER Pro evaluates multiple system configurations and optimization scenarios by combining different sizes of photovoltaic (PV) arrays and wind turbines. This approach allows a comprehensive comparison of possible design alternatives under varying environmental and economic conditions. The obtained simulation outcomes provide deeper insight into the system behavior, particularly the influence of resource availability and cost fluctuations on optimal techno-economic performance. Moreover, the sensitivity analysis highlights the robustness of the proposed hybrid system and its ability to maintain reliable operation at different renewable energy penetration levels.
The grid-connected system is modeled under a net-metering assumption, in which surplus electricity generated by the PV/Wind hybrid system is exported to the utility grid and credited at the prevailing electricity tariff. Accordingly, excess electricity is not treated as energy loss but as exported energy that contributes positively to the overall economic performance of the system. This modeling assumption justifies the high renewable penetration and apparent PV oversizing observed in the optimal configuration, as the exported energy enhances cost-effectiveness and reduces the net electricity import from the grid.

4.2. Techno-Economic Analysis of Al-Tafilah Region

Each categorized scenario was thoroughly discussed in the techno-economic analysis of the present system with regard to the technical and economic parameters resulting from the simulation procedures. After that, the optimal scenario, which meets demand at the lowest cost, was chosen for further investigation. The costs for the proposed system in Al-Tafilah are depicted in Table 3 as the net present cost (NPC), the levelized cost of electrical energy (LOCE), and operation and maintenance (O&M) costs.
The capital, replacement, and operation and maintenance costs are illustrated in Figure 11 and Table 4, respectively. The overall capital cost, total replacement cost, and total operation and maintenance cost of the system were USD 20.06 million, USD 6.95 million, and USD 0.58 million, respectively. In comparison, the total replacement cost was relatively low, amounting to USD 6.95 million, which reflects the long operational lifetime of the main system components and the limited need for mid-life replacements. Moreover, the total operation and maintenance cost was USD 0.58 million, indicating a moderate running cost associated with system maintenance and operational management over the project life cycle.
In general, the cost distribution demonstrates that the hybrid solar/wind energy system has high initial capital intensity with lower replacement and O&M costs. This cost structure is typical for renewable-based hybrid energy systems and further supports their long-term economic viability.
Table 5 illustrates the quantity of energy generated via solar modules and wind turbines. Solar energy accounts for 68.7% of total production, while wind energy accounts for 31.3%.
The proposed system differs from previous hybrid energy systems in three aspects: (i) its application to a large-scale cement industry with continuous high energy demand, (ii) the integration of a significant wind power share with solar PV under Jordanian conditions, and (iii) achieving high renewable penetration in a grid-connected industrial setup. It improves energy balance, reliability, and cost performance compared to PV-dominant systems.
The unmet load and capacity shortage values achieved in this study are 0.057% and 0.1%, respectively, which reflect a system with high reliability. As per IEEE reliability standards and HOMER optimization criteria, the accepted reliability should be kept within a 1–5% range for industrial and grid-connected hybrid renewable energy systems. Thus, the obtained values in the proposed PV/Wind system are significantly lower than the commonly accepted industrial limits, confirming that the system satisfies the reliability requirements of large industrial electrical loads such as cement manufacturing facilities.
The very low unmet load percentage demonstrates that the proposed hybrid system can continuously satisfy the factory’s electrical demand with minimal risk of interruption, while the negligible capacity shortage further confirms the adequacy of the selected system sizing and configuration. These findings indicate that the optimized system achieves excellent operational reliability and is technically suitable for industrial-scale applications under real operating conditions.
Table 6 illustrates the key performance indicators of the proposed PV/Wind hybrid system and their benchmarks using data from global studies. Overall, the proposed system characteristics indicate excellent reliability and sizing. The comparison with global benchmarks shows that our system is fully renewable and highly reliable and reflects typical values observed in well-designed PV-dominated energy systems.
Figure 12 displays the system’s monthly power production from both PV and wind sources. The productivity of the wind turbine is almost constant throughout the year. In contrast, the PV array exhibits significant seasonal variability in its electrical productivity. Higher energy generation is observed during the summer months, attributed to increased solar irradiance and longer daylight hours, while a noticeable reduction occurs during winter due to lower irradiance levels and shorter solar exposure periods. This complementary behavior between wind and solar resources enhances the overall reliability of the hybrid system by partially compensating for seasonal fluctuations in individual energy sources.

