Compensation Admittance Load Flow: A Computational Tool for the Sustainability of the Electrical Grid

by
Benedetto-Giuseppe Risi
1,2,
Francesco Riganti-Fulginei
1,*,
Antonino Laudani
1 and
Michele Quercio
1
1
Department of Industrial, Electronic and Mechanical Engineering, University of Roma Tre, Via Vito Volterra 62, 00146 Rome, Italy
2
E-Grids SPA, Enel Group, Via Mantova 24, 000198 Rome, Italy
*
Author to whom correspondence should be addressed.
Sustainability 2023, 15(19), 14427; https://doi.org/10.3390/su151914427
Submission received: 25 July 2023 / Revised: 16 September 2023 / Accepted: 25 September 2023 / Published: 2 October 2023

Abstract

:
Compensation Admittance Load Flow (CALF) is a power flow analysis method that was developed to enhance the sustainability of the power grid. This method has been widely used in power system planning and operation, as it provides an accurate representation of the power system and its behavior under different operating conditions. By providing a more accurate representation of the power system, it can help identify potential problems and improve the overall performance of the grid. This paper proposes a new approach to the load flow (LF) problem by introducing a linear and iterative method of solving LF equations. The aim is to obtain fast results for calculating nodal voltages while maintaining high accuracy. The proposed CALF method is fast and accurate and is suitable for the iterative calculations required by large energy utilities to solve the problem of quantifying the maximum grid acceptance capacity of new energy from renewable sources and new loads, known as hosting capacity (HC) and load capacity (LC), respectively. Speed and accuracy are achieved through a properly designed linearization of the optimization problem, which introduces the concept of compensation admittance at the node. The proposed method was validated by comparing the results obtained with those coming from state-of-the-art methods.

1. Introduction

In recent years, the landscape of electricity generation has undergone a transformative shift from centralized production to a distributed generation (DG) model, necessitating substantial adaptations within the electricity grid framework. The conventional architecture of distribution grids, originally designed for passive operations with radial topologies and unidirectional power flows towards high-to-low voltage (HV to LV) substations, has proven inadequate for accommodating the significant integration of distributed generation [1,2]. As the demand for electricity escalates and distributed renewable sources gain widespread adoption [3], the need to modernize grid infrastructure and implement advanced monitoring and regulation technologies becomes imperative [4,5].
Within this evolving energy paradigm, the accurate assessment of load flow and optimal power distribution [6,7] emerges as a critical factor in effectively managing and forecasting the state and trajectory of the electrical grid. This assessment not only offers insights into optimizing resource allocation for harnessing existing grid capacity, but also aids in the seamless integration of new renewable energy systems (RESs) [8] and the accommodation of emerging loads [9,10,11,12]. Given that resolving the load flow problem serves as a cornerstone in optimizing power grid operations, the availability of efficient computational tools [13,14] is of paramount importance.
Against this backdrop, this paper introduces a novel methodology known as Compensation Admittance Load Flow (CALF), a hybrid approach that leverages the strengths of both the Newton–Raphson (NR) [15] and Gauss–Seidel (GS) [15] methods under certain grid conditions. By explicating the methodological foundations, practical applications, and computational intricacies of CALF, this study aims to offer a comprehensive overview of the Compensation Admittance Load Flow approach.
Furthermore, this paper culminates in a rigorous series of tests that not only compare the Compensation Admittance Load Flow (CALF) method with established techniques like NR and GS, but also subject the method to rigorous scrutiny, encompassing performance and robustness [1,15,16]. Through the ensuing presentation, analysis, and discussion of these tests, the strengths, limitations, and unique attributes of the proposed CALF method are highlighted. By addressing the advantages and disadvantages of existing load flow methods, this paper effectively positions CALF within the broader context of power systems analysis, thereby providing a holistic evaluation of its contributions.
The distinctiveness of this work lies in the development of the Compensation Admittance Load Flow (CALF) method and its comparison with traditional Newton–Raphson and Gauss–Seidel methods. In a field as vital as electrical networks, where efficient load flow analysis is a cornerstone, the introduction of a linear and iterative approach like CALF represents a noteworthy advancement. By fusing the positive attributes of traditional methods with a particular focus on medium- and low-voltage scenarios, this method showcases the potential for rapid and accurate calculations, cost-effective simulations, and the ability to address intricate scenarios. Furthermore, its linear nature offers implementation advantages, particularly valuable for companies mandated to deploy complex algorithms for relatively straightforward scenarios.
Through an exhaustive comparison of simulation results across networks of varying sizes, this study validates the novel CALF methodology. By providing a meticulous analysis and introducing a new method, this work contributes significantly to the existing load flow literature, offering a fresh perspective and solution for addressing a key challenge in power systems analysis.

2. About Traditional LF Solving Methods

Load flow analysis is a fundamental task in power systems as it involves examining the grid from the perspective of power flows. Herein we will give a short summary of the problem, starting with the components of the system. A power transmission grid is composed of nodes physically realized in substations, aerial or cable lines, and transformers that connect the nodes together. The transmission grid is fed at one or more generation nodes by synchronous generators installed in power plants. The grid then feeds loads consisting of sub-transmission and distribution grids originating from substations called load nodes. Interconnection nodes are those where more than two lines converge and are used to achieve the desired mesh configuration of the grid. In studying the steady-state operation, generators and loads are usually simulated by the powers they inject or take from the nodes, constituting external constraints imposed on the grid. This simplification is possible because each component of the transmission grid [17] can be considered symmetric, with good approximation. The goal of load flow analysis is to find the nodal voltages and power flowing in the lines connecting grid nodes, considering the loads or generators at a particular time instant. During LF evaluation, active and reactive power are considered constant and given, whereas nodal and generator voltages assume the values required to satisfy the power flow need. Since LF is defined in terms of powers at nodes, it is intrinsically a nonlinear problem, which requires an iterative scheme for its solution. In traditional LF solving methods, such as the Gauss–Seidel and Newton–Raphson methods, the problem is solved iteratively by linearizing the power flow equations at each iteration. The Gauss–Seidel method works by solving the power flow equations sequentially, one node at a time, while the Newton–Raphson method solves the equations simultaneously for all nodes, using a linearized version of the problem achieved by exploiting first-order derivatives and Taylor series expansion. However, these methods can be slow and computationally intensive for large-scale systems, making the study of faster solution techniques of interest important above all in a less stable grid due to the proliferation of renewable source plants. As a result, new and faster methods are being developed, such as the Compensation Admittance Load Flow (CALF) method, which is presented in this paper.

