Article

Minimum-Information-Entropy-Based Control Performance Assessment

State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Beijing, 102206, China
*
Author to whom correspondence should be addressed.
Entropy 2013, 15(3), 943-959; https://doi.org/10.3390/e15030943
Submission received: 2 December 2012 / Revised: 21 January 2013 / Accepted: 22 February 2013 / Published: 27 February 2013

Abstract

:
Generally, the controller design should be performed to narrow the shape of the probability density function of the tracking error. A small information entropy value corresponds to a narrow distribution function, which means that the uncertainty of the related random variable is small. In this paper, information entropy is introduced in the field of control performance assessment (CPA). For the unknown time delay case, the minimum information entropy (MIE) benchmark is presented, and a MIE-based performance index is defined. For the known time delay case, a tight upper bound of MIE is derived and adopted as a performance benchmark to assess the stochastic control performance. Based on these, the control performance assessment procedures are developed for both the steady and the transient processes. Simulation tests and an industrial case study of a main steam pressure system of a 1,000MW power unit are utilized to verify the effectiveness of the proposed procedures.

1. Introduction

The performance of the control system has a direct impact on the security and the economy of an industrial process. However, about 66%–80% of the control systems cannot achieve the desired performance [1]. Therefore, control performance assessment (CPA) is an urgent problem, and the relevant surveys will have wide application prospects.
There are two research branches of CPA: the model-based CPA and the data-driven-based CPA. For the former branch: the Harris index was proposed first [2]. It was used in the SISO system first, and then was extended to the MIMO system [3]. Based on this index, the cascade system [4], the non-phase system [5], the traditional PID control system [6] and the predictive control system [7], etc., can be assessed accordingly. In addition, many other indexes were proposed based on variance, such as the Relative Variance Index [8], the General Minimum Variance [9]. For the latter branch Desborough and Harris [10] studied the data-based monitoring for SISO systems. McNabb and Qin [11] developed a covariance-based MIMO control monitoring method. Yu and Qin [12,13] extended data-driven covariance benchmark to performance diagnosis.
Because the data-driven-based CPA does not require much process knowledge, it is easy to apply in practice. Furthermore, the information collection and management systems are general equipment in modern industrial production processes, so a vast amount of real operation data can be obtained. Applying these data to achieve CPA is both feasible and meaningful.
For the data-driven-based CPA methods, the choice of the statistic index is an essential issue. Generally, the control system performance can be represented by the tracking error. Ideally, the controller design should be performed so that the shape of the probability density function (PDF) of the tracking error is as narrow as possible. This is simply because a narrow distribution function generally indicates that the uncertainty of the related random variable is small, which also corresponds to a small entropy value [14]. In this case, entropy, an important statistic, has natural advantages for characterizing the control stochastic performance. Unfortunately, entropy has not been used in CPA.
The purpose of this paper is to propose an information-entropy-based CPA method with its advantage of generalized random performance description, and focuses on the selection of the Minimum- Information-Entropy (MIE) benchmark and the design of minimum information entropy index. The rest parts of this paper are organized as follows: Section 2 presents the minimum information entropy benchmark. Section 3 introduces a normalized minimum entropy index. Section 4 describes a procedure for performance assessment using the MIE index for both steady and transient states. Simulation comparisons are presented in Section 5, and a CPA test for a main steam pressure control system of a 1,000MW power plant is shown in Section 6. The conclusions are given in Section 7.

2. Minimum-Information-Entropy Benchmark

2.1. Information Entropy

The information entropy is a measure of the uncertainty associated with a random variable. It can characterize the control stochastic performance. Usually, the information entropy refers to the Shannon entropy, which is a unified probabilistic measure of the uncertainty quantification [15]. For a random variable x , the continuous-type entropy (or the differential entropy) H is defined as:
H = γ ( x ) ln γ ( x ) d x
where γ ( x ) is the PDF of x .

