Buildings 2014, 4(3), 437-452; doi:10.3390/buildings4030437
Abstract
: In order to clarify the comfort temperature and to investigate the behavioral adaptation in Japanese houses, we have conducted a thermal comfort survey and occupant behavior survey in 30 living rooms during the hot and humid season in the Kanto region of Japan. We collected 3991 votes from 52 subjects. The comfort temperature was predicted by Griffiths’ method. They are analyzed according to humidity levels and compared with the adaptive model. The logistic regression analysis was conducted in order to understand occupant behavior. The mean comfort temperature in naturally ventilated mode is 27.6 °C which is within the acceptable zone of the adaptive model. The comfort temperature is related with skin moisture sensation. The results showed that the residents adapt to the hot and humid environments by increasing the air movement using behavioral adaptation such as window opening and fan use.1. Introduction
The basic survival needs for human beings are food, clothing and housing. People tend to choose the most comfortable and favorable of these items available during their life. People also want to buy and live in a comfortable home, which normally represents their most significant expenditure in their lifetime. Thus, it is highly important to build a comfortable home to fulfill this desire of the average person.
It is thought that thermal comfort is one of the most important factors in creating the most comfortable homes. By investigating and establishing the comfort temperature of the residents, this can be used as the customary temperature of the house to minimize excessive energy use and save the overall energy costs of the household. There have already been a number of research projects about the comfort temperature of houses in Japan [1,2,3,4,5], Nepal [6], Pakistan [7,8] and UK [9]. The Japanese summer is especially hot and humid, and the Japanese government recommends the indoor temperature setting of 28 °C without supporting evidence from any field survey. Thus, we need to investigate the comfort temperatures and effect of humidity on the environments and occupants concerned.
Recently, ASHRAE [10] and CEN [11] have proposed the adaptive model for naturally ventilated and free running building design. The adaptive models are based on a thermal comfort survey, mainly in the European and American offices, and Japanese data is not included in them. The occupants’ behavior in the office and at home is different, and thus the exiting adaptive models may not be applicable to residences which need to be compared using the Japanese data.
In hot and humid conditions, air movement is the important factor in determining the indoor comfort temperature [12]. Behavioral adaptation such as window opening and fan use might be useful to increase the air movement for adaptive thermal comfort. However, how people behaviorally adapt to the hot and humid season is not yet fully understood.
In order to clarify the comfort temperature and investigate the behavioral adaptation in Japanese houses, we have conducted our thermal comfort survey and occupant behavior survey in 30 living rooms during the hot and humid season in the Kanto region of Japan.
2. Field Investigation
The indoor air temperature, the globe temperature and the relative humidity were measured in the living room, avoiding direct sunlight, at ten minute intervals using a data logger (Figure 1, Table 1). Outdoor air temperature and relative humidity were obtained from the nearest meteorological station. The number of subjects comprised 25 males and 27 females. The thermal comfort survey was conducted from 25 July to 17 September 2012 (hot and humid season) several times a day using a 7 point thermal sensation scale and a 5 point thermal preference scale (Figure 2). Occupant behavior in the living room was recorded in binary form several times a day (0 = window closed or cooling off or fan off, 1 = window open or cooling on or fan on). We collected 3991 votes. These data were analyzed by the SPSS version 19.

Parameter Measured | Trade Name | Range | Accuracy |
---|---|---|---|
Air temperature, Humidity | TR-74Ui | 0 to 55 °C, 10 to 95%RH | ±0.5 °C, ±5% |
RTR-53A | 0 to 55 °C, 10 to 95%RH | ±0.3 °C, ±5% | |
Globe temperature | Tr-52i | −60 to 155 °C | ±0.3 °C |
SIBATA 080340-75 | Black painted 75 mm diameter globe |

Even though the ASHRAE scale is frequently used to evaluate the thermal sensation, the words “warm” or “cool” imply comfort in Japanese, and thus the SHASE (The Society of Heating, Air-Conditioning and Sanitary Engineers of Japan) scale is also used to evaluate the thermal sensation. To avoid the possible misunderstanding of “neutral” in the thermal sensation scale, it is explained as “neutral (neither cold nor hot)” (SHASE scale) or “neutral (neither cool nor warm)” (ASHRAE scale). It is also said that the optimum temperature occurs on the cooler side in summer and on the warmer side in winter [1,13].