4.3. Environmental Impact

The implantation of the proposed hybrid PV/Wind system not only reduces dependence on fossil fuels but also contributes to Jordan’s environmental sustainability goals by significantly reducing greenhouse gas emissions. The environmental benefits of the presented hybrid PV/Wind system can also be quantified by calculating the reduction in greenhouse gas emissions relative to the conventional grid-based electricity supply. The annual CO2 emission reduction was calculated based on total renewable electricity generation and the emission factor of the electricity. CO2 emission reduction was computed using the following equation:
C O 2 r e d u c t i o n = E a n n u a l × E F g r i d
where E a n n u a l is the annual energy production of the hybrid system (71.94 GWh = 71,940 MWh), and E F g r i d is the grid emission factor (kg CO2/kWh).
Based on the Jordanian electricity generation mix, an emission factor of approximately 0.50 kg CO2/kWh (0.5 tCO2/MWh) was adopted from regional energy and environmental reports. Substituting the values into the equation, we identified the following results:
C O 2 r e d u c t i o n =   71,940,000   k W h × 0.50   k g C O 2 / k W h
C O 2 r e d u c t i o n = 35,970,000   k g   C O 2 / y e a r 35,970   t o n s   C O 2 / y e a r
representing approximately 36,000 tons of CO2 per year.
This approach assumes that all generated renewable electricity directly displaces grid electricity with the equal emission intensity, which is a standard assumption in HOMER-based environmental assessments.
In terms of policy, through this research, we have enhanced national plans supporting renewable energy integration and shown the cost-effectiveness of promoting hybrid PV/Wind systems on an industrial scale. The outcomes of this study can guide decision-makers in developing legislation and investment strategies to expedite the shift toward cleaner energy in the industrial sector.

4.4. Sensitivity Analysis and Robustness Assessment

A comprehensive sensitivity analysis was carried out to assess the effects of key uncertain factors on the optimal configuration and techno-economic performance of the present hybrid PV/Wind power system. The analysis focused on three critical variables, namely solar irradiance, wind speed, and electricity tariff, as these parameters have a direct impact on renewable energy production, system sizing, and overall economic feasibility.
Figure 13 depicts the sensitivity analysis results of the optimized grid-connected hybrid PV/Wind system under variations in solar irradiance, wind speed, and grid electricity tariff.
For solar irradiance variation (5.0–7.0 kWh/m2/day), the results show a gradual decrease in LCOE and NPC with increasing solar availability due to higher PV energy output and improved system efficiency. The optimal PV capacity remains dominant under all solar scenarios, while wind contribution remains relatively stable.
For wind speed variation (5.5–7.5 m/s at 50 m hub height), an increase in wind speed results in a noticeable improvement in wind turbine capacity factor, leading to a moderate reduction in LCOE and a slight redistribution of the energy share between PV and wind components. However, the overall system configuration remains stable, confirming the robustness of the optimization results.
For electricity tariff variation (0.14–0.22 USD/kWh), the economic performance of the system is highly sensitive. Higher tariffs significantly improve the competitiveness of the hybrid system, resulting in lower NPC and faster economic payback, while lower tariffs slightly reduce the economic advantage but do not affect technical feasibility. In all cases, the system remains fully renewable with minimal variation in reliability indicators.
Overall, the figure demonstrates that the proposed hybrid PV/Wind system maintains stable performance across all considered scenarios, confirming its technical robustness and economic adaptability under different environmental and market conditions.
A detailed parametric sensitivity analysis was carried out to quantify the effect of variations in solar irradiance, wind speed, and electricity tariff on the optimal hybrid system configuration. Table 7 presents a summary of the resulting changes in key techno-economic indicators. The results show that PV capacity varies moderately with solar resource availability, while wind capacity is more sensitive to wind speed changes. Economic performance is dramatically influenced by electricity tariff variations, where higher tariffs reduce LCOE and NPC. Regardless of these variations, the system keeps a 100% renewable fraction and very low unmet load, confirming high reliability and stability under different climate and economic conditions.

