Energies 2014, 7(3), 1685-1705; doi:10.3390/en7031685
Article

Evaluation of Visitor Counting Technologies and Their Energy Saving Potential through Demand-Controlled Ventilation

* ,
 and
Received: 8 February 2014; in revised form: 18 March 2014 / Accepted: 19 March 2014 / Published: 21 March 2014
(This article belongs to the Special Issue Energy Efficient Building Design and Operation 2014)
View Full-Text   |   Download PDF [964 KB, uploaded 21 March 2014]
Abstract: Direction-sensitive visitor counting sensors can be used in demand-controlled ventilation (DCV). The counting performance of two light beam sensors and three camera sensors, all direction sensitive, was simultaneously evaluated at an indoor location. Direction insensitive sensors (two mat sensors and one light beam sensor) were additionally tested as a reference. Bidirectional counting data of free people flow was collected for 36 days in one-hour resolution, including five hours of manual counting. Compared to the manual results, one of the light beam sensors had the most equally balanced directional overall counting errors (4.6% and 5.2%). The collected data of this sensor was used to model the air transportation energy consumption of visitor counting sensor-based DCV and constant air volume ventilation (CAV). The results suggest that potential savings in air transportation energy consumption could be gained with the modeled DCV as its total daily airflow during the test period was 54% of the total daily airflow of the modeled CAV on average. A virtually real-time control of ventilation could be realized with minute-level counting resolution. Site-specific calibration of the visitor counting sensors is advisable and they could be complemented with presence detectors to avoid unnecessary ventilation during unoccupied periods of the room. A combination of CO2 and visitor counting sensors could be exploited in DCV to always guarantee sufficient ventilation with a short response time.
Keywords: visitor counting sensor; people flow rate; indoor people flow monitoring; zone population detection; demand-controlled ventilation visitor counting sensor; people flow rate; indoor people flow monitoring; zone population detection; demand-controlled ventilation
This is an open access article distributed under the Creative Commons Attribution License which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.

Export to BibTeX |
EndNote


MDPI and ACS Style

Kuutti, J.; Blomqvist, K.H.; Sepponen, R.E. Evaluation of Visitor Counting Technologies and Their Energy Saving Potential through Demand-Controlled Ventilation. Energies 2014, 7, 1685-1705.

AMA Style

Kuutti J, Blomqvist KH, Sepponen RE. Evaluation of Visitor Counting Technologies and Their Energy Saving Potential through Demand-Controlled Ventilation. Energies. 2014; 7(3):1685-1705.

Chicago/Turabian Style

Kuutti, Jussi; Blomqvist, Kim H.; Sepponen, Raimo E. 2014. "Evaluation of Visitor Counting Technologies and Their Energy Saving Potential through Demand-Controlled Ventilation." Energies 7, no. 3: 1685-1705.


Energies EISSN 1996-1073 Published by MDPI AG, Basel, Switzerland RSS E-Mail Table of Contents Alert