2.2. MIE Benchmark

Suppose a linear Gaussian process with time delay d is:
y k = i = 1 n α i y k i + j = 0 m b j u k d j + ω k
where y k is the process output, u k is the control variable, α i and b j are the coefficients, the independent and identically distributed (i.i.d.) stochastic disturbance ω k ; obeys Gaussian distribution N(μ, δ2) with variance δ 2 and mean μ , and its PDF is:
γ ω ( x ) = 1 2 π δ exp ( ( x μ ) 2 2 δ 2 )
The MIE benchmark is deduced with the MIE optimal control in accordance with the following steps:
Step 1: Obtain the recursive control law u k with the MIE optimal control.
The tracking error of the control system (2) is defined as:
e k + d = y k + d r k + d = i = 1 n α i y k + d i + j = 1 m b j u k j + b 0 u k + ω k + d r k + d f ( y , u , r , ω k )
where y is the process output vector collecting the immediate historical values, i.e. y ( y k , y k 1 , y k 2 , ) , u is the control variable vector, e is the tracking error vector, r is the set-point vector. Letting V k = i = 1 n α i y k i + j = 1 m b j u k d j r k and f 1 ( y , u , r , x ) = x V k b 0 u k , the PDF of the tracking error can be obtained from (4) as:
γ e k + q ( V k , u k , x ) = γ ω ( f 1 ( y , u , r , x ) ) | d f 1 ( y , u , r , x ) d x |
Then from (3), (4) and (5), the PDF of the tracking error becomes:
γ e k + d ( V k + d , u k , x ) = 1 2 π δ exp ( ( x V k + d b 0 u k μ ) 2 2 δ 2 )
According to the information-entropy definition (1), the information entropy of the tracking error is:
H e = γ e + d ( V k + d , u k , x ) ln γ e + d ( V k + d , u k , x ) d x
Then the objective of the MIE control is to find a control law u k to minimize H e , or to satisfy H e / u k = 0 . According to [14], the recursive control law is deduced as:
u k = u k 1 V k + d V k 1 + d b 0
Step 2: Obtain the PDF of the tracking error with the recursive control law uk.
Equation (8) can be rewritten as:
b 0 u k + V k + d = b 0 u k 1 + V k 1 + d = c
where c is a design constant that should be designed as μ to make the mean of the tracking error equal to 0, the control output becomes:
u k = c V k + d b 0
Step 3: Obtain the MIE benchmark.
Substituting (10) into (6), we can obtain the PDF of the tracking error as:
γ e k + d ( V k + d , u k , x ) = 1 2 π δ exp ( x 2 2 δ 2 )
From (7) and (11), the MIE benchmark can be deduced as:
H min = ln ( 2 π exp ( 1 ) δ )
where exp(1) is Euler's number.
Remark 1: During the delay-time, the controller with no delay-time compensation has no effect on the process output, so the system must achieve its steady state after the delay time. From (11), we can know that the steady-state tracking error e s obeys a Gaussian distribution. Then the steady-state MIE benchmark is ln ( 2 π exp ( 1 ) δ ) .

2.3. Upper Bound of the MIE Benchmark

Remark 2: The steady-state MIE benchmark of Remark 1 is obtained without using the time delay as a priori-knowledge. If the delay time is known, a tight upper bound of the MIE can be obtained.
The process (2) can also be described as:
A ( q 1 ) y k = B ( q 1 ) u k + ω k
where A ( q 1 ) = 1 α 1 q 1 α 2 q 2 α n q n and B ( q 1 ) = b 0 + b 1 q 1 + b 2 q 2 + b m q m .
Suppose the feedback control law is:
u k = C ( q 1 ) y k
From (13) and (14), we have:
y k = [ A ( q 1 ) + B ( q 1 ) C ( q 1 ) ] 1 ω k = i = 0 f i ω i
where f i (i=1,2,…) are constant coefficients.
According to the minimum-variance theory [2,16], the relationship between the minimum variance δ m v 2 and the tracking-error variance of the stochastic disturbance δ 2 is:
δ 2 i = 0 d 1 f i 2 δ 2 = δ m v 2
Then from (12) and (16), we obtained the upper bound of the MIE:
H min | u p p e r = ln 2 π exp ( 1 ) δ m v