5. Conclusions

In this article, we present a size and cost optimization of a hybrid PV/Wind renewable energy system for meeting the energy demand of Lafarge cement factory located in Al-Tafilah, Jordan, using HOMER Pro software. The findings show that PV contributes 68.7% and wind contributes 31.3% of total energy production. The results obtained from the optimization give an initial capital cost of USD 20.06 million, while the operating cost is 0.58 million USD/year. The total net present cost (NPC) is USD 25.827 million, and the cost of energy (COE) is 0.13 USD/kWh.
The proposed hybrid system is more cost-efficient than Jordan’s national power grid, as its cost is 0.13 USD/kWh, while that of Jordan’s national electricity grid is 0.18 USD/kWh. This emphasizes the cost-competitiveness of the proposed hybrid system relative to conventional electricity supply. Moreover, the system reduces greenhouse gas emissions by approximately 36,000 tons/CO2 per year, which in turn supports progress towards environmental sustainability targets.
The findings of this study were compared with recent regional and international research to examine similarities, differences, and the unique contributions of the proposed hybrid system in the Jordanian industrial sector.

Author Contributions

Conceptualization, methodology, validation, data curation, writing—original draft preparation, M.Q.A.-O. and A.S.A.-G.; Formal Analysis, investigation, writing—original draft preparation, writing—review and editing, M.Q.A.-O. and A.S.A.-G. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Data Availability Statement

Data are available upon request from the corresponding author.

Acknowledgments

A.S.A.-G. gratefully acknowledges Umm Al-Qura University for granting sabbatical leave (No. 4501021717), which provided the opportunity to spend a portion of this leave in Jordan collaborating with colleagues.

Conflicts of Interest

The authors declare no conflicts of interest.

Nomenclature

ACAlternating Current (A)
COECost of Energy (USD/kWh)
DCDirect Current
EEnergy (kWh)
E F g r i d Grid Emission Factor
E a n n u a l Annual Energy Production of the Hybrid System
ELElectric Load (kWh/year)
HOMERHybrid Optimization Model for Electric Renewables
IRRInternal Rate of Return (%)
kWhKilowatt-hour
LCOELevelized Cost of Energy (USD/kWh)
MWMegawatt
NPCPresent Cost (USD)
O&M CostOperation and Maintenance Cost
PVPhotovoltaic
RFRenewable Energy Fraction (%)
TTemperature (°C)
WTWind Turbine