3. Results and Discussion
3.1. The Modes
The data were divided into two groups: the NV mode (naturally ventilated) and AC mode (cooling by air conditioning). First, we have determined the AC mode based on actual cooling used. Then, all the other data were classified as being in the NV mode. So, strictly speaking, the NV mode is the “free running” mode where the cooling is not being used to control the indoor environment [14].
3.2. Distribution of Temperature and Humidity
Figure 3 shows the monthly mean temperature and relative humidity in NV and AC modes. Table 2 shows the correlation coefficient in NV and AC modes.
The monthly mean indoor and globe temperature is very similar in NV and AC mode, and thus the correlation coefficient is also high in both modes. In NV mode, indoor temperatures are higher than the outdoor air temperature. However, in AC mode, the indoor temperatures are lower than the outdoor air temperature, except in September. The Japanese government recommends the indoor temperature settings of 28 °C in summer. The results showed that the mean indoor temperature setting in AC mode was similar to the recommendation.
The mean indoor relative humidity is lower than the outdoor relative humidity (Figure 3b). Due to the mechanical cooling, the mean indoor relative humidity or correlation coefficient of the AC mode is lower than the NV mode. The results showed that the relative humidity is slightly higher than the standard: 60%.

Mode | Items | Ti:To | Tg:To | Ti:Tg | RHi:RHo |
---|---|---|---|---|---|
NV | r | 0.57 | 0.57 | 0.98 | 0.50 |
N | 1860 | 1915 | 1860 | 1860 | |
AC | r | 0.22 | 0.20 | 0.89 | 0.07 |
N | 1805 | 2076 | 1805 | 1805 |
Ti: Indoor air temperature (°C); Tg: Indoor globe temperature (°C); To: Outdoor air temperature (°C); RHi: Indoor relative humidity (%); RHo: Outdoor relative humidity (%); r: Correlation coefficient; N: Number of sample; Correlation coefficient is significant at the 0.01 level (2-tailed).
3.3. Distribution of Thermal Sensation
Table 3 shows the correlation coefficient of the thermal sensation and thermal preference or temperatures. The correlation coefficient of the SHASE scale and thermal preference is higher than the ASHRAE scale and thermal preference. The SHASE scale is better correlated with the indoor air temperature and globe temperature. Thus, we have used the SHASE scale for further analysis.
Mean thermal sensation vote was 4.7 in NV mode, 4.3 in AC mode. Even though residents used the cooling, they sometimes felt “hot”. The proportion of people voting in the thermal comfort zone (votes 3, 4 or 5) in the NV and AC modes is 84% and 97% (Table 4).
It can be said that residents were generally satisfied in the thermal environment of their houses. This may be due to the thermal adaptation of the residents to the local climate and culture.
Mode | Items | ASHRAE | SHASE | ||||
---|---|---|---|---|---|---|---|
TP | Ti | Tg | TP | Ti | Tg | ||
NV | r | 0.73 | 0.36 | 0.36 | 0.81 | 0.38 | 0.37 |
N | 1,915 | 1860 | 1915 | 1915 | 1860 | 1915 | |
AC | r | 0.77 | 0.30 | 0.28 | 0.86 | 0.35 | 0.32 |
N | 2076 | 1805 | 2076 | 2076 | 1805 | 2076 |
TP: Thermal preference; Ti: Indoor air temperature (°C); Tg: Globe temperature (°C); p < 0.001; p: Significant level; r: Correlation coefficient; N: Number of sample.
Mode | Items | Thermal Sensation | Total | ||||||
---|---|---|---|---|---|---|---|---|---|
1 | 2 | 3 | 4 | 5 | 6 | 7 | |||
NV | N | 1 | – | 24 | 904 | 685 | 253 | 48 | 1915 |
P (%) | 0.1 | – | 1.3 | 47.2 | 35.8 | 13.2 | 2.5 | 100 | |
AC | N | 2 | 5 | 152 | 1284 | 569 | 58 | 6 | 2076 |
P (%) | 0.1 | 0.2 | 7.3 | 61.8 | 27.4 | 2.8 | 0.3 | 100 |
N: Number of sample; P: Percentage.