2.4. Extension to Nonlinear Processes and Non-Gaussian Disturbance Case

Remark 3: The MIE benchmark ln ( 2 π exp ( 1 ) δ ) is also valid for nonlinear processes with non-Gaussian disturbances.
Here, we explain and prove the validity in the following two steps.
Step 1: Prove the MIE of a non-linear process is the disturbance information entropy.
Generally, a nonlinear process can be described as an autoregressive-nonlinear moving average process with exogenous inputs:
A ( q 1 ) y k = B ( q 1 ) q d g ( u k , u k 1 , u k 2 , ) + ω k
where d is the time delay, A ( q 1 ) = 1 a 1 q 1 a n q n , B ( q 1 ) = b 0 + b 1 q 1 + b m q m , ω k is a stochastic disturbance with variance δ 2 and probability distribution density function γ ω , g ( ) is a causal nonlinear function.
Denoting v t as:
v t = g ( u k , u k 1 , u k 2 , )
Equation (19) can be rewritten as:
y k = i = 1 n a i y k i + j = 0 m b j v k d j + ω k
Then the tracking error of the control system becomes:
e k + d = y k + d r k + d = i = 1 n a i y k + d i + j = 1 m b j v k j + b 0 v k + ω k + d r k + d f n ( y , v , r , ω k )
The following equation is used to solve this MIE optimization problem:
H e v k = + γ e + d ( V k + d , v k , x ) v k [ ln γ e + d ( V k + d , v k , x ) + 1 ] d x = 0
where V k = i = 1 n a i y k i + j = 1 m b j g ( u k d j ) r k . Like reference [14], the control law is given by:
v k = g ( u k , u k 1 , u k 2 , ) = c V k + d b 0
where c is a constant. With (21) and (23), we have f n 1 = x V k + d b 0 v k = x c , the probability density function of the tracking error is:
γ e k + d ( V k + d , v k , x ) = γ ω ( f n 1 ( y , v , r , x ) ) | d f n 1 ( y , v , r , x ) d x | = γ ω ( x c )
From the definition of information entropy (7), the MIE is obtained as:
H min = γ ω ( x c ) ln γ ω ( x c ) d x
The stochastic disturbance information entropy is:
H d i s t u r b α n c e = γ ω ( x ) ln γ ω ( x ) d x
and we can deduce:
H min = γ ω ( x c ) ln γ ω ( x c ) d x = γ ω ( x ) ln γ ω ( x ) d x = H d i s t u r b α n c e
Step 2: Prove the disturbance information entropy extremum is ln ( 2 π exp ( 1 ) δ )
The following work is to prove that the extremum of H d i s t u r b α n c e is ln ( 2 π exp ( 1 ) δ ) , no matter what distribution the stochastic disturbance with variance δ 2 obeys. The variance δ 2 of the disturbance is defined as:
+ x 2 γ ω ( x ) d x = δ 2
All the probability density functions should meet:
+ γ ω ( x ) d x = 1
According to the definition of H d i s t u r b α n c e , and using the variational method, we have:
δ H d i s t u r b α n c e = 0
Considering the constraints (28) and (29), the Lagrange function is defined as:
J = γ ω ( x ) ln γ ω ( x ) + λ 1 γ ω ( x ) + λ 2 x 2 γ ω ( x )
With (30) and the Euler's equation J / γ ω = 0 , we can obtain:
ln γ ω ( x ) 1 + λ 1 + λ 2 x 2 = 0
The solution of (33) is:
γ ω ( x ) = exp ( λ 1 1 ) exp ( λ 2 x 2 )
Substituting (34) into the constraints (28) and (29), we have:
{ λ 2 = 1 2 δ 2 exp ( λ 1 1 ) = 2 2 π δ 2
Substituting (35) into (34), the probability distribution density function is:
γ ω ( x ) = 1 2 π δ exp ( x 2 2 δ 2 )
So, the disturbance entropy extremum is obtained as:
H d i s t u r a n c e | e x t r e m u m = ln ( 2 π exp ( 1 ) δ )
It is equal to the MIE of linear process with Gaussian disturbance.

3. MIE Performance Assessment Index

For the entropy-based performance assessment, the MIE index η is defined as:
η = exp( H m i n ) exp ( H α c t )
where Hact is the information entropy of the tracking error.
This MIE index is easily understandable, meaning clear and succinct. It compares the current information entropy of the tracking error with the information entropy under the MIE control. In the meaning of the MIE, the closer the index is to 1, the better the control performance is.
The Hmin is a slack information entropy upper bound. If the delay is known as a prior-knowledge, a tight minimum information entropy upper bound H min | upper will be obtained. In this case, the MIE performance index is defined as:
η u p p e r = exp ( H min | upper ) exp ( H act )
Compared to the Harris index, the advantages of the new CPA index are as follows:
(1)
If the upper bound of the MIE is ln ( 2 π exp ( 1 ) δ mv ) , which is selected as the performance benchmark to assess the control performance, the new CPA index will have the similar computational complexity and assessment result with the Harris index.
(2)
If the MIE is ln ( 2 π exp ( 1 ) δ ) , which is selected as the performance benchmark to assess the control performance, the delay need not be obtained as a prior knowledge. So, it is easier to be used than the Harris index in this case.
(3)
The new CPA index can be used in non-linear processes and non-Gaussian disturbances case.