References

  1. Kaldellis, J.K.; Kondili, E.; Filios, A. Sizing a hybrid wind–diesel stand-alone system on the basis of minimum long-term electricity production cost. Appl. Energy 2006, 83, 1384–1403. [Google Scholar] [CrossRef]
  2. Kazem, H.A.; Al-Badi, H.A.S.; Al Busaidi, A.S.; Chaichan, M.T. Optimum design and evaluation of hybrid solar/wind/diesel power system for Masirah Island. Environ. Dev. Sustain. 2017, 19, 1761–1778. [Google Scholar] [CrossRef]
  3. He, G.-X.; Cheng, L.; Xu, J.; Chen, L.; Tao, W.-Q. Optimal configuration of a wind/PV/battery hybrid energy system using HOMER software. Chem. Eng. Trans. 2017, 61, 1507–1512. [Google Scholar] [CrossRef]
  4. Hossen, M.D.; Shezan, S.A. Optimization and assessment of a hybrid solar–wind–biomass renewable energy system for Kiribati Island. J. Eng. Res. Appl. 2019, 9, 58–64. [Google Scholar]
  5. Navamani, J.D.; Lavanya, A.; Prahadheeshwar, C.M.; Riyazudeen, S.M. Hybrid power system design using HOMER Pro. Int. J. Recent Technol. Eng. 2019, 8, 605–609. [Google Scholar]
  6. Çetinbaş, İ.; Tamyürek, B.; Demirtaş, M. Design, analysis and optimization of a hybrid microgrid system using HOMER software: Eskişehir Osmangazi University example. Int. J. Renew. Energy Dev. 2019, 8, 65–79. [Google Scholar] [CrossRef]
  7. Mas’ud, A.A.; Al-Garni, H.Z. Optimum configuration of a renewable energy system using multi-year parameters and advanced battery storage modules: A case study in northern Saudi Arabia. Sustainability 2021, 13, 5123. [Google Scholar] [CrossRef]
  8. Rasool, N.M.; Abbasoğlu, S.; Hashemipour, M. Analysis and optimization of hybrid wind and solar photovoltaic generation system for off-grid small village. J. Energy Syst. 2022, 6, 176–187. [Google Scholar] [CrossRef]
  9. Ozogbuda, J.C.; Iqbal, M.T. Sizing and analysis of an off-grid photovoltaic system for a house in remote Nigeria. Jordan J. Electr. Eng. 2022, 8, 17–26. [Google Scholar] [CrossRef]
  10. Jha, N.; Prashar, D.; Rashid, M.; Khanam, Z.; Nagpal, A.; AlGhamdi, A.S.; Alshamrani, S.S.; Darba, A. Energy-efficient hybrid power system model based on solar and wind energy for integrated grids. Math. Probl. Eng. 2022, 2022, 4877422. [Google Scholar] [CrossRef]
  11. Hasan, G.T.; Mutlaq, A.H.; Salih, M.O. Investigate the optimal power system using hybrid optimization of multiple energy resources software. Indones. J. Electr. Eng. Comput. Sci. 2022, 26, 9–19. [Google Scholar] [CrossRef]
  12. Acharya, S. Simulation and control of PV–wind–hydro hybrid renewable energy system and possibility in Nepal. Int. J. Sci. Eng. Res. 2016, 7, 1540. [Google Scholar]
  13. Mekonnen, A. Optimal sizing of grid-connected PV/wind hybrid system using HOMER software. Int. J. Sci. Res. 2019, 8, 482–488. [Google Scholar]
  14. Al Garni, H.Z.; Awasthi, A.; Ramli, M.A.M. Optimal design and analysis of photovoltaic systems under different tracking systems using HOMER. Energy Convers. Manag. 2018, 155, 42–57. [Google Scholar] [CrossRef]
  15. Jenkins, P.; Elmnifi, M.; Younis, A.; Emhamed, A. Hybrid power generation by using solar and wind energy: Case study. World J. Mech. 2019, 9, 81–93. [Google Scholar] [CrossRef]
  16. Suresh, V.; Prasad, K.S.K.; Venkateswarlu, P.; Kumar, R.V.R. Techno-economic optimization of grid-connected distributed energy systems using HOMER. Int. J. Mod. Trends Sci. Technol. 2020, 6, 191–202. [Google Scholar]
  17. Konchou, F.A.T.; Temene, H.D.; Tchinda, R.; Njomo, D. Techno-economic and environmental design of an optimal hybrid energy system for a community multimedia centre in Cameroon. SN Appl. Sci. 2021, 3, 127. [Google Scholar] [CrossRef]
  18. de Carvalho, C.M.; Medina, D.O.G.; Lopes, J.C.; Sousa, T. Computer Modeling and analysis of a hybrid renewable energy system using HOMER Pro. SBSE Simpósio Bras. De Sist. Elétricos 2020. [Google Scholar] [CrossRef]
  19. Ibrahim, M.H.; Ibrahim, M.A. Solar–wind hybrid power system analysis using HOMER for Duhok, Iraq. Przegląd Elektrotechniczny 2021, 97, 139. [Google Scholar] [CrossRef]
  20. Sedeeqi, M.M.; Vaisakh, K. Techno-economic analysis for remote area electrification of Awbeh village in Afghanistan using HOMER Pro. Int. J. Emerg. Technol. Innov. Res. JETIR 2021, 8, b20–b23. [Google Scholar]
  21. Thirunavukkarasu, M.; Sawle, Y. Techno-economic viability of hybrid grid-integrated and stand-alone generation systems for an Indian tea plant. Front. Energy Res. 2022, 10, 806870. [Google Scholar] [CrossRef]
  22. Bahramara, S.; Moghaddam, M.P.; Haghifam, M.R. Optimal planning of hybrid renewable energy systems using HOMER: A review. Renew. Sustain. Energy Rev. 2016, 62, 609–620. [Google Scholar] [CrossRef]
  23. Khare, V.; Nema, S.; Baredar, P. Solar–wind hybrid renewable energy system: A review. Renew. Sustain. Energy Rev. 2016, 58, 23–33. [Google Scholar] [CrossRef]
  24. Nighoskar, A. Cost analysis of hybrid system using HOMER—A review. Int. J. Adv. Res. Electr. Electron. Instrum. Eng. 2017, 6, 2115–2120. [Google Scholar]
  25. Madhav, D.; Gupta, A.K. A review on renewable energy sources for hybrid power generation. Int. J. Creat. Res. Thoughts (IJCRT) 2018, 6, 1618–1621. [Google Scholar]
  26. Giedraityte, A.; Rimkevicius, S.; Marciukaitis, M.; Radziukynas, V.; Bakas, R. Hybrid Renewable Energy Systems—A Review of Optimization Approaches and Future Challenges. Appl. Sci. 2025, 15, 1744. [Google Scholar] [CrossRef]
  27. Bhuiyan, M.A.; Zhang, Q.; Khare, V.; Mikhaylov, A.; Pintér, G.; Huang, X. Renewable energy consumption and economic growth nexus-A systematic literature review. Front. Environ. Sci. 2022, 10, 878394. [Google Scholar] [CrossRef]
  28. Al-Ghussain, L.; Ahmed, H.; Haneef, F. Optimization of hybrid PV/wind system: Case study Al-Tafilah cement factory, Jordan. Sustain. Energy Technol. Assess. 2018, 30, 24–36. [Google Scholar] [CrossRef]
  29. Al-Odat, M.; Al-Hasan, M.; Obeidat, F.; Chamkha, A.J. Optimization of on-grid hybrid PV/wind system for a cement factory in Kuwait using HOMER Pro software. Int. J. Low-Carbon Technol. 2024, 19, 120–126. [Google Scholar] [CrossRef]
  30. Nwachukwu, S.E.; Folly, K.A.; Awodele, K.O.; Omogoye, S.O.; Adeyemo, K.K. Hybrid Renewable Energy Optimization Using HOMER Pro: A Systematic Literature Review and Future Research Agenda for Emerging Economies. IEEE Access 2026, 14, 10695–10718. [Google Scholar] [CrossRef]
  31. Masters, G.M. Renewable and Efficient Electric Power Systems, 2nd ed.; Wiley: Hoboken, NJ, USA, 2013. [Google Scholar]
  32. Alghassab, M.; Khan, Z.A.; Altamimi, A.; Imran, M.; Alruwaili, F.F. Prospects of Hybrid Energy in Saudi Arabia, Exploring Irrigation Application in Shaqra. Sustainability 2022, 14, 5397. [Google Scholar] [CrossRef]
  33. Imam, A.A.; Abusorrah, A.; Marzband, M. Potentials and opportunities of solar PV and wind energy sources in Saudi Arabia: Land suitability, techno-socio-economic feasibility, and future variability. Results Eng. 2024, 21, 101785. [Google Scholar] [CrossRef]
  34. Abusaq, M.; Zohdy, M.A. Optimizing Renewable Energy Integration through Innovative Hybrid Microgrid Design: A Case Study of Najran Secondary Industrial Institute in Saudi Arabia. Clean Technol. 2024, 6, 397–417. [Google Scholar] [CrossRef]
Figure 1. Jordanian wind map.
Figure 1. Jordanian wind map.
Energies 19 02735 g001
Figure 2. The annual average wind speeds for the seven locations.
Figure 2. The annual average wind speeds for the seven locations.
Energies 19 02735 g002