3.4. Thermal Comfort Zone
To clarify the thermal comfort zone, the Probit regression analysis [15] is conducted for the thermal sensation votes (TSV) (SHASE scale) categories and temperatures for NV and AC modes. The analysis method is Ordinal regression using Probit as the link function and the temperature as the covariate.
The results of the Probit analysis is shown in Table 5. The “mean” temperature is calculated by dividing the constant by regression coefficient. For example, the mean temperature of the first equation will be 4.790/0.289 = 16.6 °C (Table 5). The inverse of the Probit regression is the standard deviation of the cumulative Normal distribution. For example, the standard deviation of air temperature of the NV mode will be 1/0.289 = 3.460 °C (Table 5). These calculations are fully given in the Table 5. Transforming the Probits using the following function into proportions gives the curve of Figure 4a–d. The vertical axis is the proportion of votes.
The highest line is for category 1 (very cold) and so on successively. Thus, it can be seen that the temperature for thermal neutrality (a probability of 0.5) is around 26 °C for the AC mode.
Reckoning the three central categories as representing thermal comfort, and transforming the Probits into proportions gives the bell-curve of Figure 4e,f. The result is remarkable in two respects. The proportion of people comfortable at the optimum is very high for AC mode, only just less that 100%, and the range over which 80% are comfortable is wide—from around 23 to 30 °C in NV mode. This is presumably because people in their own homes are free to clothe themselves according to the room temperature, without the constraints that are apt to apply at the office.
Mode | Indoor air temperature Ti (°C) | Globe temperature Tg (°C) | ||||
---|---|---|---|---|---|---|
Equation | Mean | S.D. | Equation | Mean | S.D. | |
NV | P(≤1) = 0.289Ti − 4.790 | 16.6 | 3.460 | P(≤1) = 0.285Tg − 4.691 | 16.5 | 3.509 |
P(≤2) = 0.289Ti − 5.919 | 20.5 | P(≤2) = 0.285Tg − 5.817 | 20.4 | |||
P(≤4) = 0.289Ti − 8.292 | 28.7 | P(≤4) = 0.285Tg − 8.238 | 28.9 | |||
P(≤5) = 0.289Ti − 9.461 | 32.7 | P(≤5) = 0.285Tg − 9.388 | 32.9 | |||
P(≤6) = 0.289Ti − 10.506 | 36.4 | P(≤6) = 0.285Tg − 10.424 | 36.6 | |||
AC | P(≤1) = 0.260Ti − 3.861 | 14.9 | 3.846 | P(≤1) = 0.250Tg − 3.701 | 14.8 | 3.846 |
P(≤2) = 0.260Ti − 4.150 | 16.0 | P(≤2) = 0.250Tg − 4.085 | 16.3 | |||
P(≤3) = 0.260Ti − 5.655 | 21.8 | P(≤3) = 0.250Tg − 5.410 | 21.6 | |||
P(≤4) = 0.260Ti − 8.043 | 30.9 | P(≤4) = 0.250Tg − 7.506 | 30.0 | |||
P(≤5) = 0.260Ti − 9.210 | 35.4 | P(≤5) = 0.250Tg − 8.953 | 35.8 | |||
P(≤6) = 0.260Ti − 10.118 | 38.9 | P(≤6) = 0.250Tg − 9.912 | 39.6 |
P(≤1) is the Probit of proportion of the votes that are 1 and less, P(≤2) is the Probit of the proportion that are 2 and less, and so on, S.D.: Standard deviation of the cumulative Normal distribution.

3.5. Prediction of Comfort Temperature by Regression Method
Regression analysis of the thermal sensation and indoor air temperature was conducted to predict the comfort temperature (Figure 5). The following regression equations are obtained for the thermal sensation (C) and indoor air temperature (Ti, °C) or globe temperature (Tg, °C).
NV mode:
AC mode:
The regression coefficient for the NV mode is higher than that of the AC. When the indoor or globe comfort temperature is predicted by substituting “4 neutral” in the Equations (2) to (5), it would be 25.4 °C in the NV mode and 26.4 °C or 25.9 °C in the AC mode.
As shown in the figure, the comfort temperature is predicted around the few data points, and thus a linear model is not suitable to predict the comfort temperature. This might be due to the problem of applying the regression method in the presence of adaptive behavior, where it can be misleading when used to estimate the comfort temperature, as has been found in previous research [5,6]. So to avoid this problem the comfort temperature is estimated using the Griffiths method in the next section.

3.6. Prediction of Comfort Temperature by Griffiths Method
Griffiths [16] suggested a way in which the comfort temperature can be calculated from a small sample of data. Griffiths made the assumption that the increase in temperature for each scale point on the thermal sensation scale was effectively 3K for a seven point scale [17]. This means that for each thermal sensation vote away from neutral, he subtracted or added 3K from the actual temperature at the time to obtain the temperature that might be expected to result in neutrality [17]. The detail of the Griffiths method can be found in the various publications [7,17,18]. The comfort temperature is predicted by the Griffiths’ method which is given below.
In applying the Griffiths’ method, Nicol et al. [7] and Humphreys et al. [19] used the constants 0.25, 0.33 and 0.50 for a 7 point thermal sensation scale. We have also investigated the comfort temperature using these regression coefficients. The mean comfort temperature with each coefficient is not very different (Table 6), so it matters little which coefficient is adopted. The comfort temperature calculated with the coefficient 0.50 is used for further analysis.
Mode | RC | Tci (°C) | Tcg (°C) | ||||
---|---|---|---|---|---|---|---|
N | Mean | S.D. | N | Mean | S.D. | ||
NV | 0.25 | 1860 | 26.2 | 3.1 | 1915 | 26.3 | 3.0 |
0.33 | 1860 | 26.9 | 2.4 | 1915 | 26.9 | 2.4 | |
0.50 | 1860 | 27.6 | 1.8 | 1915 | 27.6 | 1.8 | |
AC | 0.25 | 1805 | 26.9 | 2.5 | 2076 | 26.8 | 2.6 |
0.33 | 1805 | 27.1 | 2.1 | 2076 | 27.0 | 2.1 | |
0.50 | 1805 | 27.3 | 1.8 | 2076 | 27.3 | 1.7 |
RC: Regression coefficient; Tci: Comfort indoor temperature; Tcg: Comfort globe temperature; N: Number of sample; S.D.: Standard deviation.
The mean comfort air or globe temperature by the Griffiths’ method is 27.6 °C in NV mode and 27.3 °C in AC mode (Figure 6). Since the mean comfort temperature of the Griffiths’ method is comparable to the indoor air and globe temperature when voting “4 neutral” (Table 7). It is probable that the comfort temperature as estimated by the Griffiths’ method is more appropriate.
Table 8 shows a comparison of the comfort temperature obtained in this study with existing research. The comfort temperature of the existing research is similar to this research.

Mode | Items | N | Mean (°C) | S.D. (°C) |
---|---|---|---|---|
NV | Ti | 851 | 28.5 | 1.5 |
Tg | 904 | 28.5 | 1.5 | |
AC | Ti | 1264 | 27.4 | 1.7 |
Tg | 1284 | 27.6 | 1.6 |
Ti: Indoor air temperature; Tg: Indoor globe temperature; S.D.: Standard deviation.
Area | Reference | Comfort Temperature (°C) |
---|---|---|
Japan (Kanto) | This study (NV mode) | 27.6 |
Japan (Gifu) | Rijal et al. [5] | 26.1 |
Japan (Kanto) | Katsuno et al. [4] | 27.6 |
Japan (Kanto) | Yoshimura et al. [2] | 29 |
Japan (Kanto) | Rijal and Yoshimura [3] | 27.2 * |
Japan (Kansai) | Nakaya et al. [1] | 27.6 |
Nepal | Rijal et al. [6] | 21.1–30.0 |
Pakistan | Nicol and Roaf [8] | 26.7–29.9 |
UK | Rijal and Stevenson [9] | 22.9 |
*: Summer and autumn.
3.7. Comfort Temperature and Humidity
The humidity is one of the key issues in the hottest season. In a moist environment, people become uncomfortable with a smaller change in temperature than they do in a dry environment [12]. The comfort temperature is analyzed by relating it to the relative humidity, absolute humidity and skin moisture. The comfort temperatures were correlated with the indoor relative humidity and skin moisture sensation (Table 9). However, the correlation effect of the comfort temperature and relative humidity might have simply been arrived at from the correlation between air temperature and relative humidity. To investigate the effect of humidity on the comfort temperature, the multiple regression analysis was conducted for the NV mode.
As shown in the equations, the relative humidity and absolute humidity have no important effect on the comfort temperature. However, Nicol [12] found that in a humid climate or in conditions when the relative humidity is high people may require temperatures that are about 1°C lower to remain comfortable. As for the skin moisture, it has significantly affected the comfort temperature (Figure 7). Nicol [20] found that when indoor air temperature is 31–40 °C, the increased wind velocity reduced the skin moisture.
The results showed that the evaporation of the skin moisture is important to increase the comfort temperature in Japan’s hot and humid season.
Items | Tci:RHi | Tcg:RHi | Tci:AHi | Tcg:AHi | Tci:SM | Tcg:SM |
---|---|---|---|---|---|---|
r | −0.37 | −0.34 | −0.03 | −0.01 | −0.35 | −0.34 |
p | <0.001 | <0.001 | 0.135 | 0.784 | <0.001 | <0.001 |
N | 1860 | 1860 | 1860 | 1860 | 1860 | 1915 |
r: Correlation coefficient; p: Significant level; N: Number of sample; Tci: Comfort indoor temperature (°C); Tcg: Comfort globe temperature (°C); RHi: Indoor relative humidity (%); AHi: Indoor absolute humidity (g/kg’); SM: Skin moisture sensation.

3.8. A Comparison with the Adaptive Model
It is well known that people adapt to the outdoor temperature, and thus comfort temperature has seasonal and regional differences [14]. To predict such comfort temperature, the CEN and CIBSE proposed the adaptive model for office buildings. We wished to compare our results with these adaptive models.
The running mean outdoor temperature (Trm) is used in the adaptive model which is the exponentially weighted daily mean outdoor temperature. It is calculated using the following equation [11,17,21,22].
Figure 8 shows the relation between the comfort temperature and the running mean outdoor temperature. The six parallel lines in Figure 8a show the acceptable zone of the adaptive model of CEN standard [11]. The two parallel lines in Figure 8b show upper and lower margins of the comfort temperature [22]. The Japanese guide line is also shown in the figure.
Generally the comfort temperature of NV mode is within the acceptable zone of the adaptive model. As for the AC mode, the comfort temperature is higher than the CIBSE guide [22]. The results showed that the residents are living by adapting to the higher indoor air temperature of the houses.

3.9. Occupant Behavior
As we have shown in the previous sections, the residents questioned are living by adapting to higher indoor air temperature of the houses. Residents might be regulating the thermal environments by using various adaptations: behavioral, physiological and psychological [23]. This section focuses on the behavioral adaptation. Nicol and Humphreys [24] made use of logistic regression analysis to predict occupant control behavior in naturally ventilated buildings. We have also adopted the logistic regression method to predict the window opening and fan use in the living room. The relationship between the probability of windows open or fan use (p) and the indoor or outdoor temperature (T) is of the form:
The following regression equations were obtained in between the window opening or fan use and temperatures for NV mode.
Window opening:
Fan use:
These equations are shown in Figure 9. The predicted window opening or fan use is well matched with the measured values. The proportion of window opening or fan use is increased when temperature rises. The window opening behavior is similar to the previous research [5,18].
The regression coefficient for indoor air temperature or globe temperature is higher than the outdoor air temperature. It seems that the occupants respond more closely to the indoor temperatures than outdoor air temperature while operating the windows and fans.
Window opening and fan use might be important to increase the air movement and lower the indoor air temperature. Window opening is effective at increasing the indoor comfort temperature [5,25]. Theoretically, if wind velocity is 1 m/s, the indoor comfort temperature can be increased by some 3 or 4 °C [12,26,27]. Nicol [12] found that the presence of air movement can be equivalent to a reduction in indoor temperature of as much as 4 °C. When outdoor running mean temperature is 30 °C, the indoor comfort temperature when the fan is on is 31 °C which is 2.2 °C higher than when the fan is off [18,27].
Thus, the results showed that residents undertake behavioral adaptation to regulate their hot and humid thermal environment.

4. Conclusions
In order to clarify the comfort temperature and to investigate the behavioral adaptation in Japanese houses, we conducted a thermal comfort survey and occupant behavior survey in 30 living rooms for the hot and humid season in the Kanto region of Japan. Following are the results:
- (1)
The proportion of people voting in the thermal comfort zone is 84% in NV mode, and thus the residents are highly adapted and satisfied with the thermal environment of their houses.
- (2)
The mean comfort temperature in naturally ventilated mode is 27.6 °C (standard deviation = 1.8 °C) in hot and humid season. The results showed that the comfort temperature of this study is within the acceptable zone of the adaptive model.
- (3)
The comfort temperature is related with skin moisture sensation, and thus the evaporation of the skin moisture is important to increase the comfort temperature in hot and humid season.
- (4)
The residents adapt to hot and humid environments by increasing the air movement usage through the behavioral adaptive actions such as opening the windows and using fans.
Acknowledgments
This research was supported by Grant-in-Aid for Scientific Research (C) Number 24560726 and (B) Number 25289200. I would like to thank to Madhavi Indraganti for reviewing the paper. I would like to give especial thanks to Michael Humphreys and Fergus Nicol of Oxford Brookes University for their research guidance.
Conflicts of Interest
The author declares no conflict of interest.
References
- Nakaya, T.; Matsubara, N.; Kurazumi, Y. A field study of thermal environment and thermal comfort in Kansai region, Japan: Neutral temperature and acceptable range in summer. J. Environ. Eng. AIJ 2005, 597, 51–56. [Google Scholar]
- Yoshimura, S.; Rijal, H.B.; Kikuchi, S. Research on the comfort temperature and the adaptive model of houses. AIJ Kanto Chapter Archit. Res. Meet. 2012, 82, 113–116. [Google Scholar]
- Rijal, H.B.; Yoshimura, S. Investigation of Comfort Temperature in Naturally Ventilated and Air Condition Mode in Japanese Houses. In Proceedings of the 4th International Conference on Human-Environment System, Sapporo, Japan, 3–6 October 2011; pp. 259–264.
- Katsuno, J.; Rijal, H.B.; Kikuchi, S. Investigation of the Comfort Temperature and Adaptive Model in Japanese Houses in Summer. In Proceedings of 7th Conference: The Changing Context of Comfort in an Unpredictable World, Windsor, UK, 12–15 April 2012.
- Rijal, H.B.; Honjo, M.; Kobayashi, R.; Nakaya, T. Investigation of comfort temperature, adaptive model and the window opening behaviour in Japanese houses. Archit. Sci. Rev. 2013, 56, 54–69. [Google Scholar] [CrossRef]
- Rijal, H.B.; Yoshida, H.; Umemiya, N. Seasonal and regional differences in neutral temperatures in Nepalese traditional vernacular houses. Build. Environ. 2010, 45, 2743–2753. [Google Scholar]
- Nicol, F.; Jamy, G.N.; Sykes, O.; Humphreys, M.; Roaf, S.; Hancock, M. A Survey of Thermal Comfort in Pakistan toward New Indoor Temperature Standards; Oxford Brookes University: Oxford, UK, 1994. [Google Scholar]
- Nicol, F.; Roaf, S. Pioneering new indoor temperature standards: The Pakistan project. Energy Build. 1996, 23, 169–174. [Google Scholar] [CrossRef]
- Rijal, H.B.; Stevenson, F. Thermal Comfort in UK Housing to Avoid Overheating: Lessons from a “Zero Carbon” Case Study. In Proceedings of the Conference: Adapting to change: New thinking on comfort, Windsor, UK, 9–11 April 2010.
- AHRAE Standard 55. Thermal Environment Conditions for Human Occupancy; American Society of Heating Refrigeration and Air-Conditioning Engineers: Atlanta, GA, USA, 2004. [Google Scholar]
- Comité Européen de Normalisation (CEN). Indoor Environmental Input Parameters for Design and Assessment of Energy Performance of Buildings Addressing Indoor Air Quality, Thermal Environment, Lighting and Acoustics; EN 15251; CEN: Brussels, Belgium, 2007. [Google Scholar]
- Nicol, F. Adaptive thermal comfort standards in the hot-humid tropics. Energy Build. 2004, 36, 628–637. [Google Scholar] [CrossRef]
- McIntyre, D.A. Indoor Climate; Applied Science Publishers, Ltd.: London, UK, 1980. [Google Scholar]
- Humphreys, M.A. Outdoor temperatures and comfort indoors. Build. Res. Pract. 1978, 6, 92–105. [Google Scholar]
- Finney, D.J. Probit Analysis; Cambridge University Press: Cambridge, UK, 1971. [Google Scholar]
- Griffiths, I.D. Thermal Comfort in Buildings with Passive Solar Features: Field Studies; Report to the Commission of the European Communities; EN3S-090 UK; University of Surrey Guildford: Surrey, UK, 1990. [Google Scholar]
- Nicol, F.; Humphreys, M.; Roaf, S. Adaptive Thermal Comfort: Principles and Practice; Earthscan: London, UK, 2012. [Google Scholar]
- Rijal, H.B.; Tuohy, P.; Humphreys, M.A.; Nicol, J.F.; Samuel, A.; Raja, I.A.; Clarke, J. Development of adaptive algorithms for the operation of windows, fans and doors to predict thermal comfort and energy use in Pakistani buildings. ASHRAE Trans. 2008, 114, 555–573. [Google Scholar]
- Humphreys, M.A.; Rijal, H.B.; Nicol, J.F. Updating the adaptive relation between climate and comfort indoors; new insights and an extended database. Build. Environ. 2013, 63, 40–55. [Google Scholar] [CrossRef]
- Nicol, J.F. An analysis of some observations of thermal comfort in Roorkee, India and Baghdad, Iraq. Ann. Human Biol. 1974, 1, 411–426. [Google Scholar] [CrossRef]
- McCartney, K.J.; Nicol, J.F. Developing an adaptive control algorithm for Europe, Energy and Buildings. Energy Build. 2002, 34, 623–635. [Google Scholar] [CrossRef]
- Humphreys, M.A.; Nicol, J.F. Chapter 1, Environmental Criteria for Design. In Environmental Design: CIBSE Guide A; CIBSE: London, UK, 2006. [Google Scholar]
- Brager, G.; de Dear, R. Thermal adaptation in the built environment: A literature review. Energy Build. 1998, 27, 83–96. [Google Scholar] [CrossRef]
- Nicol, J.F.; Humphreys, M.A. A stochastic approach to thermal comfort—Occupant behavior and energy use in buildings. ASHRAE Trans. 2004, 110, 554–568. [Google Scholar]
- Brager, G.S.; Paliaga, G.; de Dear, R. Operable windows, personal control, and occupant comfort. ASHRAE Transac. 2004, 110, 17–33. [Google Scholar]
- Humphreys, M.A. A simple theoretical derivation of thermal comfort conditions. J. Instit. Heat. Vent. Eng. 1970, 38, 95–98. [Google Scholar]
- Rijal, H.B. Chapter 3: Thermal Adaptation Outdoors and the Effect of Wind on Thermal Comfort. In Ventilating Cities Air-flow—Criteria for Healthy and Comfortable Urban Living; Kato, S., Hiyama, K., Eds.; Springer: London, UK, 2012; pp. 33–58. [Google Scholar]
© 2014 by the authors; licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution license (http://creativecommons.org/licenses/by/3.0/).