3.1. Information Entropy Calculation

Before calculating the MIE of the tracking error, the PDF should be calculated.
The approximation of the tracking error PDF defined on [ p , q ] can be represented as:
γ ( e , u ) = i = 1 n ρ i ( u ) S i ( e ) + ε
where S i ( e ) represents the ith basic function, ρ i ( u ) is the ith weight, ε represents the approximation error.
The weight ρ i ( u ) estimation can be used as the least squares polynomial approximation, namely B-spline approximation [17]. Many similar parametric estimation methods can be used, and the difference among them is the selection of basic function. There are also nonparametric estimation methods to calculated the information entropy [18]. In addition, bias correction procedures to obtain accurate estimates of the information conveyed by spike trains can be used to calculate the information entropy [19,20].

3.2. Hmin Estimation

From Remark 1, the MIE of the tracking error depends on the stochastic disturbance variance when the stochastic disturbance obeys Gaussian distribution, so the disturbance estimation, especially its variance, is needed.
The estimation of the noise sequence is important for the MIE estimation. In general, the relationship between the tracking error and the stochastic disturbance is established. Then, by reversing the process, the stochastic disturbance can be viewed as the output of the filtering, whose input is the tracking error. The filtering can be chosen as a time-series modeling. If the residuals of the modeling are “white”, they can be viewed as the estimated stochastic disturbance. Depending on the data, an AR, ARMA or Kalman filter can be used to estimate the white noise [21]. The estimation of white noise is known as “whitening”.
After the stochastic disturbance variance is estimated, the minimum variance can be obtained by (16) with the known delay. In addition, there are also some other methods to estimate the minimum variance, such as the processes and disturbances completely identification method, the filtering and correlation analysis method [21], the recursive least squares method [22]. With the estimation of the minimum variance, the upper bound of the MIE can be obtained by (17).

4. MIE Based CPA Procedure

4.1. CPA under Steady State

Actual performance assessment can be divided into two situations: 1) delay is unknown; 2) delay is known. The traditional CPA method cannot achieve the performance assessment in the first case. But, the MIE-based CPA can achieve the performance assessment in both cases. The MIE-based CPA method is given as follows:
When the delay is unknown, the steps of the MIE-based CPA index estimating procedure under steady state are summarized as below:
Step 1. Get the tracking error from the set-points and the process outputs.
Step 2. Calculate the tracking error PDF γ from (40), which can be canceled when using the nonparametric information entropy estimation method.
Step 3. Calculate the actual tracking error information entropy H act from (1) and the PDF γ.
Step 4. Estimate the stochastic disturbance ω k by “whitening”.
Step 5. Obtain the MIE Hmin from (12).
Step6. Get the MIE index η from (38).
When delay is known, a tight MIE performance index can be obtained from (39). The steps of estimating the CPA index are different in Step 5 and Step 6. They should be changed to:
Step 5. Calculate the MIE H min | upper from (17).
Step 6. Obtain the MIE index η upper from (39).

4.2. Transient CPA

In transient state, the actual tracking error contains the response of the stochastic disturbance and the response of the deterministic disturbance. The stochastic tracking error is gotten by the difference between the actual tracking error and the deterministic part of the tracking error.
The deterministic part of the tracking error is estimated by trend extraction. An efficient method of trend extraction is based on local linear fitting [23]. Besides, many filters of trend extraction such as GLAS weighted moving average filters, Henderson weighted moving average filters are represented in [24]. There are also many smoothers, such as the Savitzky-Golay (SG) filter [25,26], Hodrick-Prescott smoothers [27], Loess smoother [28] and smoothing B-spline [29] to be adopted to achieve trend extraction.
The CPA procedure for transient state is shown in Figure 1. The steps are summarized as below:
  • Step1: Estimate the deterministic tracking error by trend extraction.
  • Step2: Estimate the stochastic tracking error by the actual tracking error minus the deterministic tracking error.
  • Step3: Using the stochastic tracking error, the CPA under steady state method is selected to calculate the performance index.
From the above steps, the CPA under steady state is a special case of the transient CPA . For the real industrial stochastic control performance assessment, the CPA under transient state method can be utilized without indentifying the system state (steady state or transient state). In addition, there is a basic assumption that the disturbance obeys linear Gaussian distribution in the MIE based CPA. Though the disturbance in the industry environment is non-Gaussian, the method here is valid. The reason is that the performance benchmark ln ( 2 π exp ( 1 ) δ ) or ln ( 2 π exp ( 1 ) δ mv ) is still an ideal information entropy benchmark with the non-Gaussian disturbance.
Figure 1. The procedure of the transient CPA.
Figure 1. The procedure of the transient CPA.
Entropy 15 00943 g001

5. Case Study

5.1. Case 1: CPA under Steady State

In this section, a simple example is presented to validate the effectiveness of the MIE-based CPA under steady state. Consider a SISO process:
y k = 0.08 q 3 ( 1 0.92 q 1 ) u k + 1 ( 1 0.92 q 1 ) ω t
Figure 2. (a)The tracking error; (b) the PDF.
Figure 2. (a)The tracking error; (b) the PDF.
Entropy 15 00943 g002
It is controlled by a PI controller k c ( 1 + 1 τ i s ) with k c = 3.33 and τ i = 6.94 . The stochastic disturbance ω k obeys Gaussian distribution N ( 0 , 0.02 ) . The sample time is 1s. The tracking error and the PDF are shown in Figure 2. In the PDF sub-figure, the two PDFs (blue line and green line) correspond to two performance benchmarks (the MIE benchmark and the upper bound of the MIE benchmark). Performance assessment is a process to measure the distance between the benchmark PDF and the tracking error PDF. Through entropy, this distance can be given to achieve CPA. The upper bound of the MIE benchmark is equal to the minimum variance benchmark. It also can be obtained from Table 1 by the two performance indexes. The MIE-based CPA procedure under steady state is utilized to achieve the CPA. Using the nonparametric estimation method, the actual information entropy is calculated as 0.01385. The calculation result is shown in Table 1. From this table, the MIE based CPA procedure under steady state is validate to be an effective CPA method. Using the MIE benchmark, the effective CPA can be achieved without using delay.
Table 1. CPA results comparison (Actual Entropy is 0.01385, variance is 0.0642).
Table 1. CPA results comparison (Actual Entropy is 0.01385, variance is 0.0642).
MethodBenchmarkPerformance Index
NameValueNameValue
MIE based CPA (Time delay is known)Upper bound of MIE-0.5602MIE index0.5632
MIE based CPA (Time delay is unknown)MIE-0.493MIE index0.6024
nimum-variance-based CPAMinimum variance0.0362Harris index0.5639

5.2. Case 2: CPA under Transient State

Several simulation examples [30,31], shown in Table 2, are used to verify the effectiveness of the transient CPA method. The disturbance α k of all examples is a white noise with zero mean and variance 0.2. With the MIE CPA procedure, the performance of all the examples is assessed.
Generally, for a given control system, stochastic performance assessment results should be the same, no matter it is obtained from the steady-state data or the transient data. To test the effectiveness of the transient CPA procedure, the MIE-based transient CPA results of the proposed method are compared with the MIE-based CPA under steady-state results. Comparison results are shown in Figure 3, Figure 4 and Figure 5. By comparison, absolute error (between transient CPA and steady-state CPA) is at the level of 10−2 in Figure 5, so the transient CPA results have little difference with the steady-state CPA results. It indicates the effectiveness of the transient CPA procedure. For example 2, the actual information entropy with different states is different from each other in Figure 3, and the upper bound of the MIE is also different under different states in Figure 4. Although different calculation processes with different states data, the transient CPA results have little difference from the steady-state CPA results in Figure 5. It indicates the effectiveness of the transient CPA procedure. From any other example, the same conclusion can be obtained.
Table 2. Simulation Examples.
Table 2. Simulation Examples.
Number of ExamplePlantControllerDisturbance
1 0.1 q 3 1 0.8 q 1 6.53 9.236 q 1 + 3.357 q 2 1 q 1 α k
2 0.1 q 6 1 0.8 q 1 8.21 13.7 q 1 + 5.95 q 2 1 q 1 α k
3 0.0891 q 12 1 0.8669 q 1 1.84 3.38 q 1 + 1.54 q 2 1 q 1 α k
4 0.5108 q 28 1 0.9601 q 1 0.068 + 0.0021 q 1 1 q 1 0.44 0.03 1 + 0.03 q 1 1 q 1 α k
5 0.2412 e 28.6 s 25.6 s + 1 1.89 + 0.075 s α k
6 0.1859 e 43.6 s 20.58 s + 1 1.89 + 0.075 s α k
7 0.1608 e 46.8 s 17.85 s + 1 1.89 + 0.075 s α k
8 0.1507 e 61.5 s 17.3 s + 1 1.89 + 0.075 s α k
Figure 3. Comparison of the entropy estimations of the tracking error.
Figure 3. Comparison of the entropy estimations of the tracking error.
Entropy 15 00943 g003
Figure 4. Comparison of upper bound of the MIE.
Figure 4. Comparison of upper bound of the MIE.
Entropy 15 00943 g004
Figure 5. Comparison of the MIE index.
Figure 5. Comparison of the MIE index.
Entropy 15 00943 g005

5.3. Case3: CPA for Nonlinear Non-Gaussian Case

In this section, a nonlinear case is provided to demonstrate the methodology outlined in this paper. Consider a nonlinear system, which can be represented by a second-order Volterra series as:
y t = 0.2 u t 3 + 0.3 u t 4 + u t 5 + 0.8 u t 3 2 + 0.8 u t 3 u t 4 0.7 u t 4 2 0.5 u t 5 2 0.5 u t 3 u t 5 + ω t
A proportional integral (PI) controller u t = 0.3 0.2 q 1 1 q 1 e t is used for different disturbance distributions (Weibull distribution, Beta distribution and Gaussian distribution). The comparison of the CPA results is shown in Table 3. The traditional variance-based CPA method is used when the disturbance ω t obeys Gaussian distribution. According to the variance-based CPA method, the Harris index is 0.8023 which indicates the control system has good stochastic performance. If the ω t obeys non-Gaussian distribution, the traditional variance-based method cannot be utilized, but the entropy-based CPA method can be used to achieve performance assessment. For a Weibull distribution and Beta distribution, the entropy-based CPA results also represent good stochastic performance. For a given control system, the CPA results with different disturbances should be consistent. From the MIE index values and the Harris index value in Table 3, similar CPA results can be obtained. This indicates the effectiveness of the entropy-based CPA method for nonlinear process and non-Gaussian disturbance.
Table 3. CPA results comparison of nonlinear non-Gaussian case.
Table 3. CPA results comparison of nonlinear non-Gaussian case.
MethodItemDisturbution of Disturbance ω t
Gaussian Distribution with Mean 0 and Variance 0.1 Weibull Distribution with A=0.6 B=2Beta Distribution with λ = 3
Entropy-based Actual Entropy0.34930.3164-0.3655
Benchmark (MIE)0.14980.1484-0.1566
MIE index0.81910.84530.8115
Variance-basedActual variance0.1239--
Minimum variance0.0994--
Harris index0.8023--

6. MIE-Based CPA of an Industrial Example

In order to illustrate the above performance assessment procedure, an industrial data set from the main steam pressure control system of a 1,000MW power unit is used. This control system is an important part of the boiled-turbine system (BTS) [32,33]. The fuel-pressure path is considerably slower than the valve-power path (especially the power of the high-pressure turbine) and the two paths are coupled [34]. As a result, main steam pressure fluctuation is common. The main steam pressure is an important embodiment of steam quality. So its stochastic performance assessment is important for BTS.
Figure 6. Estimation of the stochastic disturbance.
Figure 6. Estimation of the stochastic disturbance.
Entropy 15 00943 g006
The sample data was acquired from 21:00 on March 5th to 2:00 on March 6th, 2011. Sampling interval is 3 s. There are 6,001 samples. The main steam pressure and its set-point are given in Figure 6a. The tracking error is shown in Figure 6b. The actual information entropy is calculated as Hact ≈ −3.509 by a non-parameter estimator [18]. The trend of the tracking error is obtained by Hodrick-Prescott smoother [27]. Then, the stochastic error is estimated and shown in Figure 6c. The tracking error is fit and adequately modeled by AR (30) model [21]. The variance of the stochastic disturbance is 2.2756 × 10−5 by “whitening”. The disturbance distribution is plotted in Figure 6(d). From Figure 6d, we can find the disturbance obeys non-Gaussian distribution, so the entropy-based transient CPA should be chosen. With (12), the MIE is −3.926. Then, the stochastic performance index is obtained as 0.6589 by (40). Because the disturbance obeys non-Gaussian distribution, strictly speaking, the variance-based CPA method can be used. But, the disturbance distribution is approximately symmetrical, the minimum-variance-based CPA result can be given for reference. Using the minimum variance benchmark (the delay is 34 sample intervals) with the estimated stochastic error, the Harris index is 0.6612. The two performance assessment results are similar, with the two methods. When the CAP uses the minimum variance index, the delay as a priori is necessary to be estimated. However, the delay is not the necessary priori-knowledge for the MIE-based CPA. This is a significant advantage. It will make the MIE index being widely applied in the actual industrial process by the engineers.

7. Conclusions

In this paper, a MIE-based CPA method is developed. The concept of information entropy is introduced to CPA. The MIE benchmark is presented by the MIE optimal control in a linear process and Gaussian disturbance. Then this benchmark is extended to nonlinear processes and non-Gaussian disturbance cases. If the delay is unknown, the MIE performance index is defined. If the time delay is known, a tight upper bound of MIE is used as a performance benchmark to assess the stochastic control performance. For engineering applications, a formal procedure is presented based on this performance index. This procedure only utilizes routine operating data no matter whether it is steady state data or transient data. The effectiveness of the CPA procedures is tested by many simulation examples. To show that this CPA method can be easily used in the real industrial system, the main steam pressure system in a 1,000MW power unit is used to achieve CPA. Of course, the extension of the MIE performance assessment to MIMO systems still has much work to do. Utilizing the concept of the information entropy, evaluating the performance of a specific controller or a control structure, such as a PID controller, the predictive controller, the cascade control structure, etc. is also a meaningful task.

Acknowledgments

This work was supported by the National Basic Research Program of China (973 Program) (2012CB215203, 2011CB710706), National Natural Science Foundation of China (NSFC) (61203107) and the Fundamental Research Funds for the Central Universities (12QX19), Joint Project With Beijing Education Committee.

References

  1. Hugo, A.J. Process controller performance monitoring and assessment. Control. Arts Inc. 2001. Available on line: http://www.controlarts.com/ (accessed on 17 September 2011). [Google Scholar]
  2. Harris, T.J. Assessment of control loop performance. Can. J. Chem. Eng. 1989, 67, 856–861. [Google Scholar] [CrossRef]
  3. Harris, T.; Seppala, C.; Desborough, L. A review of performance monitoring and assessment techniques for univariate and multivariate control systems. J. Process Contr. 1999, 9, 1–17. [Google Scholar] [CrossRef]
  4. Ko, B.S.; Edgar, T.F. Performance assessment of cascade control loops. AICHE J. 2000, 46, 281–291. [Google Scholar] [CrossRef]
  5. Tyler, M.; Morari, M. Performance assessment for unstable and nonminmum-phase systems. In Preprints IFAC Workshop On-Line Fault Detection Supervision Chemical Process Industries; Pergamon: Newcastle upon Tyne, UK, 1995. [Google Scholar]
  6. Grimble, M. Restricted structure control loop performance assessment for pid controllers and state-space systems. Asian J. Control 2003, 5, 39–57. [Google Scholar] [CrossRef]
  7. Julien, R.H.; Foley, M.W.; Cluett, W.R. Performance assessment using a model predictive control benchmark. J. Process. Contr. 2004, 14, 441–456. [Google Scholar] [CrossRef]
  8. Bezergianni, S.; Georgakis, C. Controller performance assessment based on minimum and open-loop output variance. Control. Eng. Pract. 2000, 8, 791–797. [Google Scholar] [CrossRef]
  9. Grimble, M. Controller performance benchmarking and tuning using generalised minimum variance control. Automatica 2002, 38, 2111–2119. [Google Scholar] [CrossRef]
  10. Desborough, L.; Harris, T. Performance assessment measures for univariate feedforward/feedback control. Can. J. Chem. Eng. 1993, 71, 605–616. [Google Scholar] [CrossRef]
  11. McNabb, C.A.; Qin, S.J. Projection based MIMO control performance monitoring: I—Covariance monitoring in state space. J. Process. Contr. 2003, 13, 739–757. [Google Scholar] [CrossRef]
  12. Yu, J.; Qin, S.J. Statistical MIMO controller performance monitoring. Part I: Data-driven covariance benchmark. J. Process. Contr. 2008, 18, 277–296. [Google Scholar] [CrossRef]
  13. Yu, J.; Qin, S.J. Statistical MIMO controller performance monitoring. Part II: Performance diagnosis. J. Process. Contr. 2008, 18, 297–319. [Google Scholar] [CrossRef]
  14. Hong, Y.; Hong, W. Minimum entropy control of closed-loop tracking errors for dynamic stochastic systems. IEEE T. Automat. Contr. 2003, 48, 118–122. [Google Scholar] [CrossRef]
  15. Probability, Random Variables, and Stochastic Processes, 4th Ed.; Papoulis, A.; Pillai, S. (Eds.) McGraw Hill Higher Education: New York, NY, USA, 2002.
  16. Joe Qin, S. Control performance monitoring—A review and assessment. Comput. Chem. Eng. 1998, 23, 173–186. [Google Scholar] [CrossRef]
  17. Bounded Dynamic Stochastic Systems: Modelling and Control; Wang, H. (Ed.) Springer Verlag: London, UK, 2000.
  18. Information Theoretic Learning: Rényi's Entropy and Kernel Perspectives; Principe, J.C. (Ed.) Springer: Berlin, Germany, 2010.
  19. Panzeri, S.; Senatore, R.; Montemurro, M.A.; Petersen, R.S. Correcting for the sampling bias problem in spike train information measures. J. Neurophysiol. 2007, 98, 1064–1072. [Google Scholar] [CrossRef] [PubMed]
  20. Panzeri, S.; Treves, A. Analytical estimates of limited sampling biases in different information measures. Network—Comp. Neural. 1996, 7, 87–107. [Google Scholar] [CrossRef]
  21. Performance Assessment of Control Loops: Theory and Applications; Huang, B.; Shah, S.L. (Eds.) Springer Verlag: London, UK, 1999.
  22. Lynch, C.B.; Dumont, G.A. Control loop performance monitoring. IEEE Trans. Contr. Syst. Technol. 1996, 4, 185–192. [Google Scholar] [CrossRef]
  23. Charbonnier, S.; Garcia-Beltan, C.; Cadet, C.; Gentil, S. Trends extraction and analysis for complex system monitoring and decision support. Eng. Appl. Artif. Intel. 2005, 18, 21–36. [Google Scholar] [CrossRef]
  24. Bianchi, M.; Boyle, M.; Hollingsworth, D. A comparison of methods for trend estimation. Appl. Econ. Lett. 1999, 6, 103–109. [Google Scholar] [CrossRef]
  25. Bromba, M.U.A.; Ziegler, H. Application hints for Savitzky-Golay digital smoothing filters. Anal. Chem. 1981, 53, 1583–1586. [Google Scholar] [CrossRef]
  26. Luo, J.; Ying, K.; Bai, J. Savitzky-Golay smoothing and differentiation filter for even number data. Signal.Process. 2005, 85, 1429–1434. [Google Scholar] [CrossRef]
  27. Maravall, A.; Del Rio, A. Time Aggregation and the Hodrick-Prescott Filter; Bancode España, 2001; No. 0108. [Google Scholar]
  28. Cleveland, R.B.; Cleveland, W.S.; McRae, J.E.; Terpenning, I. STL: A seasonal-trend decomposition procedure based on loess. J. Off. Stat. 1990, 6, 3–73. [Google Scholar]
  29. Reinsch, C.H. Smoothing by spline functions. II. Numer. Math. 1971, 16, 451–454. [Google Scholar] [CrossRef]
  30. Shahni, F.; Malwatkar, G.M. Assessment minimum output variance with PID controllers. J. Process. Contr. 2011, 21, 678–681. [Google Scholar] [CrossRef]
  31. Yu, Z.; Wang, J.; Huang, B.; Bi, Z. Performance assessment of PID control loops subject to setpoint changes. J. Process Contr. 2011, 21, 1164–1171. [Google Scholar] [CrossRef]
  32. Liu, H.; Li, S.; Chai, T. Intelligent decoupling control of power plant main steam pressure and power output. Int. J. Elec. Power 2003, 25, 809–819. [Google Scholar] [CrossRef]
  33. Fang, F.; Wei, L. Backstepping-based nonlinear adaptive control for coal-fired utility boiler–turbine units. Appl. Energy 2011, 88, 814–824. [Google Scholar] [CrossRef]
  34. Lu, S.; Hogg, B. Predictive co-ordinated control for power-plant steam pressure and power output. Control. Eng. Pract. 1997, 5, 79–84. [Google Scholar] [CrossRef]

Share and Cite

MDPI and ACS Style

Meng, Q.-W.; Fang, F.; Liu, J.-Z. Minimum-Information-Entropy-Based Control Performance Assessment. Entropy 2013, 15, 943-959. https://doi.org/10.3390/e15030943

AMA Style

Meng Q-W, Fang F, Liu J-Z. Minimum-Information-Entropy-Based Control Performance Assessment. Entropy. 2013; 15(3):943-959. https://doi.org/10.3390/e15030943

Chicago/Turabian Style

Meng, Qing-Wei, Fang Fang, and Ji-Zhen Liu. 2013. "Minimum-Information-Entropy-Based Control Performance Assessment" Entropy 15, no. 3: 943-959. https://doi.org/10.3390/e15030943

Article Metrics

Back to TopTop