Figure 3. (a) Solar map of Jordan, showing global horizontal irradiation in KWh/m2, (b) Global Solar Radiation Map of Jordan in W h / m 2 / d a y .
Figure 3. (a) Solar map of Jordan, showing global horizontal irradiation in KWh/m2, (b) Global Solar Radiation Map of Jordan in W h / m 2 / d a y .
Energies 19 02735 g003
Figure 4. Monthly average solar irradiance, measured at Tafilah, Baqura, Mafraq, Ras-Muneef and Deir-Alla.
Figure 4. Monthly average solar irradiance, measured at Tafilah, Baqura, Mafraq, Ras-Muneef and Deir-Alla.
Energies 19 02735 g004
Figure 5. The average hourly electricity demand of the cement factory in Al-Tafilah, Jordan, in 2015 [28].
Figure 5. The average hourly electricity demand of the cement factory in Al-Tafilah, Jordan, in 2015 [28].
Energies 19 02735 g005
Figure 6. The daily load profile of the energy demand for the cement factory in Al-Tafilah [28].
Figure 6. The daily load profile of the energy demand for the cement factory in Al-Tafilah [28].
Energies 19 02735 g006
Figure 7. The representation of the monthly mean wind speed (m/s) at 20 m above the ground level in Al-Tafilah.
Figure 7. The representation of the monthly mean wind speed (m/s) at 20 m above the ground level in Al-Tafilah.
Energies 19 02735 g007
Figure 8. Estimates of the solar radiation potential of Al-Tafilah.
Figure 8. Estimates of the solar radiation potential of Al-Tafilah.
Energies 19 02735 g008
Figure 9. Estimates of daily temperature for Al-Tafilah.
Figure 9. Estimates of daily temperature for Al-Tafilah.
Energies 19 02735 g009
Figure 10. The configuration of the system used in HOMER.
Figure 10. The configuration of the system used in HOMER.
Energies 19 02735 g010
Figure 11. The total cost of the project in Al-Tafilah.
Figure 11. The total cost of the project in Al-Tafilah.
Energies 19 02735 g011
Figure 12. The monthly electric production of the hybrid PV/Wind system.
Figure 12. The monthly electric production of the hybrid PV/Wind system.
Energies 19 02735 g012
Figure 13. A combined sensitivity analysis of the LCOE conducted under variations in solar irradiance, wind speed, and electricity tariff.
Figure 13. A combined sensitivity analysis of the LCOE conducted under variations in solar irradiance, wind speed, and electricity tariff.
Energies 19 02735 g013
Table 1. The physical characteristics of the selected sites.
Table 1. The physical characteristics of the selected sites.
SiteCoordinatesElevation (m)
Latitude (N)Longitude (E)
Deg.Min.Deg.Min.
Hofa32303551792
Ibrahimya32263549992
Ras Monief322235451150
Zabda305035441134
Tafila 2304635411436
Fujiaj 40303435371274
Aqaba 52940352139
Table 2. The annual and monthly average wind speeds (m/s) for the selected sites.
Table 2. The annual and monthly average wind speeds (m/s) for the selected sites.
SiteHeight (m)Measurement PeriodAnnual Mean (m/s)
Hofa452002–20047.16
302002–20046.93
Ibrahimya602006–20086.83
452006–20086.39
222006–20085.87
Ras Monief452006–20086.64
Tafila 2452006–20088.54
302006–20088.26
Fujaij 40402002–20036.88
102002–20035.99
Zabda502003–20067.03
402003–20066.54
102003–20066.24
Aqaba 5452002–20057.23
302002–20056.90
Table 3. The NPC, LOCE and O&M for the proposed system Al-Tafilah.
Table 3. The NPC, LOCE and O&M for the proposed system Al-Tafilah.
Total NPCUSD 25.827 Million
LCOE0.13 USD/kWh
O&M CostUSD 0.58 million
Salvage ValueUSD 1.288 million
Table 4. The capital, replacement, and O&M costs for the hybrid PV/Wind system in Al-Tafilah.
Table 4. The capital, replacement, and O&M costs for the hybrid PV/Wind system in Al-Tafilah.
ComponentCapital (M USD)Replacement (M USD)O&M
(M USD)
Fuel (USD)Salvage (M USD)Total (M USD)
Generic 6.1 MW8.56.9500.170.001.28813.765
Generic flat plate PV (22.8 MW)11.30.000.410.000.0011.71
System Converter0.2630.1120.000.000.0130.362