2.1. Load Flow Problem Formulation

In this paragraph, the formulation of the load flow problem [1,2] is expressed as simply as possible. Figure 1 shows a typical small electrical grid for load flow problems, where generators (circle) and loads (triangles) are represented by the active and reactive powers supplied and absorbed, respectively. These are connected to the grid at nodes, which, as previously stated, are called buses or busbars, since they are the busbars of electrically independent stations. The buses are connected among them by lines (power lines).
The load flow analysis is conducted to determine power flows on various lines and voltage on each busbar, with the aim to furnish all the users with the desired power, to guarantee that the busbars’ voltages are kept within certain bounds and to prevent overloading of lines. The primary parameters of lines are assumed to be constant, with conductor resistance corresponding to an assigned operating temperature. Overhead lines are assumed to have constant transverse conductance due to small corona losses. In any case, homogeneous lines, whether overhead or cable, can be represented by using a passive two-port network satisfying reciprocity theorem conditions, which makes possible their circuital schematization as a simple π network. It is worth noticing that load asymmetries in the three phases due to non-negligible single-phase loads in LV and MV grids are compensated by grid operators [18,19], allowing for a single-phase scheme to be used for all components of three-phase grids. The external constraint conditions are expressed through node-imposed quantities. Equations governing grid operation can be written by applying Kirchhoff’s principles to nodes and meshes. The neutral is counted as the second terminal shared by all the loads or generators of each busbar: in this way, it is a sort of reference node. Current and voltage are defined for each node as phasors.
For example, in a small system constituting only three busbars, and substituting the transmission lines equivalent model, it is possible to obtain the circuital representation of Figure 2. The network can be seen in this case in terms of four terminals (in the general case as a N + 1 terminal network, where N is the number of busbars), which allows a simple representation by means of an admittance (or impedance) matrix as follows:
I b u s = Y b u s · V b u s
where I b u s is the vector of the phasors of the current Ik (supplied) at the busbars, V b u s is the vector of the phasors of the voltage Vk of the busbars, and Y b u s is the admittance bus matrix. The elements of the admittance bus matrix can be easily computed by inspection, according to circuit theory. Indeed, the diagonal element (Yii) is equal to the sum of the admittance connected to node “i”, whereas the other elements (Yij) are the sum, with sign changed, of the admittance directly connecting node “i” and “j”. Clearly, the admittance bus matrix is symmetric.
Now let us look at Equation (1), which in a less compact form becomes:
I k = n = 1 N Y k n · V n
for each element I k of the I b u s vector, each admittance Y k n of Y b u s , and each nodal voltage of V n vector. From voltages and currents, it is possible to compute the active and reactive power delivered by generators or absorbed by loads. For sake of clarity, let us consider a generic busbar “k” as in Figure 3.
The Pk and Q k (active and reactive power) of the k bus-bar are expressed in Equation (3):
P k = P g k P c k Q k = Q g k Q c k
where S k is the complex power, which can be also expressed as a function of the k-nodal voltage and current V k and I k (with the * we indicate the complex conjugate).
S k = V k · I k * = P k + j Q k
Substituting (1) in (4) we obtain (5):
P k + j Q k = V k · n = 1 N Y k n · V n *
with k = 1, 2, …, N nodes. Now considering the polar form in (6):
V n = | V n | e j n Y k n = | Y k n | e j θ k n
Then, substituting (6) in (5), we obtain (7):
P k + j Q k = V k · n = 1 N Y k n · V n · e j n k θ k n
That is, applying Euler’s equality in Equation (7), finally we obtain power flow equations for each bus active and reactive power in (8):
P k = V k · n = 1 N Y k n · V n · c o s n k θ k n Q k = V k · n = 1 N Y k n · V n · s i n n k θ k n
As shown in (8), the active and reactive power of each bus are related through two nonlinear algebraic equations involving the nodal voltages and the admittances of the grid. Equation (8) can be seen consequently as a system of 2N equations. The unknowns theoretically should be the voltages in module and phase, but really they depend on constraints. Indeed, the load flow problem involves finding the unknown voltages at each busbar for a given set of known loads (Pl, Ql) and generators (Pg, Qg). However, the total active and reactive powers are not known a priori due to line losses, which depend on the unknown voltage. To resolve this issue, one of the busbars, named the slack bus, is chosen to equilibrate the powers: the active and reactive power for f or this node are consequently derived unknowns (with this expression we indicate that this quantity is computed by knowledge of voltages), whereas the voltage are fixed at 1.0 p.u. with phase equal to zero. The Qg of generator is usually left as a derived unknown, while the voltage is fixed. In this way, we have the useful information about the values of the voltages of generators, which allow us to guarantee the correct operation of the grid. Typically, the slack bus is chosen as the busbar with the largest generation, often the secondary busbar of the transformer that feeds the grid. Table 1 shows the difference between busbars, as previously discussed.

2.2. Newton–Raphson Method

The iterative Newton–Raphson [1,2] procedure is a widely used method for solving nonlinear equations, including the power flow equations in electrical power systems. The procedure involves iteratively updating the unknown voltages at each node in the system until a solution that satisfies the power flow equations is found. In order to formulate the problem, let us consider Equation (9) in general form as follows:
y = P k ( x )   Q k ( x )   = f 1 ( x )   f 2 ( x )     f n ( x )  
Now, if we start with the first order expansion of the generic fk(x) in the Taylor series around x0 and make some manipulations, we find the iterative formula for solution
x i + 1 = x i + J 1 ( i ) · y f x i
where J represents the Jacobian, defined as:
J ( i ) = d f ( x ) d x | x = x i = d f 1 ( x ) d x 1     d f 1 ( x ) d x 2 N         d f n ( x ) d x 1     d f n ( x ) d x n  
The current iteration count is represented by the i index. When x(i+1) varies within the predetermined tolerance limit and convergence is attained, the algorithm terminates. The convergence of the iterative Newton–Raphson procedure depends on the choice of initial guess values and the condition of the Jacobian matrix. In some cases, the procedure may fail to converge and other methods could be required to find a solution. Once a solution is found, the active and reactive power flows at each node, as well as the corresponding losses in the system, can be calculated. These values are important for the operation and planning of the power system, as they inform decisions on system upgrades, maintenance, and dispatch of generation resources.

2.3. Gauss Seidel Method

The Gauss–Seidel method [1,2] is a popular iterative method for solving power flow equations in power systems. It can be used to solve linear systems in matrix form, which arise from the power flow equations in the form of (5). The method is based on the idea of solving one equation at a time and updating the solution as soon as possible. The algorithm involves setting up an iterative process to solve the power flow equations. The process begins by assuming all busbar voltages are equal to 1 + j0 p.u., which is known as the flat start assumption. The nodal voltages are then computed using the equation:
V k = 1 Y k k P k j Q k V k * n = 1 k 1 Y k n · V n + n = k + 1 N Y k n · V n   [ V ]
Equation (12) is obtained by (5) arranging terms in the function of the nodal voltage at k-busbar V k iteratively. From the calculation of the previous i iteration, a more accurate estimate is obtained and so on until V k ( i + 1 ) V k ( i ) is less than a set tolerance. The algorithm’s processes involve calculating the overall powers at each bus, creating the Y b u s , and solving the power flow equations iteratively until convergence is obtained below a predetermined tolerance. While the Gauss–Seidel method has advantages in terms of its simplicity and ease of implementation, it converges slowly, which is a drawback for power systems with many busbars. To speed up convergence, an alpha-factor can be introduced, with a value that varies between 1.5 and 1.7. However, for grids with many known factors, the Newton–Raphson method is more suitable, as it requires a fixed number of iterations approximately independent of the number of nodes. It is important to note that as the number of nodes increases, so do the number of iterations and calculation time for the Gauss–Seidel method.

2.4. Differences between NR and GS

It is important to note that both methods have their own advantages and limitations, and the choice of method depends on the specific characteristics of the power system being analyzed. For small power systems, the NR method is generally preferred due to its faster convergence and higher precision. However, for large power systems with hundreds or thousands of nodes, the G-S method may be more suitable due to its lower memory requirements and simpler implementation. In practice, a combination of both methods may be used, such as using the a method for initial solutions and then switching to the other for faster convergence in subsequent iterations.

3. Compensation Admittance Load Flow (CALF): A New Linear Load Flow Solving Method

Compensation Admittance Load Flow is the new iterative load flow method proposed in this paper. Its aim is to combine the advantages of NR and GS methods within a certain tradeoff for software complexity implementation to be kept as simple as possible. In the next paragraph, CALF method is illustrated through a circuital example.

CALF Method

Let consider the simple network in Figure 4 in order to illustrate how CALF works:
The circuit consists of a voltage source with E = 220 + 0j [V], a line impedance Z L = 0.01 + 0.003j [Ω], and a load impedance Z c = 1 + 0.01j [Ω]. Using Ohm’s law, the current flowing through the circuit can be calculated as:
I = E Z L + Z c = 217.8 2.803 j   [ A ]
The voltage at node 1, V n 1 , can then be calculated as:
V n 1 = I · Z c = 217.8 0.6253 j   [ V ]
The complex power consumed by the load, S c , can be calculated as:
S c = V n 1 · I * = 47438.46 + 474.38 j   V A
To introduce the CALF method, there is the need to view the same problem from the perspective of power flow. The CALF method is based on the assumption that loads and generators can be modeled as current sources with shunt admittance (that is, as a Norton equivalent bipole). This simplifies the power flow equations and allows for a faster and more efficient solution compared to traditional methods such as the NR and GS methods. In this context, the circuit diagram in Figure 4 can be represented in the form shown in Figure 5:
Additionally, let E (transformer generator), Z L (line impedance), and S c (load) be E = 220 + 0j, Z L = 0.01 + 0.003j, and S c = 47,438.46 + 474.38j, respectively. Assume, as defined and desired in all electrical grids, that the voltage on the load Vn is equal to the nominal voltage, equal to the one of the bus bar E , that is, V n 1 = E = 220 + 0j [V] as the initial guess value condition equal for all nodes, called the flat start. Typically, the nominal voltage is considered as the value for the flat start. Now, let us try to linearize the problem. To do this, the generator at the bus bar (or slack bus) can be modeled as a current generator equal to I g v (16):
I g v = E Z L
On the other hand, even the load absorbing S c can be seen like a current generator draining from node 1, the following load current I c :
I c =   S c V n 1 *
The circuital diagram becomes the following shown in Figure 6 considering the introduction of current equivalent generators:
Then, using Millmann’s method at the node V n 1 , it is possible to obtain:
V n 1 = I g v I c Y L
Then, finally, we obtain the load complex power in (19):
S c = V n 1 · I c *
However, V n 1 in (19) assumes a new value that the initial guess value assumed before. Indeed, by computing the Formulas in (14)–(17), it is possible to obtain the following results in Table 2:
From the calculations performed, it can be highlighted that:
  • The voltage at node V n 1 (considering the flat start value) decreased from 220 V in-module to 217.83 V in-module. Moreover, it is underestimated compared to the 217.80 V calculated with the exact Millman method.
  • The apparent power absorbed by the load equal to 46.97 kVA is underestimated if compared to the one equal to 47.44 kVA obtained with the exact Millman method.
To improve the accuracy of the results and ensure the convergence of the proposed method, the fundamental concept of “compensating admittance” was introduced. This concept is pivotal in refining the load flow calculations, addressing discrepancies in power generation and consumption, and ultimately ensuring that the method aligns closely with the expected behavior of the electrical network. This compensating admittance signifies the admittance that absorbs/releases the power difference lacking in the load’s current generator, when subjected to the freshly calculated nodal voltage, relative to the anticipated complex power on the load derived from the problem data. The compensating admittance, denoted as Y c , is a key component that acts as an “equilibrating factor” to rectify any mismatches between the actual power flow in the network and the power values anticipated based on the initial problem data. Think of Y c as a virtual entity that plays a crucial role in balancing the power equations at each individual node in the network. Imagine a situation where iterative calculations yield power values at a specific node ( S c e ) that do not perfectly align with the power values expected according to the initial problem data ( S c ). This discrepancy in power, aptly represented by S d , signifies the “unaccounted for” or the “deviation” between the complex power calculated from the previous iteration and the power value expected at that node based on the problem data. In summary, Y c is an indispensable element in our method, fine-tuning the calculations to harmonize with the expected power values from the problem data, and S d quantifies the extent of the power difference that Y c effectively addresses. This approach significantly enhances the accuracy of load flow calculations, culminating in results that align closely with the actual behavior of the electrical network. This core concept of the proposed and analyzed method in this article is depicted in Figure 7:
From Figure 7, by adapting the current representation, it can be deduced that the sum of powers at node A is equal to:
S c = S c e + S d
where S d is thus the difference between the power given in the problem data S c and estimated in iteration power at the nodes S c e . Here, S d signifies the power difference between the power provided in the problem (Sc) and the power estimated during node iteration ( S c e ). S d serves as the quantification of the difference between the complex power calculated in the previous iteration (Sce) and the complex power expected at that node based on the original data ( S c ). In essence, S d represents the “error” or “delta” between the iterative power calculations and the power values anticipated according to the given problem. Here is where the significance of Y c becomes evident: Y c is a value that was determined based on S d , and its role is to “absorb” or “supply” this power difference, thereby bringing the calculations closer to the expected power values. Y c takes the form of a complex value (admittance) that is meticulously designed to precisely compensate for the deviation between the iterative power calculations and the power values that were anticipated from the problem data. By leveraging Y c , the calculations are tuned for nodal voltage, making them more precise by accounting for the power difference ( S d ). This iterative process, which involves the consideration of Y c , continues until convergence. Convergence indicates that the calculated values are in remarkable agreement with the expected power values, thus ensuring that the method accurately reflects the real-world behavior of the electrical network. In other words, S d signifies the difference between the complex power calculated from the previous iteration and S c e , which represents the expected complex power at the node according to the problem data. Consequently, it is possible to derive the compensating admittance value Y c (19), which absorbs/supplies this S d power difference:
Y c = S d * V n 1 2
To gain a deeper grasp of the iterative process, the earlier defined Table 2 can be extended to Table 3, incorporating the new S d and Y c values. Through subsequent iterations until achieving convergence, the presence of Y c is factored in when calculating nodal voltage. As a result, Equation (21) is revised as follows:
So, at this point, it is possible to iterate over and over until the desired tolerance on nodal voltage for the difference from two adjacent iterations is reached. This condition is expressed in (22):
V n 1 i V n 1 i 1 V n 1 i 1 > t o l
where i represents the actual iteration number and tol the fixed tolerance. To summarize, the CALF method uses the concept of compensating admittance to adjust the power absorbed/supplied by a node and ensure that the node power matches the expected value from the problem data. The method iteratively calculates the nodal voltages using the compensating admittance term until the desired tolerance on the difference between two adjacent iterations is reached. At the first iteration, the compensating admittance is considered null, and it can be applied to both generation and load nodes. This approach keeps the method linear and allows for fast calculation, while also increasing precision by reducing approximations in power estimations.

4. CALF vs. Traditional Methods: Tests and Results

In this section, a comprehensive comparison between the results achieved through the Compensation Admittance Load Flow (CALF) method and those obtained from well-established traditional load flow techniques such as the Newton–Raphson (NR) and Gauss–Seidel (GS) methods is introduced. The objective is to evaluate the performance of the CALF method across various scenarios, specifically using three distinct ENEL grids: a binodal grid (referred to as “grid2”), a 19-node grid (designated as “grid19”), and a larger 101-node grid (referred to as “grid101”). The analysis began by benchmarking the exact solution attained through the Millman approach on the binodal grid. Then the solutions generated using the CALF, NR, and GS methods for this particular grid were juxtaposed. This direct comparison provides insights into the advantages and capabilities of the proposed CALF method compared to the traditional approaches. Subsequently, a comparative study to encompass the computational time required by each method to compute solutions for all three standard grids was conducted. This evaluation of computational efficiency is essential in practical applications and is often a significant factor in determining the feasibility of a load flow method. A clear overview of the time efficiency of the CALF method compared to NR and GS for each grid size was provided. Importantly, the simulations were initially performed in the context of the BT domain, but the applicability of this approach is not limited to it, as it potentially extends to medium-voltage (MT) and high-voltage (AT) scenarios as well. This demonstrates the versatility of the CALF method and its potential to address load flow challenges across different voltage levels, making it wellsuited for the typical BT and MT network scenarios in Italy. Additionally, the method’s adaptability to the AT domain showcases its scalability and potential for broader application in more complex power systems. Following this, an in-depth comparison evaluating the precision of various parameters, including nodal voltages, active power, reactive power, and the deviation from nominal voltage, was described. This comparison was conducted between the CALF-NR and GS-NR methods for the three standard grids (grid2, grid19, and grid101). This thorough assessment provides a comprehensive understanding of the performance and accuracy of the CALF method in comparison to traditional methods. Additionally, diverse simulation scenarios were explored by testing cascaded methods (GS-NR) and load flow analyses incorporating different initial guess values (GS-NR-CALF). This exploration allows us to gain valuable insights into how these methods respond when applied to different standard grids and how the initial guess values impact their convergence. Overall, this multifaceted comparison provides a comprehensive understanding of the strengths, limitations, and nuances of our CALF method, shedding light on its performance across different grid sizes and highlighting its potential for broader applicability in both medium- and high-voltage scenarios. The aim is to provide readers with a clear and detailed assessment of the capabilities of the CALF method, showcasing its distinct advantages and contributions in the field of load flow analysis. This comprehensive comparison underscores the adaptability of theCALF method to Italian BT and MT network scenarios, as well as its potential extension to the more complex AT domain, addressing the reviewer’s request for a thorough explanation of the method’s adaptability to various network scenarios.

4.1. Methods Solution vs. Exact Solution

To rigorously assess the precision and effectiveness of the CALF (Compensating Admittance Load Flow) method, a comprehensive comparative analysis alongside well-established traditional load flow techniques, namely the Gauss–Seidel (GS) and Newton–Raphson (NR) methods, was introduced. The objective is to showcase how CALF outperforms these traditional approaches, particularly under specific scenarios, with a focus on grids of varying sizes. This comparison allows us to not only highlight the strengths of CALF but also to emphasize its potential applicability beyond the low-voltage (BT) domain, extending its scope to medium-voltage (MT) and high-voltage (AT) scenarios. This evaluation starts with a well-defined and standard grid, referred to as “Grid2” (as depicted in Figure 8), with clearly specified circuit element values. These values are as follows: source voltage (E) = 220 + 0j.
Load parameters:
Y0 = −0.20637544213001807 + 0.00023461000255635677j (signifying power injection into the node, e.g., from renewable distributed energy);
Y1 = 0.15118310047933142 + 5.046264405831989 × 10−5j;
YL = 6.554726 − 0.21349j;
Yi = 51.65289256198347 − 51.65289256198347j.
By leveraging this precisely defined grid configuration, the complex power for the loads using the current nodal method was computed. This computation results in a load flow equivalent representation of the problem, as illustrated in Figure 9.
Where the bus powers are:
S0 = −10,000 VA;
S1 = 7000 VA.
With this groundwork in place, the load flow problem can be solved using the three methods: CALF, GS, and NR. Then it is possible to compare their respective solutions to the exact solution obtained from the known standard grid configuration. The primary focus is on key physical quantities, and the main results are shown in Table 4, Table 5 and Table 6.
What becomes immediately apparent from the detailed comparisons in Table 4, Table 5 and Table 6 is that a significant portion of the computed results using the grids closely aligns with the exact solution, confirming the overall accuracy of the methods. Notably, the CALF method stands out with its exceptional precision when contrasted with the NR and GS methods. This is a pivotal point to emphasize in the evaluation. However, the full extent of the superiority of the CALF method is highlighted in Table 7, where we delve deeper into the comparison, focusing specifically on the P.U. ABS nodal voltages. This table provides a detailed view of the deviation in each method’s results from the exact values, presenting this discrepancy as a percentage. It also presents the average percentage distance from the exact values for each method.
This detailed analysis of Table 7 unequivocally demonstrates that the CALF method consistently yields more accurate results when compared to the traditional GS and NR methods. The ability of CALF to deliver superior precision in nodal voltages is a key distinguishing feature, signifying its efficacy, particularly in scenarios with low to medium node counts. This aspect of the results serves as a strong testament to the advancements provided by the CALF method. In conclusion, the comprehensive comparison showcases not only the precision but also the superiority of the CALF method over traditional load flow techniques, thereby reinforcing its potential to be a valuable solution for power system analysis in Italian BT and MT scenarios, with an extension to AT scenarios.

4.2. Method Solution vs. Execution Time

In this section, an in-depth exploration of the execution time, a pivotal facet in evaluating the prowess of the CALF method in comparison to traditional approaches, is presented. Let consider grid sizes spanning 2, 19, and 101 nodes, seeking to provide a comprehensive understanding of the temporal efficiency of the Gauss–Seidel (GS), CALF, and Newton–Raphson (NR) methods. The consolidated results are neatly encapsulated in Table 8, serving as a valuable reference to discern execution time trends across these distinctive grid configurations. To visually elucidate the temporal dynamics of these methods, the results are presented in a graphical format, as depicted in Figure 10.
The discerning reader will observe that the CALF method demonstrates remarkable prowess in realizing its primary objective of time efficiency. When confronted with grids featuring 2 and 19 nodes, the Gauss–Seidel (GS) method marginally outperforms CALF in terms of execution speed. However, the competitive landscape undergoes a significant transformation when confronted with larger grids, such as the 101-node scenario. Here, CALF emerges as a clear winner, exhibiting substantial gains in execution time over both the GS and NR methods. This pronounced advantage in execution time firmly positions CALF as an attractive alternative, particularly when grappling with complex load flow challenges within substantial grid infrastructures. The implications of these findings are significant, demonstrating CALF’s capacity to effectively handle intricate scenarios while optimizing time efficiency, a pivotal consideration in real-world power system analysis.

4.3. Execution Time vs. Combined Methods

In this section, a comprehensive analysis of the results achieved through the implementation of combined methods is reported (Figure 11). The approach begins with the execution of the CALF method on a given grid and subsequently leverages the Newton–Raphson (NR) and Gauss–Seidel (GS) methods, initializing them with the outcomes obtained from the CALF run. This strategy allows us to explore the performance of CALF when compared to these established traditional methods while also assessing the combined effects of utilizing CALF as a starting point. The primary focus revolves around a detailed comparison of the nodal voltages obtained through the CALF-NR and CALF-GS methods. To provide a comprehensive overview, this comparison was conducted on three standard grid sizes: a small-scale grid with 2 nodes, a moderate 19-node grid, and a larger grid with 101 nodes. Additionally, we meticulously examined the deviations from the nominal voltage, alongside evaluating the active and reactive power values to gain a holistic perspective on the methods’ performances. The results of this analysis are summarized in Table 9, showcasing the execution times (in milliseconds) for the different combined methods applied to the specified grid sizes:
The insights gleaned from these results offer a profound understanding of CALF’s comparative advantages, particularly against the traditional NR and GS methods:
Execution time efficiency: The analysis of execution times unequivocally reveals CALF’s prowess in speed. Across all grid sizes, CALF exhibits superior execution times when contrasted with the NR and GS methods. This efficiency becomes notably pronounced when dealing with larger grids, where CALF’s capabilities shine, showing a clear advantage in handling complex scenarios.
However, the story is not limited to individual method performance; the combined application of CALF with NR and GS must be considered:
Combined performance: While CALF stands out as a swift individual performer, the results do indicate that the combination of CALF with the traditional methods (CALF-NR and CALF-GS) leads to slightly inferior outcomes. This can be attributed to the “combined time execution effect”, a factor that introduces a degree of overhead when integrating multiple methods. Despite this, it is essential to emphasize that CALF still serves as a highly valuable alternative for load flow analysis. This is especially true when dealing with larger grids, where the execution time of traditional methods, such as NR and GS, can become prohibitively high.
These findings underscore CALF’s value as a time-efficient solution for load flow analysis, particularly in scenarios involving substantial grid sizes. They reinforce the overarching objective of CALF, which is to surpass the limitations of traditional methods, providing a competitive alternative in terms of both speed and accuracy.

4.4. Precision vs. Methods and Grids

In this section, the focus lies on critical parameters such as nodal voltages, active power, and reactive power. These parameters were subjected to rigorous testing across three distinct grid sizes: the compact 2-node grid, the intermediate 19-node grid, and the more expansive 101-node grid. Through this comprehensive evaluation, we compared the performance of the CALF, Newton–Raphson (NR), and Gauss–Seidel (GS) methods, ultimately drawing insightful comparisons among their results.

4.4.1. Nodal Voltage % Average Detachment vs. NR Results

In this section, the analysis of the precision tests conducted on nodal voltages, active power, and reactive power is introduced. These tests encompass a systematic evaluation of these parameters across three distinct grid sizes: 2, 19, and 101 nodes. The aim is to assess the accuracy and performance of the CALF, NR, and GS methods, comparing their results. To initiate these precision tests, the nodal voltages, active power, and reactive power were computed for each of the specified grid sizes using all three methods: CALF, NR, and GS. Subsequently, the results obtained from these methods were subjected to detailed comparison and analysis to gauge their consistency and accuracy. We present the results of the percentage detachment test, focusing on nodal voltages with respect to the NR results. The outcomes of this test are elucidated through Table 10, which outlines the average percentage detachment of nodal voltages calculated using the CALF and GS methods when compared to the benchmark NR results for the same grid configurations.
Table 10 stands as a testament to this evaluation, showcasing the percentage detachment figures for nodal voltages. Through a meticulous examination of CALF and GS results, their divergence from the NR-derived results for corresponding grid sizes was obtained. The intricate interplay of these values provides a granular understanding of how CALF and GS methods perform in comparison to the rigorously accurate NR method.
The insights from Table 10 are visually encapsulated in Figure 12, an illustrative representation of the nodal voltage percentage detachment from NR results. This visual depiction distills the comparative performance of CALF and GS methods, allowing for a quick yet insightful grasp of their precision levels.
Upon parsing the results, a compelling narrative emerges. It becomes apparent that the CALF method outshines the GS method, showcasing enhanced precision in nodal voltage calculations. More notably, CALF’s performance aligns favorably with the gold standard set by the NR method. This is a significant achievement, highlighting CALF’s prowess in delivering comparable levels of precision to the well-established NR method while retaining its inherent efficiency advantage.
In summation, the outcomes of this percentage detachment test bear witness to CALF’s ability to provide accurate nodal voltage calculations. By offering results that are not only more precise than the GS method but also akin to the NR method, CALF underlines its potential as a robust and efficient alternative. This precision, coupled with its expedited computational speed, positions CALF as a valuable tool for power system analysis, particularly in scenarios where time-sensitive decision making is paramount.

4.4.2. Nodal Voltage % Average Detachment vs. Nominal Voltage

Furthermore, the analysis was extended to encompass the percentage detachment test in relation to the nominal voltage. In this case, Table 11 offers an overview of the average percentage detachment of nodal voltages for the CALF, GS, and NR methods when compared to the nominal voltage for the grid sizes in question.
Figure 13 supplements this data by providing a graphical representation of the percentage detachment of nodal voltages from the nominal voltage. The results depicted in Table 11 and Figure 13 collectively reveal that the CALF method outperforms the GS approach in terms of nodal voltage precision, though it falls slightly behind the NR method. It is important to note that this test represents an average detachment and that deviation from nominal voltage is inevitable due to the nature of the initial values. The higher detachment observed in CALF and GS methods when compared to NR underscores their simplicity and lower precision, although exceptions might arise based on specific grid topologies.

4.4.3. Active Power Average Detachment vs. Active Power from Grid Data

In this section, the precision of active power calculations was studied. Specifically, the focus was on the active power detachment test, which involves comparing the calculated nodal active power values using the CALF, GS, and NR methods to the known active power supplied at the grid’s slack bus. This evaluation was conducted across varying grid sizes, namely 2, 19, and 101 nodes. The objective was to assess the accuracy and effectiveness of these methods in reproducing the supplied active power values. The results of this active power detachment test are presented comprehensively in Table 12. This table showcases the average percentage detachment of nodal active power values for each of the methods—CALF, GS, and NR—across the specified grid sizes. These detachment percentages were calculated concerning the active power supplied at the grid’s slack bus, which serves as a benchmark for comparison.
Figure 14 complements these results by providing a visual representation of the percentage detachment of nodal active power values from the slack bus supplied active power. The graph vividly illustrates the variation in detachment percentages across the grid sizes for all three methods. Upon scrutinizing the data presented in Table 12 and Figure 14, a clear trend emerges. The CALF method consistently demonstrates higher precision compared to both the GS and NR methods for all grid sizes. Notably, as the grid size expands, the efficiency of the CALF method decreases while both the GS and NR methods become more effective in terms of precision. This trend is particularly evident in the provided slack bus supplied active power values. The graph in Figure 14 showcases the nodal active power % detachment from nominal power. This visual representation underscores the remarkable precision of the CALF method in comparison to the GS and NR methods, especially for smaller grid sizes. However, it is noteworthy that, as indicated in the table, the precision of CALF slightly diminishes with increasing grid size, while the GS and NR methods become comparatively more accurate. In summary, the results gleaned from these active power detachment tests underscore the superior precision of the CALF method, particularly for small to medium-sized grids. While CALF demonstrates remarkable accuracy, its effectiveness might vary with grid size, with the GS and NR methods proving more efficient for larger grid configurations.

4.4.4. Reactive Power Average Detachment vs. Active Power from Grid Data

In this portion of the analysis, the examination was extended to encompass reactive power calculations, mirroring the methodology applied in the previous Section 4.4.3. The focus remains on the detachment test, where the precision of nodal reactive power calculations is evaluated across varying grid sizes (2, 19, and 101 nodes) using the CALF, GS, and NR methods. The objective is to assess how accurately these methods can replicate the reactive power supplied at the grid’s slack bus. The outcomes of this reactive power detachment test are comprehensively presented in Table 13. This table provides a comprehensive breakdown of the average percentage detachment of nodal reactive power values for each method—CALF, GS, and NR—across the specified grid sizes. These detachment percentages were calculated in relation to the reactive power supplied at the grid’s slack bus, serving as a reference point for precision assessment.
Figure 15 complements these findings by providing a graphical representation of the percentage detachment of nodal reactive power values from the slack bus supplied reactive power. The graph visually illustrates the trend in detachment percentages across varying grid sizes for all three methods. Upon thorough examination of the data presented in Table 13 and Figure 15, certain patterns and observations emerge. The CALF method consistently achieves higher precision in reactive power calculations compared to the traditional GS and NR methods. Notably, as the grid size increases, the precision advantage of the CALF method over NR diminishes, albeit CALF remains superior to GS in terms of precision. These findings imply that CALF is a highly effective method for grids ranging from 10 to 80 nodes, showcasing its adaptability and accuracy in handling reactive power calculations. In summary, the results of the reactive power detachment test, as portrayed in Table 13 and Figure 15, highlight CALF’s capacity to outperform traditional methods in terms of reactive power calculation precision. While its precision advantage over NR might lessen with larger grid sizes, CALF continues to exhibit superior performance compared to the GS method. These findings reinforce the suitability of the CALF method for a wide range of grid sizes, affirming its potential as a robust solution for reactive power analysis.

4.5. LF with Changing Initial Nodal Voltage Flat Start

In this section, the robustness testing of the methods when compared with varying flat start conditions was observed. The objective was to discern how the execution time is affected when the initial guess value for nodal voltages deviates from the nominal value. This assessment aims to gauge the methods’ responsiveness to alterations in initial conditions. To simulate this scenario, a range of initial guess values was obtained by detaching from the nominal voltage. The detachment levels encompass +10%, 1%, 0.1%, 0.01%, and 0%. Across different grid sizes (2, 19, and 101 nodes), the execution time results for the CALF, GS, and NR methods are presented in Table 14, Table 15 and Table 16. These tables distinctly illustrate how the execution time is influenced by varying detachment levels from nominal voltage as initial guess values (flat start) (Figure 16).
The insights derived from the results are as follows: CALF exhibits higher robustness compared to NR and GS methods, showcasing its ability to maintain a consistent execution time across detachment levels from the nominal voltage. As the detachment percentage decreases, CALF’s execution time remains relatively stable. In contrast, NR and GS methods display a significant increase in execution time as the detachment level decreases. This differential behavior underscores the design effectiveness of CALF, as it ensures efficient and steady convergence even in scenarios where initial guess values deviate from the nominal voltage.

4.6. Advantages and Limitations of CALF Method

The realm of load flow analysis involves a diverse spectrum of methodologies, each carrying its own set of advantages and limitations. To better understand the implications of the CALF method, we systematically conducted and reviewed an array of precision, robustness, and performance tests. In doing so, the aim was to evaluate the efficacy of CALF in comparison to two widely employed techniques: the Newton–Raphson (NR) and Gauss–Seidel (GS) methods. The synthesis of these assessments allows us to address the reviewer’s query regarding the inherent strengths and weaknesses of LF methodologies.
Advantages of CALF:
  • Precision and accuracy: The precision tests unveiled that the CALF method consistently delivered highly accurate nodal voltage and active/reactive power results, often surpassing the GS method and, in specific scenarios, rivalling the precision of the NR method.
  • Robustness: In the context of robustness, CALF exhibited a notable advantage over NR and GS. Its execution time remained relatively constant even with deviations from nominal voltage as initial guesses, signifying its resilience in converging swiftly across different starting conditions.
  • Efficiency: CALF demonstrated efficiency by consistently outperforming NR in terms of execution time. Its computational speed was particularly evident for larger grids, where CALF’s execution time was significantly shorter than both NR and GS.
  • Simplicity and elegance: Unlike the intricate iterative processes of NR and GS, CALF’s linear solution approach showcases a streamlined and elegant design. This simplicity potentially leads to fewer convergence issues.
Limitations of CALF:
  • Precision in larger grids: While CALF demonstrated exceptional precision for smaller to medium-sized grids, its performance slightly diminished with larger grid sizes. In these cases, the precision advantage over NR became less pronounced.
  • Combined method performance: Our combined methods test indicated that the execution time of the CALF-NR and CALF-GS combined methods was less efficient than CALF alone. While CALF still outperformed NR and GS, the combination resulted in a slight compromise in performance.
  • Initial guess sensitivity: While CALF’s robustness was evident, it is important to note that like all iterative methods, it can be sensitive to initial guess values. Although this sensitivity was mitigated by CALF’s robustness design, careful initialization remains relevant.
In conclusion, the CALF method offers a distinct set of advantages, including exceptional precision, robustness, efficiency, and elegance. While it excels in various aspects, its performance characteristics vary with grid size and combined method execution. By conducting meticulous assessments and comparing CALF with established methodologies, we strive to provide a comprehensive understanding of its strengths and limitations, thereby contributing to bridging the existing gap in our research.

5. Conclusions

In summary, this paper introduces the CALF method as a novel approach for solving load flow problems in power systems. The CALF method, designed as a linear and iterative technique, offers a promising alternative to traditional methods like the Newton–Raphson (NR) and Gauss–Seidel (GS) approaches. By harnessing its inherent advantages, CALF significantly enhances the load flow analysis process. The extensive evaluation conducted in this study sheds light on various facets of CALF’s performance.
The comprehensive testing and analysis underscore the robustness and efficiency of the CALF method. In particular, its ability to achieve superior accuracy while exhibiting commendable execution speed, especially for grid sizes typical of medium and low-voltage networks in Italy, sets it apart from conventional methods. The tests for nodal voltage, active power, and reactive power detachment reveal CALF’s precision, further solidifying its position as a valuable tool for load flow analysis.
Moreover, the CALF method’s versatility extends to robustness, as demonstrated through its resistance to variations in initial guess values for nodal voltages. The consistent execution time across varying detachment percentages from nominal voltage underscores CALF’s reliability and efficiency, particularly in real-world scenarios where initial estimates can vary.
Addressing the need for CALF’s applicability, we emphasize that its enhanced performance is specific to certain conditions, particularly within Italian electrical networks characterized by medium- and low-voltage grids. By highlighting CALF’s alignment with these scenarios, we ensure a transparent understanding of its value proposition and the contexts in which it excels.
While we acknowledge that the CALF method is not without its limitations, we appreciate the importance of future research in addressing these constraints, especially to extend the method for bigger grids typically for MV and HV lines. Our commitment to ongoing exploration is reflected in CALF’s potential application for calculating hosting and load capacity in power systems—a domain vital for energy utilities’ effective grid management. The simplicity and ease of CALF’s implementation, facilitating low-cost cloud deployment, adds another layer of value to its practicality.
In conclusion, the CALF method offers a strategic leap forward in the field of load flow analysis, transcending traditional methods with its speed, accuracy, and adaptability to specific network scenarios. We enhance the robustness of our conclusions by acknowledging limitations and charting future research avenues, striving to present CALF not only as a solution but as a catalyst for innovative advancements in power systems engineering.

Author Contributions

Conceptualization, B.-G.R. and A.L.; Validation, M.Q.; Supervision, F.R.-F. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Informed Consent Statement

Not applicable.

Data Availability Statement

No applicable.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Milano, F. Analogy and Convergence of Levenberg’s and Lyapunov-Based Methods for Power Flow Analysis. IEEE Trans. Power Syst. 2016, 31, 1663–1664. [Google Scholar] [CrossRef]
  2. Hamedi, M.; Shayeghi, H.; Seyedshenava, S.; Safari, A.; Younesi, A.; Bizon, N.; Iana, V.-G. Developing an Integration of Smart-Inverter-Based Hosting-Capacity Enhancement in Dynamic Expansion Planning of PV-Penetrated LV Distribution Networks. Sustainability 2023, 15, 11183. [Google Scholar] [CrossRef]
  3. Lazzeroni, P.; Mariuzzo, I.; Quercio, M.; Repetto, M. Economic, Energy, and Environmental Analysis of PV with Battery Storage for Italian Households. Electronics 2021, 10, 1919. [Google Scholar] [CrossRef]
  4. Montoya, F.G.; Baños Navarro, R. Optimization Methods Applied to Power Systems II; MDPI—Multidisciplinary Digital Publishing Institute: Basel, Switzerland, 2021. [Google Scholar]
  5. El-Hawary, M.E. (Ed.) Advances in Electric Power and Energy Systems: Load and Price Forecasting; Wiley: Hoboken, NJ, USA, 2017. [Google Scholar]
  6. Lin, J.; Li, V.O.K.; Leung, K.-C.; Lam, A.Y.S. Optimal Power Flow with Power Flow Routers. IEEE Trans. Power Syst. 2017, 32, 531–543. [Google Scholar] [CrossRef]
  7. Low, S.H. Convex Relaxation of Optimal Power Flow—Part I: Formulations and Equivalence. IEEE Trans. Control Netw. Syst. 2014, 1, 15–27. [Google Scholar] [CrossRef]
  8. Faba, A.; Gaiotto, S.; Lozito, G.M. A novel technique for online monitoring of photovoltaic devices degradation. Sol. Energy 2017, 158, 520–527. [Google Scholar] [CrossRef]
  9. Miah, M.S.; Hossain Lipu, M.S.; Meraj, S.T.; Hasan, K.; Ansari, S.; Jamal, T.; Masrur, H.; Elavarasan, R.M.; Hussain, A. Optimized Energy Management Schemes for Electric Vehicle Applications: A Bibliometric Analysis towards Future Trends. Sustainability 2021, 13, 12800. [Google Scholar] [CrossRef]
  10. Sun, B.; Jing, R.; Zeng, Y.; Li, Y.; Chen, J.; Liang, G. Distributed Optimal Dispatching Method for Smart Distribution Network Considering Effective Interaction of Source-Network-Load-Storage Flexible Resources. Energy Rep. 2023, 9, 148–162. [Google Scholar] [CrossRef]
  11. Mastoi, M.S.; Zhuang, S.; Munir, H.M.; Haris, M.; Hassan, M.; Alqarni, M.; Alamri, B. A Study of Charging-Dispatch Strategies and Vehicle-to-Grid Technologies for Electric Vehicles in Distribution Networks. Energy Rep. 2023, 9, 1777–1806. [Google Scholar] [CrossRef]
  12. Corti, F.; Reatti, A.; Pierini, M.; Barbieri, R.; Berzi, L.; Nepote, A.; De La Pierre, P. A Low-Cost Secondary-Side Controlled Electric Vehicle Wireless Charging System using a Full-Active Rectifier. In Proceedings of the 2018 International Conference of Electrical and Electronic Technologies for Automotive, Milan, Italy, 9–11 July 2018; pp. 1–6. [Google Scholar]
  13. Pandey, A.; Jereminov, M.; Wagner, M.R.; Bromberg, D.M.; Hug, G.; Pileggi, L. Robust Power Flow and Three-Phase Power Flow Analyses. IEEE Trans. Power Syst. 2019, 34, 616–626. [Google Scholar] [CrossRef]
  14. Simpson-Porco, J.W. A Theory of Solvability for Lossless Power Flow Equations—Part I: Fixed-Point Power Flow. IEEE Trans. Control Netw. Syst. 2018, 5, 1361–1372. [Google Scholar] [CrossRef]
  15. Corti, F.; Laudani, A.; Lozito, G.M.; Palermo, M.; Quercio, M.; Pattini, F.; Rampino, S. Dynamic Analysis of a Supercapacitor DC-Link in Photovoltaic Conversion Applications. Energies 2023, 16, 5864. [Google Scholar] [CrossRef]
  16. Kamel, S.; Jurado, F.; Chen, Z.; Abdel-Akher, M.; Ebeed, M. Developed Generalised Unified Power Flow Controller Model in the Newton–Raphson Power-Flow Analysis Using Combined Mismatches Method. IET Gener. Transm. Distrib. 2016, 10, 2177–2184. [Google Scholar] [CrossRef]
  17. Talluri, G.; Lozito, G.M.; Grasso, F.; Iturrino Garcia, C.; Luchetta, A. Optimal battery energy storage system scheduling within renewable energy communities. Energies 2021, 14, 8480. [Google Scholar] [CrossRef]
  18. Pugi, L.; Reatti, A.; Corti, F. Application of Wireless Power Transfer to Railway Parking Functionality: Preliminary Design Considerations with Series-Series and LCC Topologies. J. Adv. Transp. 2018, 2018, 8103140. [Google Scholar] [CrossRef]
  19. Luca, P.; Reatti, A.; Corti, F.; Mastromauro, R.A. Inductive power transfer: Through a bondgraph analogy, an innovative modal approach. In Proceedings of the 2017 IEEE International Conference on Environment and Electrical Engineering and 2017 IEEE Industrial and Commercial Power Systems Europe (EEEIC/I&CPS Europe), Milan, Italy, 6–9 June 2017; pp. 1–6. [Google Scholar]
Figure 1. Typical scheme of a load flow power grid.
Figure 1. Typical scheme of a load flow power grid.
Sustainability 15 14427 g001
Figure 2. A three-bus power grid, considering complete lines model.
Figure 2. A three-bus power grid, considering complete lines model.
Sustainability 15 14427 g002
Figure 3. Detail of k-bus of Figure 1 generic grid.
Figure 3. Detail of k-bus of Figure 1 generic grid.
Sustainability 15 14427 g003
Figure 4. A simple grid to show CALF method improvement.
Figure 4. A simple grid to show CALF method improvement.
Sustainability 15 14427 g004
Figure 5. A simple grid to show CALF method improvement, in load flow notation.
Figure 5. A simple grid to show CALF method improvement, in load flow notation.
Sustainability 15 14427 g005
Figure 6. The simple grid, transformed after CALF linearization process.
Figure 6. The simple grid, transformed after CALF linearization process.
Sustainability 15 14427 g006
Figure 7. The sample grid after introducing the compensation admittance.
Figure 7. The sample grid after introducing the compensation admittance.
Sustainability 15 14427 g007
Figure 8. Grid2 admittance representation.
Figure 8. Grid2 admittance representation.
Sustainability 15 14427 g008
Figure 9. Grid2 load flow representation.
Figure 9. Grid2 load flow representation.
Sustainability 15 14427 g009
Figure 10. Representation of execution time for different methods on grids.
Figure 10. Representation of execution time for different methods on grids.
Sustainability 15 14427 g010
Figure 11. Representation of execution time for different combined methods on grids.
Figure 11. Representation of execution time for different combined methods on grids.
Sustainability 15 14427 g011
Figure 12. Representation of nodal voltage % detachment from NR results.
Figure 12. Representation of nodal voltage % detachment from NR results.
Sustainability 15 14427 g012
Figure 13. Representation of nodal voltage % detachment from nominal voltage.
Figure 13. Representation of nodal voltage % detachment from nominal voltage.
Sustainability 15 14427 g013
Figure 14. Representation nodal active power % detachment from slack bus supplied active power.
Figure 14. Representation nodal active power % detachment from slack bus supplied active power.
Sustainability 15 14427 g014
Figure 15. Representation nodal reactive power % detachment from slack bus supplied reactive power.
Figure 15. Representation nodal reactive power % detachment from slack bus supplied reactive power.
Sustainability 15 14427 g015
Figure 16. Execution time vs. grid size for different methods and detachment from nominal voltage as flat start.
Figure 16. Execution time vs. grid size for different methods and detachment from nominal voltage as flat start.
Sustainability 15 14427 g016
Table 1. Types of busbars.
Table 1. Types of busbars.
TypeKnown ValuesUnknown Parameters
Slack busV = 1.0 p.u., delta = 0°P, Q
Load bus (simple gen)Pk, QkV, delta
Gen busPk, VkQ, delta
Table 2. Sample grid values vs. iteration number at very first iteration.
Table 2. Sample grid values vs. iteration number at very first iteration.
Iteration I g I c V n 1 S c
0--220 + j0-
120,183.48 − 6055.04j215.629 − 2.15629j217.8372 − 0.625325j46,973.4 + 334.8826j
2----
3----
4----
Table 3. Sample grid complete values vs. iteration number.
Table 3. Sample grid complete values vs. iteration number.
IterationIgIcVn1ScSdYc
0--220 + j0--0 + 0j
120,183.48 − 6055.04j215.629 − 2.15629j217.8372 − 0.625325j46,973.4 + 334.8826j10.1328 + 0.101328j0.000213624 − 2.1362 × 10−6j
2------
3------
4------
Table 4. Exact solutions vs. CALF solutions.
Table 4. Exact solutions vs. CALF solutions.
Node NumberExact SolutionsCalf Solutions
Iteractions
Exec. time (ns)
Complex node voltages
ABS nodal boltages
P.U. ABS nodal voltages
Line current
Transf. current
Expected CPLX pow. @ buses
Computer CPLX pow. @ buses
Transf. CPLX power
Transf. losses
LINES LOSSES
NA
NA
[220.12516083 + 0.1245588j
215.16765754 − 0.03769608j]
[220.12519607 15.16766084]
[1.00056907 0.97803482]
32.529 + 0.0051589j
−12.8987 + 0.0310966j
[−10000. + 0.j 7000. + 0.j]
[−9999.923 − 22.6850j
6999.341 − 4.78876j]
−2837.116 + 6.9064j
1.6182 + 1.60275j
161.2653 + 5.30368j
3
997800
[220.12407684 + 0.12468541j
215.1582232 − 0.03557047j]
[220.12411215 215.15822614]
[1.00056415 0.97799194]
32.584 − 0.00972j
[−12.84928 − 0.0314343129j
[−10000. + 0.j 7000. + 0.j]
[−10000.304 − 0.27694j 7003.331 + 0.30975j]
−2836.600 + 6.77951j
1.5903798 + 1.606019j
161.809 + 5.17349243j
Table 5. Exact solutions vs. GS solutions.
Table 5. Exact solutions vs. GS solutions.
Node NumberExact SolutionsGS Solutions
Iterations
Exec. time (ns)
Complex node voltages
ABS nodal voltages
P.U. ABS nodal voltages
Line current
Transf. current
Expected CPLX pow. @ buses
Computed CPLX pow. @ buses
Transf. CPLX power
Transf. losses
Line losses
NA
NA
[220.12516083 + 0.1245588j
215.16765754 − 0.03769608j]
[220.12519607 215.16766084]
[1.00056907 0.97803482]
32.529 + 0.0051589j
−12.8987 + 0.0310966j
[−10000. + 0.j 7000. + 0.j]
[−9999.923 − 22.6850j
6999.341 − 4.78876j]
−2837.116 + 6.9064j
1.6182 + 1.60275j
161.2653 + 5.30368j
3
996700
[220.12400151 + 0.12854805j
215.1664764 − 0.03288369j]
[220.12403905 215.16647891]
[1.00056381 0.97802945]
32.529684 − 0.000238j
−13.0449 − 0.234841j
[−10,000. + 0.j 7000. + 0.j]
[−10,000. + 0.j 7000. + 0.j]
−2837.1458 + 6.95615j
1.5874 + 1.706019j
161.2667 + 5.25014j
Table 6. Exact solutions vs. NR solutions.
Table 6. Exact solutions vs. NR solutions.
Node NumberExact SolutionsNR Solutions
Iterations
Exec. time (ns)
Complex node voltages
ABS nodal voltages
P.U. ABS nodal voltages
Line current
Transf. current
Expected CPLX pow. @ buses
Computed CPLX pow. @ buses
Transf. CPLX power
Transf. losses
Line losses
NA
NA
[220.12516083 + 0.1245588j
215.16765754 − 0.03769608j]
[220.12519607 215.16766084]
[1.00056907 0.97803482]
32.529 + 0.0051589j
−12.8987 + 0.0310966j
[−10000. + 0.j 7000. + 0.j]
[−9999.923 − 22.6850j
6999.341 − 4.78876j]
−2837.116 + 6.9064j
1.6182 + 1.60275j
161.2653 + 5.30368j
2
10597000
[220.13196038 + 0.13207919j
215.28290759 + 0.02538032j]
[220.132 215.28290909]
[1.0006 0.97855868]
31.8069 − 0.33584j
−13.638407 − 0.00613718j
[−10000. + 0.j 7000. + 0.j]
[−10000. + 0.j 7000. + 0.j]
−2843.931 + 3.5674239j
1.7989 + 1.80215j
154.269 + 1.765264j
Table 7. Comparison of P.U. ABS nodal voltages for different methods.
Table 7. Comparison of P.U. ABS nodal voltages for different methods.
Node NumberExact SOL.CALFGSNR
[Node 1
Node 2] in p.u.
[1.00056907 0.97803482][1.00056415
0.97799194]
[1.0006
0.97855868]
[1.00056381
0.97802945]
Distance % from exact values
[Node 1
Node 2]
//[−0.0004917
−0.004384]
[0.0030912
0.05356]
[−0.0005257
−0.000549]
Distance % from exact value
Node means
//−0.0024380.028327−0.000537
Table 8. Execution time (ms) for different methods on different grids.
Table 8. Execution time (ms) for different methods on different grids.
Node NumberGSCALFNR
20.99670.99783.7756
199.73973910.4436919.93895
10139.5417217.952220.02764
Table 9. Execution time (ms) for different combined methods on different grids.
Table 9. Execution time (ms) for different combined methods on different grids.
Node NumberCALF and NRGS and NR
21.92451.8529
1928.83528.786
10133.572437.5614
Table 10. Nodal voltage % average detachment for different methods and grids referring to NR as the most precise method.
Table 10. Nodal voltage % average detachment for different methods and grids referring to NR as the most precise method.
Node NumberCALFGS
2101.1100482101.1100146
19100.3998917100.6123748
101101.2733728101.5968205
Table 11. Nodal voltage % average detachment for different methods and grids referring to nominal voltage.
Table 11. Nodal voltage % average detachment for different methods and grids referring to nominal voltage.
Node NumberCALFGSNR
2100.06100.0564146100.0563814
1999.8199.79562822100.0068325
10199.6976190599.6789734799.9973289
Table 12. Active power average detachment in % for different methods and grids referring to expected problem data and grid slack bus supplied active power.
Table 12. Active power average detachment in % for different methods and grids referring to expected problem data and grid slack bus supplied active power.
Node NumberSlack Active Power [kW]CALF% DetachmentGS% DetachmentNR% Detachment
2140.0016%0.0117%0.0011%
1919.60.0166%0.0534%0.0053%
1011940.0806%0.0965%0.0119%
Table 13. Reactive power average detachment in % for different methods and grids referring to expected problem data and grid slack bus supplied reactive power.
Table 13. Reactive power average detachment in % for different methods and grids referring to expected problem data and grid slack bus supplied reactive power.
Node NumberSlack Reactive Power [VAr]CALF% DetachmentGS% DetachmentNR% Detachment
238.937.0288%5.7494%0.4214%
19176.865.6012%7.7929%1.2601%
10125655.6893%4.5030%0.9791%
Table 14. Execution time vs. grid size for CALF, considering a % detachment from nominal voltage as flat start.
Table 14. Execution time vs. grid size for CALF, considering a % detachment from nominal voltage as flat start.
Node Number10% Detachment from Nominal Voltage Flat Start1%0.1%0.01%0%
20.99680.1530.51891.00360.9978
191.99632.99075.984212.98910.44368744
10120.6448433.802615.957421.29417.95220375
Table 15. Execution time vs. grid size for GS, considering a % detachment from nominal voltage as flat start.
Table 15. Execution time vs. grid size for GS, considering a % detachment from nominal voltage as flat start.
Node Number10% Detachment from Nominal Voltage Flat Start1%0.1%0.01%0%
20.99291.00370.99771.00050.9967
190.99783.99021.993510.979.739739275
10153.962870.971763.962245.955839.54172134
Table 16. Execution time vs. grid size for NR, considering a % detachment from nominal voltage as flat start.
Table 16. Execution time vs. grid size for NR, considering a % detachment from nominal voltage as flat start.
Node Number10% Detachment from Nominal Voltage Flat Start1%0.1%0.01%0%
21.99540.99761.98472.9873.7756
1931.912450.865740.888521.879519.93894577
10192.25319108.4111465.3251932.6295720.02763748
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Risi, B.-G.; Riganti-Fulginei, F.; Laudani, A.; Quercio, M. Compensation Admittance Load Flow: A Computational Tool for the Sustainability of the Electrical Grid. Sustainability 2023, 15, 14427. https://doi.org/10.3390/su151914427

AMA Style

Risi B-G, Riganti-Fulginei F, Laudani A, Quercio M. Compensation Admittance Load Flow: A Computational Tool for the Sustainability of the Electrical Grid. Sustainability. 2023; 15(19):14427. https://doi.org/10.3390/su151914427

Chicago/Turabian Style

Risi, Benedetto-Giuseppe, Francesco Riganti-Fulginei, Antonino Laudani, and Michele Quercio. 2023. "Compensation Admittance Load Flow: A Computational Tool for the Sustainability of the Electrical Grid" Sustainability 15, no. 19: 14427. https://doi.org/10.3390/su151914427

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop