- freely available
- re-usable
Energies 2012, 5(11), 4643-4664; doi:10.3390/en5114643
Article
Development of a Terminal Control System with Variable Minimum Airflow Rate
School of Architecture, Kumoh National Institute of Technology, Gumi, Gyeongbuk 730-701, Korea
Received: 12 June 2012; in revised form: 9 October 2012 / Accepted: 13 November 2012 / Published: 15 November 2012
(This article belongs to the Special Issue Energy Efficient Buildings and Green Buildings)
Abstract: A constant minimum airflow rate is used in conventional Single Duct Variable Air Volume Terminal Box control sequences. This control sequence can cause occupant discomfort or use excessive energy under partial load conditions. If the minimum airflow rate is higher than required; terminal boxes will have significantly more simultaneous heating and cooling; and AHUs will consume more fan power. Buildings will have indoor air quality problems if the minimum airflow rate is less than required. Many engineers and researchers have investigated advanced variable air volume terminal box control algorithms without a system retrofit for thermal comfort; indoor air quality and energy savings. In this study a developed control system with variable minimum airflow rate for Single Duct Variable Air Volume Terminal Boxes was applied and validated using an actual building and evaluated for comfort; indoor air quality and energy consumption. The energy consumption and thermal performance of terminal boxes using the conventional and proposed control algorithms were compared.
Keywords: terminal control system; variable minimum airflow rate; energy consumption; thermal performance; control algorithms
Article Statistics
Click here to load and display the download statistics.Cite This Article
MDPI and ACS Style
Cho, Y.-H. Development of a Terminal Control System with Variable Minimum Airflow Rate. Energies 2012, 5, 4643-4664.
AMA StyleCho Y-H. Development of a Terminal Control System with Variable Minimum Airflow Rate. Energies. 2012; 5(11):4643-4664.
Chicago/Turabian StyleCho, Young-Hum. 2012. "Development of a Terminal Control System with Variable Minimum Airflow Rate." Energies 5, no. 11: 4643-4664.
Energies
EISSN 1996-1073
Published by MDPI AG, Basel, Switzerland
RSS
E-Mail Table of Contents Alert