System20.067.0620.580.001.28825.827
Table 5. The percentage of energy produced by the PV/Wind hybrid system.
Table 5. The percentage of energy produced by the PV/Wind hybrid system.
ProductionKWh/yr%ConsumptionKWh/yr%QuantityKWh/yr%
Generic flat plate PV (22.8 MW)49,454,87368.7AC Primary Load21,887,517100Excess Electricity48,652,85667.6
Generic 6.1 MW22,481,89731.3DC Primary Load00Unmet Electric Load12,4830.057
Total71,936,770100Deferrable Load00Capacity Shortage21,8980.100
Total21,887,517100
QuantityValueUnit
Renewable Fraction100%
Max. Renew. Penetration1649%
Table 6. The key performance indicators of the present PV/Wind hybrid system compared to global studies.
Table 6. The key performance indicators of the present PV/Wind hybrid system compared to global studies.
MetricPresent SystemBenchmark Range [22,23]Comments/Interpretation
Excess Electricity (% of load)67.6%30–70% (solar PV-only systems, high-irradiance regions)Our system is completely dependent on renewable energy
Unmet Electric Load (% of total load)0.057%0–5%Extremely low; indicates adequate PV sizing
Capacity Shortage (% of total load)0.1%0–3%Very minor; similar to well-designed PV microgrids
Renewable Fraction (%)100%80–100% (fully PV-powered microgrids)Fully renewable supply, aligns with global fully solar systems
Max Renewable Penetration (% of load)1649%1000–2000% (oversized PV with no storage)High PV oversizing; typical for research case studies or islanded microgrids
System ReliabilityhighHigh in well-sited PV systems with proper sizingOur system reliability is good compared to global benchmarks
Table 7. Parametric sensitivity analysis of the optimal hybrid PV/Wind system.
Table 7. Parametric sensitivity analysis of the optimal hybrid PV/Wind system.
CaseSolar (kWh/m2/day)Wind (m/s)Tariff (USD/kWh)PV (MW)Wind (MW)NPC (M$)LCOE ($/kWh)Excess (%)Grid Export (GWh)Unmet Load (%)Renewable Fraction (%)
Base6.07.00.1822.86.125.830.1367.648.650.057100
S15.57.00.1824.06.126.400.13472.150.200.060100
S26.57.00.1821.56.125.100.12663.846.100.055100
W16.06.50.1823.55.826.100.13370.049.000.065100
W26.07.50.1822.06.525.200.12764.547.300.050100
T16.07.00.1422.86.128.100.14867.648.650.060100
T26.07.00.2222.86.123.900.11267.648.650.050100
S1 = Solar sensitivity case 1 → low solar irradiance (5.5 kWh/m2/day), T1 = Tariff case 1 → low electricity price (0.14 USD/kWh). S2 = Solar sensitivity case 2 → high solar irradiance (6.5 kWh/m2/day), T2 = Tariff case 2 → high electricity price (0.22 USD/kWh). W1 = Wind sensitivity case 1 → lower wind speed (6.5 m/s). W2 = Wind sensitivity case 2 → higher wind speed (7.5 m/s). Base = reference optimal case (6.0 kWh/m2/day, 7.0 m/s, 0.18 USD/kWh).
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Al-Odat, M.Q.; Al-Ghamdi, A.S. Optimal Design and Performance Analysis for Hybrid PV/Wind System of Al-Tafilah Cement Factory Using HOMER Pro Software. Energies 2026, 19, 2735. https://doi.org/10.3390/en19122735

AMA Style

Al-Odat MQ, Al-Ghamdi AS. Optimal Design and Performance Analysis for Hybrid PV/Wind System of Al-Tafilah Cement Factory Using HOMER Pro Software. Energies. 2026; 19(12):2735. https://doi.org/10.3390/en19122735

Chicago/Turabian Style

Al-Odat, Mohammed Q., and Abdulmajeed S. Al-Ghamdi. 2026. "Optimal Design and Performance Analysis for Hybrid PV/Wind System of Al-Tafilah Cement Factory Using HOMER Pro Software" Energies 19, no. 12: 2735. https://doi.org/10.3390/en19122735

APA Style

Al-Odat, M. Q., & Al-Ghamdi, A. S. (2026). Optimal Design and Performance Analysis for Hybrid PV/Wind System of Al-Tafilah Cement Factory Using HOMER Pro Software. Energies, 19(12), 2735. https://doi.org/10.3390/en19122735

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop